CVE-2019-10918 lets an attacker who has network access to the DCOM interface of Siemens SIMATIC WinCC or PCS 7, and a low-privileged user account, execute arbitrary commands with SYSTEM privileges on the station. WinCC V7.x, PCS 7 up to V9.0, WinCC (TIA Portal) and WinCC Runtime Professional V13 to V15 are affected. NVD and Siemens both score it CVSS 8.8. Fixes include WinCC V7.4 SP1 Update 11 and V7.5 Update 3.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
1.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-10918 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC WinCC V7.x and SIMATIC PCS 7 | cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:* | WinCC V7.2 and earlier (all), V7.3 before Upd 19, V7.4 before SP1 Upd 11, V7.5 before Upd 3; PCS 7 V8.0 and earlier (all), V8.1 before WinCC V7.3 Upd 19, V8.2 and V9.0 before WinCC V7.4 SP1 Upd 11. No update for WinCC V7.2 and PCS 7 V8.0 or earlier: apply the workarounds |
| Siemens SIMATIC WinCC (TIA Portal) and WinCC Runtime Professional V13 to V15 | cpe:2.3:a:siemens:simatic_wincc_runtime_professional:*:*:*:*:*:*:*:* | WinCC (TIA Portal) V13 (all, no update), V14 before V14 SP1 Upd 9, V15 before V15.1 Upd 3; Runtime Professional V13 (all, no update), V14 before V14.1 Upd 8, V15 before V15.1 Upd 3 |
What does this mean for affected devices?
NVD's description, from Siemens, says that an authenticated attacker with network access to the DCOM interface "could execute arbitrary commands with SYSTEM privileges", and that "successful exploitation requires authentication with a low-privileged user account and no user interaction". NVD's Primary scores are CVSS v3.1 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 9.0. NVD records its weakness as NVD-CWE-Other; Siemens and CISA use CWE-749 (exposed dangerous method or function) (NVD, CVE record).
What does Siemens say?
Siemens advisory SSA-697412 (V1.4, published 2019-05-14, last updated 2019-10-08) scores CVE-2019-10918 CVSS v3.0 8.8 (CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C), the same base score as NVD, and says no public exploitation was known at publication. CNCERT/CC and ChengBin Wang of ZheJiang Guoli Security Technology reported it. The advisory shares one product table with CVE-2019-10916 and CVE-2019-10917.
The fixes are WinCC V7.3 Upd 19, V7.4 SP1 Upd 11 and V7.5 Upd 3; for PCS 7, V8.1 with WinCC V7.3 Upd 19 and V8.2 and V9.0 with WinCC V7.4 SP1 Upd 11; WinCC (TIA Portal) V14 SP1 Upd 9 and V15.1 Upd 3; and Runtime Professional V14.1 Upd 8 and V15.1 Upd 3. PCS 7 V8.0 and earlier, WinCC V7.2 and earlier, and the V13 TIA Portal products have no update. Siemens' workarounds are defense in depth, enabling "Encrypted communication" in WinCC and PCS 7, and opening project files only from trusted locations.
What does CISA say?
CISA advisory ICSA-19-134-08 (CSAF), "Siemens SIMATIC PCS7, WinCC, TIA Portal (Update D)", gives CVSS v3.0 8.8 and CWE-749 with the same products, and adds CISA's standard advice to isolate control networks behind firewalls and use VPNs for remote access.
What should an owner do?
- Install the fixed Update for each WinCC line or the WinCC level named for each PCS 7 release.
- Review which Windows accounts exist on WinCC servers and clients; any account that can authenticate over the network is enough for this flaw.
- Limit DCOM and RPC traffic to the WinCC stations that need it, and enable Encrypted communication.
The Siemens WinCC and PCS 7 guide covers the database, project-file and authentication families this flaw belongs to. CVE-2019-10916 is the project-file SQL injection fixed by the same updates, and CVE-2019-10922 is the unauthenticated flaw closed by Encrypted Communication. The OT/ICS security guide for small manufacturers covers account and network hardening for SCADA hosts.
CVE-2019-10918 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01926, a percentile of 80.6, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2019-05-14; NVD Primary CVSS v3.1 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H and CVSS v2 9.0; NVD CWE NVD-CWE-Other, Siemens CWE-749; CPEs simatic_wincc up to 7.5, simatic_pcs_7 up to 9.0, WinCC (TIA Portal) 13.0 to 15.0, WinCC Runtime Professional. — NVD
- Siemens SSA-697412 V1.4 PDF (read 2026-11-28): CVSS v3.0 8.8 with E:P/RL:O/RC:C; credit CNCERT/CC and ChengBin Wang (ZheJiang Guoli Security Technology); fixed versions and workarounds shared with CVE-2019-10916. — Siemens ProductCERT SSA-697412
- CISA ICSA-19-134-08 (Update D) CSAF (read 2026-11-28): CVSS v3.0 8.8, CWE-749. — CISA ICSA-19-134-08
- CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CWE-749. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.01926, percentile 0.80572, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Does CVE-2019-10918 need credentials?
Yes, but only a low-privileged user account. Siemens says an authenticated attacker with network access to the DCOM interface could then run arbitrary commands with SYSTEM privileges, with no user interaction.
Which updates fix CVE-2019-10918?
The SSA-697412 updates: WinCC V7.3 Upd 19, V7.4 SP1 Upd 11 and V7.5 Upd 3, the matching WinCC level for PCS 7 V8.1, V8.2 and V9.0, WinCC (TIA Portal) V14 SP1 Upd 9 and V15.1 Upd 3, and Runtime Professional V14.1 Upd 8 and V15.1 Upd 3.
Who reported it?
Siemens credits CNCERT/CC and ChengBin Wang of ZheJiang Guoli Security Technology for coordinated disclosure of CVE-2019-10918.
Is CVE-2019-10918 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01926 (percentile 80.6) in the 2026-11-27 dataset.