CVE-2019-10942 is a denial-of-service flaw in the Telnet service of Siemens SCALANCE X-200, X-200IRT and X204RNA industrial switches: an unauthenticated attacker who repeatedly sends large message packages to TCP port 23 can make the switch unavailable. NVD and Siemens score it 8.6 (CWE-400). Siemens fixes X-200 in V5.2.5 and X-200IRT in V5.5.0; the X204RNA models get no fix.
Vulnerability summary
CVSS base score
8.6
High severity
EPSS score (FIRST)
1.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-10942 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| SCALANCE X-200 switch family (incl. SIPLUS NET variants) | cpe:2.3:o:siemens:scalance_x-200_firmware:*:*:*:*:*:*:*:* | All versions before V5.2.5; fixed in V5.2.5 (Siemens SSA-100232). NVD's CPE has no version limit |
| SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) | cpe:2.3:o:siemens:scalance_x-200irt_firmware:*:*:*:*:*:*:*:* | All versions before V5.5.0; fixed in V5.5.0 (Siemens SSA-100232). NVD's CPE has no version limit |
| SCALANCE X204RNA (HSR), X204RNA (PRP), X204RNA EEC (HSR), X204RNA EEC (PRP), X204RNA EEC (PRP/HSR) | cpe:2.3:o:siemens:scalance_x-200rna_firmware:*:*:*:*:*:*:*:* | All versions; no fix as of 2026-11-21, Siemens states no remediation is intended; mitigations only (Siemens SSA-100232) |
What does this mean for affected devices?
NVD carries the Siemens description: the device "contains a vulnerability that could allow an attacker to trigger a denial-of-service condition by sending large message packages repeatedly to the telnet service", and "successful exploitation requires no system privileges and no user interaction." NVD's Primary score is CVSS v3.1 8.6 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H); NVD and the Siemens CNA both use CWE-400 (uncontrolled resource consumption). The record was published on 2019-08-13 (NVD, CVE record).
How severe is CVE-2019-10942?
Siemens ProductCERT scores it the same, CVSS v3.1 8.6 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H/E:P/RL:T/RC:C), in SSA-100232. Only availability is hit, but the scope is changed, which means the impact reaches beyond the switch itself: a switch that is down also cuts off the devices that talk through it. CISA republished the advisory as ICSA-19-225-03 (Update D, 2022-02-10) with CVSS v3.0 8.6; that file names the weakness CWE-410 (insufficient resource pool) instead of CWE-400. Siemens credits Younes Dragoni and Alessandro Di Pinto of Nozomi Networks with the report.
Which switches are affected?
| Product (Siemens wording) | Affected | Fixed |
|---|---|---|
| SCALANCE X-200 switch family (incl. SIPLUS NET) | before V5.2.5 | V5.2.5 |
| SCALANCE X-200IRT switch family (incl. SIPLUS NET) | before V5.5.0 | V5.5.0 |
| SCALANCE X204RNA (HSR), X204RNA (PRP) | all versions | no fix |
| SCALANCE X204RNA EEC (HSR), EEC (PRP), EEC (PRP/HSR) | all versions | no fix |
SSA-100232 was first published on 2019-08-13. Siemens added the X-200IRT update on 2021-02-09 and the X-200 update on 2021-09-14, and on 2022-02-08 stated explicitly that the X204RNA devices get no fix. NVD's CPE entries for X-200, X-200IRT and X-200RNA firmware carry no version limit, so a CPE-only match also flags switches that already run V5.2.5 or V5.5.0.
How do you mitigate it where there is no fix?
For every affected model, including the X204RNA, Siemens lists two mitigations: restrict network access to 23/tcp on the device, and disable the Telnet service and use SSH instead. Update the X-200 and X-200IRT lines to the fixed versions; that update also closes the web server overflows CVE-2021-25668 and CVE-2021-25669 on the X-200 (V5.2.5) and requires V5.5.1 on the X-200IRT. The X204RNA is also affected by the WBM bypass CVE-2019-13933, which does have a fix. Our SCALANCE and RUGGEDCOM vulnerability guide covers the HSR and PRP models, and the input handling fix guide covers this class of bug.
CVE-2019-10942 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01361, the 72.4th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Modified; published 2019-08-13; NVD Primary CVSS v3.1 8.6 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H, v2 5.0; CWE-400 (NVD and Siemens); CPE scalance_x-200_firmware, scalance_x-200irt_firmware and scalance_x-200rna_firmware without version limits; description lists X-200 before V5.2.5, X-200IRT before V5.5.0 and five X204RNA models, all versions. — NVD
- Siemens SSA-100232 V1.4 (published 2019-08-13, updated 2022-02-08), CSAF read 2026-11-21: CVE-2019-10942 Telnet denial of service by repeated large message packages, CWE-400, CVSS v3.1 8.6 with E:P/RL:T/RC:C; fixes X-200 V5.2.5 and X-200IRT V5.5.0; five X204RNA models with no remediation; mitigations: restrict 23/tcp, disable Telnet and use SSH; credits Nozomi Networks (Younes Dragoni, Alessandro Di Pinto). — Siemens ProductCERT SSA-100232
- CISA ICSA-19-225-03 CSAF (Update D, current release 2022-02-10), read 2026-11-21: CVE-2019-10942, CVSS v3.0 8.6, CWE-410. — CISA CSAF ICSA-19-225-03
- CVE record (checked 2026-11-21): state PUBLISHED, CNA Siemens, published 2019-08-13; CNA CWE-400; no CNA CVSS metric in the record. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
- EPSS 0.01361, percentile 0.72416, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2019-10942?
V5.2.5 for the SCALANCE X-200 switch family and V5.5.0 for the X-200IRT switch family, including SIPLUS NET variants. The five SCALANCE X204RNA models (HSR, PRP and the EEC variants) have no fix (per Siemens SSA-100232).
How do I protect an X204RNA HSR or PRP switch?
Siemens recommends restricting network access to port 23/tcp and disabling the Telnet service in favour of SSH (per SSA-100232). With Telnet off, the vulnerable service is not reachable.
Can the attack change the switch configuration?
No. Siemens and NVD both score only an availability impact: the attacker can make the switch unavailable, but confidentiality and integrity impact are none. Because the scope is changed, the outage reaches beyond the switch to the devices connected through it.
Why does a scanner flag my updated X-200 switch?
NVD's CPE entries for X-200, X-200IRT and X-200RNA firmware for this CVE have no version limit, so a match on CPE alone flags every firmware version. Check the version against SSA-100232 instead: X-200 V5.2.5 and X-200IRT V5.5.0 are fixed.