CVE-2010-2772 is a hard-coded password flaw in Siemens SIMATIC WinCC and SIMATIC PCS 7: the SCADA software logged in to its own SQL Server database with built-in credentials that customers could not change or disable. NVD scores it CVSS v3.1 7.8. Siemens fixed it in WinCC V7.0 SP2 Update 1, which switches the database login to Windows authentication; PCS 7 users apply the same update.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
0.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2010-2772 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC WinCC | cpe:2.3:a:siemens:simatic_wincc:7.0:*:*:*:*:*:*:* | Siemens SSA-027884 and CISA: all versions before V7.0 SP2 Update 1 (7.0.2.1); NVD CPEs 6.2 and 7.0; fixed in V7.0 SP2 Update 1 and later (latest named update V7.0 SP3 Update 2) |
| Siemens SIMATIC PCS 7 | cpe:2.3:a:siemens:simatic_pcs_7:7.1:sp1:*:*:*:*:*:* | Siemens SSA-027884 and CISA: versions before V7.1 SP2; NVD CPEs 6.0, 6.1, 7.0, 7.0 SP1, 7.1, 7.1 SP1; Siemens says PCS 7 users should apply the WinCC update |
What does this mean for affected devices?
NVD's description reads: "Siemens Simatic WinCC and PCS 7 SCADA system uses a hard-coded password, which allows local users to access a back-end database and gain privileges, as demonstrated in the wild in July 2010 by the Stuxnet worm, a different vulnerability than CVE-2010-2568." NVD's Primary scores are CVSS v3.1 7.8 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 6.9 (AV:L/AC:M/Au:N/C:C/I:C/A:C), with CWE-798. MITRE assigned the record with no CNA score; NVD published it on 2010-07-22 (NVD, CVE record).
Why do Siemens and CISA score it higher than NVD?
Siemens ProductCERT advisory SSA-027884 (V1.4, 2012-07-23) scores the issue CVSS v2 10.0 base, 8.3 overall, with a network vector, because the pre-defined credentials "could be used to gain remote access to the database server with administrative privileges". CISA's ICSA-12-205-01 (CSAF), "Siemens WinCC Insecure SQL Server Authentication", uses the same 10.0 score and CWE-798. NVD scores the local path that its description names. Siemens says the update for this flaw shipped in 2010, and the 2012 advisory documents it.
Which products are affected?
Per Siemens and CISA: SIMATIC WinCC versions before V7.0 SP2 Update 1 (7.0.2.1) and SIMATIC PCS 7 versions before V7.1 SP2. The NVD CPE list names WinCC 6.2 and 7.0 and PCS 7 6.0, 6.1, 7.0, 7.0 SP1, 7.1 and 7.1 SP1. WinCC is the HMI and SCADA layer of many Siemens plants, and PCS 7 is the Siemens distributed control system built on it.
How do I fix it?
Install SIMATIC WinCC V7.0 SP2 Update 1 or later; Siemens names V7.0 SP3 Update 2 as the latest update and says SIMATIC PCS 7 users should apply it too. The update "removes the pre-defined credentials and switches to Windows authentication mechanisms". CISA adds the usual network controls: keep WinCC and PCS 7 stations behind firewalls, away from the business network and the internet, and use VPN-based remote access only where needed.
CISA's earlier ICSA-10-201-01C covers the July 2010 USB malware that targeted WinCC and STEP 7, and the Windows shortcut flaw CVE-2010-2568 it used; that Windows CVE is in the KEV catalog (added 2022-09-15), while CVE-2010-2772 is not.
The hard-coded credentials guide explains how to find and remove fixed credentials, and the OT/ICS security guide for small manufacturers covers segmenting SCADA stations. CVE-2011-4509 is a default password in Siemens SIMATIC HMI panels and WinCC flexible runtime.
CVE-2010-2772 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0055, a percentile of 39.4, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS); the KEV and EPSS prioritization guide explains how to weigh those two signals.


Evidence
- NVD (read 2026-11-28): status Modified; published 2010-07-22; NVD Primary CVSS v3.1 7.8 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H and v2 6.9 AV:L/AC:M/Au:N/C:C/I:C/A:C; CWE-798; CPEs simatic_wincc 6.2, 7.0; simatic_pcs_7 6.0, 6.1, 7.0, 7.0 sp1, 7.1, 7.1 sp1. — NVD
- Siemens SSA-027884 V1.4 (2012-07-23, read 2026-11-28): WinCC < V7.0 SP2 Update 1 (7.0.2.1), PCS7 < V7.1 SP2; pre-defined SQL server credentials cannot be changed; CVSS v2 base 10.0, overall 8.3; fix V7.0 SP2 Update 1, latest V7.0 SP3 Update 2; update switches to Windows authentication; addressed by a software update in 2010. — Siemens ProductCERT
- CISA ICSA-12-205-01 web page and CSAF (read 2026-11-28): CVE-2010-2772, CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C, CWE-798; WinCC older than V7.0 SP2 Update 1, PCS 7 older than V7.1 SP2; Siemens advisory SSA-027884. — CISA ICSA-12-205-01
- CISA ICSA-10-201-01C (read 2026-11-28): USB malware targeting SIMATIC WinCC and STEP 7; CVE-2010-2568 Windows shortcut flaw. — CISA ICSA-10-201-01C
- CVE record (read 2026-11-28): state PUBLISHED, assigner mitre; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28; CVE-2010-2568 is listed (dateAdded 2022-09-15). — CISA KEV
- EPSS 0.00546, percentile 0.3938, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
- NVD
- Siemens ProductCERT SSA-027884: Insecure SQL Server Authentication in SIMATIC WinCC
- CISA ICSA-12-205-01: Siemens WinCC Insecure SQL Server Authentication
- CISA ICSA-12-205-01 CSAF (machine-readable advisory)
- CISA ICSA-10-201-01C: USB Malware Targeting Siemens Control Software
- CVE record CVE-2010-2772 (CVE Services JSON)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which WinCC and PCS 7 versions are affected by CVE-2010-2772?
SIMATIC WinCC before V7.0 SP2 Update 1 (7.0.2.1) and SIMATIC PCS 7 before V7.1 SP2, per Siemens SSA-027884 and CISA ICSA-12-205-01. NVD lists WinCC 6.2 and 7.0 and PCS 7 6.0 through 7.1 SP1.
What does the Siemens fix change?
WinCC V7.0 SP2 Update 1 and later remove the pre-defined SQL Server credentials and switch the database login to Windows authentication. Siemens names V7.0 SP3 Update 2 as the latest update and tells PCS 7 users to apply it as well.
Why does NVD show 7.8 when Siemens and CISA say 10.0?
NVD scores the local attack path in its description (v3.1 7.8, v2 6.9). Siemens and CISA score a network vector, since the credentials allow remote administrative access to the database server (CVSS v2 10.0).
Is CVE-2010-2772 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0055 (percentile 39.4) in the 2026-11-27 dataset. The Windows shortcut flaw CVE-2010-2568 from the same 2010 incident is in KEV.
Questions about this page?