Security Advisory

CVE-2018-5447: Nari PCS-9611 Relay Input Validation Flaw

Last updated:
  • CVE-2018-5447

CVE-2018-5447 is an improper input validation flaw in a network service of the Nari PCS-9611 relay, a protection, control and monitoring unit used in electric power. A remote attacker without credentials may read or access system resources and disrupt the relay. NVD and CISA both score it 9.8. Nari released software version 3.14 to fix it.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

2.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-5447 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Nari (NR Electric) PCS-9611 relay, control and monitoring unitcpe:2.3:o:nrec:pcs-9611_firmware:-:*:*:*:*:*:*:*All versions before the fix (CISA ICSA-18-025-01; NVD CPE without a version range); fixed in software version 3.14 (Update A)

What does this mean for affected devices?

The CVE record from CISA says: "An Improper Input Validation issue was discovered in Nari PCS-9611 relay. An improper input validation vulnerability has been identified that affects a service within the software that may allow a remote attacker to arbitrarily read/access system resources and affect the availability of the system." NVD and CISA both map it to CWE-20 (NVD, CVE record).

How severe is CVE-2018-5447?

This is one of the cases where NVD and CISA agree. NVD's Primary CVSS v3.0 score is 9.8 with CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, the same vector CISA published, and its CVSS v2 score is 10.0. CISA's risk note goes a step further than the CVE text and says successful exploitation could give a remote attacker arbitrary read and write abilities on the system. In a substation, a relay is the device that trips the breaker, so a flaw that reaches its availability touches protection itself.

Which PCS-9611 versions are affected and what fixes it?

CISA's ICSA-18-025-01 was released on 2018-01-25 with all versions of the PCS-9611 listed as affected. Update A on 2018-05-03 added the fix: Nari released version 3.14 of the software and asks customers to get it through NR Electric's service and sales contacts. CISA lists the Energy sector, deployment in Asia and a headquarters in China; the flaw was reported by Kirill Nesterov and Alexey Osipov of Kaspersky Lab. NVD's CPE carries no version range, so asset inventories have to match on the installed software version against 3.14. Until the update is in, CISA's advice applies: no internet exposure, a firewall between the relay network and the business network, and remote access only over an up-to-date VPN. Utilities that run the relay inside a bulk electric system will handle the update under NERC CIP-007 patch management; for smaller sites the OT security guide for small manufacturers covers the same network basics, and the enterprise patch management guide the update cycle.

Other protection relay pages: CVE-2021-27426 (GE UR relay factory mode) and CVE-2023-2265 (SEL-411L web HMI).

Is CVE-2018-5447 exploited?

CVE-2018-5447 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit. FIRST EPSS gives it 0.02414, the 84.86th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2018-01-25; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE-20 (NVD Primary and ICS-CERT); CPE nrec:pcs-9611_firmware with no version range. — NVD
  • CISA ICSA-18-025-01 CSAF (released 2018-01-25, Update A 2018-05-03, read 2026-11-27): PCS-9611 relay, all versions; CWE-20; CISA CVSS v3 9.8 with the same vector; Nari released version 3.14 of the software; Energy sector, deployed in Asia, HQ China; reported by Kirill Nesterov and Alexey Osipov of Kaspersky Labs; no known public exploits. — CISA ICSA-18-025-01
  • CISA advisory page (read 2026-11-27 via a page fetch): title Nari PCS-9611 (Update A); all versions of the relay, a control and monitoring unit, affected; version 3.14 resolves the vulnerability. — CISA
  • CVE record (read 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2018-01-25; affected Nari PCS-9611; no CNA CVSS in the record. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.02414, percentile 0.84861, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-18-025-01: Nari PCS-9611 (Update A) (CSAF)
  3. CISA ICSA-18-025-01 advisory page
  4. CVE.org record CVE-2018-5447
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which PCS-9611 version fixes CVE-2018-5447?

Software version 3.14. CISA added the fix to ICSA-18-025-01 in Update A on 2018-05-03; the original advisory listed all versions of the relay as affected. NR Electric distributes the update through its service and sales contacts.

What does an attacker gain from CVE-2018-5447?

The CVE text says a remote attacker may read or access system resources and affect the relay's availability. CISA's risk evaluation describes arbitrary read and write abilities on the system. No credentials or user action are needed.

How should a utility protect PCS-9611 relays until they are updated?

CISA advises keeping the relays off the internet, behind firewalls and separate from the business network, with remote access only over an up-to-date VPN, and doing an impact analysis before changing anything on a protection system.

Is CVE-2018-5447 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02414 (84.86th percentile) in the 2026-11-26 dataset.