CVE-2019-10935 is a code upload flaw in the SIMATIC WinCC DataMonitor web application. An authenticated attacker with network access can upload arbitrary ASPX code, affecting confidentiality, integrity and availability. NVD and Siemens score it CVSS v3.0 7.2. Siemens fixed it in WinCC V7.3 Update 19, V7.4 SP1 Update 11 and V7.5 Update 3; WinCC V7.2 and earlier and V13 have no fix.
Vulnerability summary
CVSS base score
7.2
High severity
EPSS score (FIRST)
1.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-10935 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC WinCC V7.x (DataMonitor) | cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:* | V7.2 and earlier: all versions, no fix; V7.3 before Update 19; V7.4 before V7.4 SP1 Update 11; V7.5 before Update 3 (Siemens SSA-121293) |
| Siemens SIMATIC WinCC Professional and Runtime Professional (TIA Portal V13 to V15) | cpe:2.3:a:siemens:simatic_wincc_runtime:*:*:*:*:professional:*:*:* | V13: all versions, no fix; Professional V14 before V14 SP1 Update 9, V15 before V15.1 Update 3; Runtime Professional V14 before V14.1 Update 8, V15 before V15.1 Update 3 |
| Siemens SIMATIC PCS 7 | cpe:2.3:a:siemens:simatic_pcs_7:*:*:*:*:*:*:*:* | V8.0 and earlier: all versions, no fix; V8.1 before WinCC V7.3 Update 19; V8.2 before V8.2 SP1 with WinCC V7.4 SP1 Update 11; V9.0 before V9.0 SP2 with WinCC V7.4 SP1 Update 11 |
What does this mean for affected devices?
NVD's description, from Siemens, says: "The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application." NVD's Primary score is CVSS v3.0 7.2 (CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H), with a Primary CVSS v2 6.5 (AV:N/AC:L/Au:S/C:P/I:P/A:P). NVD and Siemens both classify the flaw as CWE-434 (unrestricted upload of a file with a dangerous type) (NVD, CVE record).
What does Siemens say?
Siemens advisory SSA-121293 ("Code Upload Vulnerability in SIMATIC WinCC and SIMATIC PCS 7", V1.3, last updated 2019-10-08, first published 2019-07-09) scores it CVSS v3.0 7.2 (CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C), the same base score as NVD. It says an attacker must be authenticated with a valid user account, and that the flaw "is only relevant for scenarios where access via the web interface is feasible for an attacker while access to the directory structure is not". Siemens credits Xuchen Zhu of ZheJiang Guoli Security Technology, with coordination by CNCERT/CC.
The fixed versions are WinCC V7.3 Update 19, V7.4 SP1 Update 11 and V7.5 Update 3; WinCC Professional (TIA Portal V14) V14 SP1 Update 9 and (TIA Portal V15) V15.1 Update 3; and WinCC Runtime Professional V14.1 Update 8 and V15.1 Update 3. PCS 7 V8.1 needs WinCC V7.3 Update 19, and PCS 7 V8.2 SP1 and V9.0 SP2 need WinCC V7.4 SP1 Update 11. WinCC V7.2 and earlier, PCS 7 V8.0 and earlier, and WinCC Professional and Runtime Professional V13 have no update; for those, Siemens' only listed measure is to apply defense-in-depth, alongside its general advice to protect network access to the devices.
What does CISA say?
CISA advisory ICSA-19-192-02 (CSAF), "Siemens SIMATIC WinCC and PCS7 (Update C)", republishes Siemens' 7.2 score, CWE-434 and the same product and fix list, with revisions matching the four Siemens versions.
What should a WinCC or PCS 7 owner do?
- Find every station with WinCC DataMonitor installed and decide whether it is still needed.
- Install the WinCC or TIA Portal update for the line; move stations off WinCC V7.2 and earlier and V13, which have no fix.
- Allow the DataMonitor web application only from named clients, and review which accounts can sign in to it.
The Siemens WinCC and PCS 7 guide covers DataMonitor and the other WinCC web components. CVE-2021-40358 is the later path traversal in the WinCC web server, and CVE-2019-10916 and CVE-2019-10918 are the other 2019 WinCC flaws that need an account. The OT/ICS security guide for small manufacturers covers keeping SCADA web services off the office network.
CVE-2019-10935 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01274, a percentile of 70.0, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2019-07-11; NVD Primary CVSS v3.0 7.2 CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H and Primary CVSS v2 6.5 AV:N/AC:L/Au:S/C:P/I:P/A:P; CWE-434 (NVD and Siemens); 32 CPE entries for simatic_wincc up to 7.5, simatic_pcs_7 8.0 to 9.0, WinCC Professional and Runtime Professional 13 to 15.1. — NVD
- Siemens SSA-121293 V1.3 (PDF and text edition, read 2026-11-28): CVSS v3.0 7.2 with E:P/RL:O/RC:C; authenticated attacker; affected products, fixed updates, defense-in-depth for versions without a fix; credit to Xuchen Zhu and CNCERT/CC. — Siemens ProductCERT SSA-121293
- CISA ICSA-19-192-02 CSAF (read 2026-11-28): Update C, CVSS v3.0 7.2, CWE-434, same products and fixes. — CISA ICSA-19-192-02
- CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CWE-434, no CNA CVSS in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.01274, percentile 0.69962, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which WinCC versions fix CVE-2019-10935?
Siemens SSA-121293 lists WinCC V7.3 Update 19, V7.4 SP1 Update 11 and V7.5 Update 3, WinCC Professional V14 SP1 Update 9 and V15.1 Update 3, and WinCC Runtime Professional V14.1 Update 8 and V15.1 Update 3.
Which versions have no fix?
WinCC V7.2 and earlier, PCS 7 V8.0 and earlier, and WinCC Professional and Runtime Professional V13. For these Siemens lists defense-in-depth as the measure, so the practical fix is moving to a supported line.
Does an attacker need an account?
Yes. Siemens says the attacker has to be authenticated with a valid user account and needs network access to the DataMonitor application; NVD's vector rates the privileges required as high.
Is CVE-2019-10935 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01274 (percentile 70.0) in the 2026-11-27 dataset.