Security Advisory

CVE-2019-10916: WinCC and PCS 7 Project File SQL Injection

Last updated:
  • CVE-2019-10916

CVE-2019-10916 is an SQL injection in Siemens SIMATIC WinCC: an attacker who can get at a WinCC project file could run arbitrary system commands with the privileges of the local database server. It affects WinCC V7.x, PCS 7 up to V9.0, WinCC (TIA Portal) and WinCC Runtime Professional V13 to V15. NVD scores it CVSS 8.8 and Siemens 9.1. Fixes include WinCC V7.4 SP1 Update 11, V7.5 Update 3 and TIA Portal V15.1 Update 3.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

1.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-10916 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC V7.x and SIMATIC PCS 7cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*WinCC V7.2 and earlier (all), V7.3 before Upd 19, V7.4 before SP1 Upd 11, V7.5 before Upd 3; PCS 7 V8.0 and earlier (all), V8.1 before WinCC V7.3 Upd 19, V8.2 before V8.2 SP1 with WinCC V7.4 SP1 Upd 11, V9.0 before V9.0 SP2 with WinCC V7.4 SP1 Upd 11. PCS 7 V8.1: WinCC V7.3 Upd 19; PCS 7 V8.2 and V9.0: WinCC V7.4 SP1 Upd 11; WinCC V7.3 Upd 19, V7.4 SP1 Upd 11, V7.5 Upd 3; WinCC (TIA Portal) V14 SP1 Upd 9 and V15.1 Upd 3; WinCC Runtime Professional V14.1 Upd 8 and V15.1 Upd 3. No update for PCS 7 V8.0 and earlier, WinCC V7.2 and earlier, WinCC (TIA Portal) and Runtime Professional V13: apply the workarounds
Siemens SIMATIC WinCC (TIA Portal) and WinCC Runtime Professional V13 to V15cpe:2.3:a:siemens:simatic_wincc_runtime_professional:*:*:*:*:*:*:*:*WinCC (TIA Portal) V13 (all), V14 before V14 SP1 Upd 9, V15 before V15.1 Upd 3; Runtime Professional V13 (all), V14 before V14.1 Upd 8, V15 before V15.1 Upd 3

What does this mean for affected devices?

NVD's description, from Siemens, says: "An attacker with access to the project file could run arbitrary system commands with the privileges of the local database server. The vulnerability could be exploited by an attacker with access to the project file." NVD's Primary scores are CVSS v3.1 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 9.0, with CWE-89 (SQL injection), the same CWE Siemens and CISA use. NVD's CPEs cover simatic_wincc up to 7.5, simatic_pcs_7 up to 9.0, WinCC (TIA Portal) 13.0 to 15.0 and WinCC Runtime Professional (NVD, CVE record).

Why do NVD and Siemens score it differently?

Siemens scores it CVSS v3.0 9.1 (CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C): high privileges required, but a changed scope. NVD scores low privileges and unchanged scope, which gives 8.8. Both rate confidentiality, integrity and availability impact as high.

What does Siemens say?

Siemens advisory SSA-697412 (V1.4, published 2019-05-14, last updated 2019-10-08) covers CVE-2019-10916 together with CVE-2019-10917 (a denial of service while a project file is loaded) and CVE-2019-10918 (command execution over DCOM). Vladimir Dashchenko and Sergey Temnikov of Kaspersky Lab ICS CERT reported CVE-2019-10916. The fixes are WinCC V7.3 Upd 19, V7.4 SP1 Upd 11 and V7.5 Upd 3; PCS 7 V8.1 with WinCC V7.3 Upd 19, PCS 7 V8.2 and V9.0 with WinCC V7.4 SP1 Upd 11; WinCC (TIA Portal) V14 SP1 Upd 9 and V15.1 Upd 3; and Runtime Professional V14.1 Upd 8 and V15.1 Upd 3. PCS 7 V8.0 and earlier, WinCC V7.2 and earlier, and WinCC (TIA Portal) and Runtime Professional V13 get no update. For them, and in general, Siemens lists three workarounds: apply defense in depth, enable "Encrypted communication" in WinCC and PCS 7, and only open project files from trusted locations.

What does CISA say?

CISA advisory ICSA-19-134-08 (CSAF), "Siemens SIMATIC PCS7, WinCC, TIA Portal (Update D)", republishes the 9.1 score, CWE-89 and the same product list and updates.

What should an owner do?

  1. Install the fixed Update for each WinCC line, or the WinCC level Siemens names for each PCS 7 release.
  2. Treat project files as sensitive: store and transfer them only through controlled locations, and never open a project from an unknown source.
  3. Restrict who can log on to the WinCC database server and engineering stations.

The Siemens WinCC and PCS 7 guide groups this flaw with the other database and project-file paths to code execution. CVE-2019-10918 is the DCOM flaw fixed by the same updates, and CVE-2010-2772 is the hard-coded WinCC SQL Server password. The KEV and EPSS prioritization guide explains how to rank a flaw like this against network-reachable ones.

CVE-2019-10916 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01541, a percentile of 75.3, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is SQL injection. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2019-05-14; NVD Primary CVSS v3.1 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H and CVSS v2 9.0 AV:N/AC:L/Au:S/C:C/I:C/A:C; CWE-89; CPEs simatic_wincc up to 7.5, simatic_pcs_7 up to 9.0, WinCC (TIA Portal) 13.0 to 15.0, WinCC Runtime Professional. — NVD
  • Siemens SSA-697412 V1.4 PDF (read 2026-11-28): affected and fixed versions; CVSS v3.0 9.1 CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C; workarounds defense in depth, Encrypted communication, open project files only from trusted locations; credit Kaspersky Lab ICS CERT. — Siemens ProductCERT SSA-697412
  • CISA ICSA-19-134-08 (Update D) CSAF (read 2026-11-28): CVSS v3.0 9.1, CWE-89, same products. — CISA ICSA-19-134-08
  • CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CWE-89. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01541, percentile 0.75268, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-697412: Multiple Vulnerabilities in SIMATIC WinCC, WinCC Runtime, PCS 7, TIA Portal
  3. CISA ICSA-19-134-08: Siemens SIMATIC PCS7, WinCC, TIA Portal
  4. CISA ICSA-19-134-08 CSAF (machine-readable advisory)
  5. CVE record CVE-2019-10916 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

What does an attacker need to exploit CVE-2019-10916?

Access to the WinCC project file. Siemens says an attacker with that access could run arbitrary system commands with the privileges of the local database server.

Which versions have no fix?

Siemens SSA-697412 lists no update for PCS 7 V8.0 and earlier, WinCC V7.2 and earlier, and WinCC (TIA Portal) and WinCC Runtime Professional V13. For those it points to defense in depth, Encrypted communication and opening project files only from trusted locations.

Why is the NVD score lower than Siemens' score?

Siemens scores high privileges with a changed scope (9.1). NVD scores low privileges with unchanged scope (8.8).

Is CVE-2019-10916 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01541 (percentile 75.3) in the 2026-11-27 dataset.