Security Advisory

CVE-2017-7905: GE Multilin Relay Weak Password Encryption

Last updated:
  • CVE-2017-7905

CVE-2017-7905 is a weak password encryption flaw in GE Multilin protective relays: user passwords are encrypted with a non-random initialization vector, and the ciphertext can be read from the front panel or with Modbus commands, which opens it to dictionary attacks. NVD scores it 9.8, CISA 8.1. GE released fixed firmware for each relay family.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2017-7905 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
GE Multilin SR 750 / 760 Feeder Protection Relaycpe:2.3:o:ge:multilin_sr_750_feeder_protection_relay_firmware:*:*:*:*:*:*:*:*firmware before 7.47; fixed in 7.47 (CISA ICSA-17-117-01B; the NVD CPE range ends at 5.02)
GE Multilin SR 469 Motor / 745 Transformer / 489 Generator / 369 Motor Protection Relaycpe:2.3:o:ge:multilin_sr_469_motor_protection_relay_firmware:*:*:*:*:*:*:*:*469 and 745 before 5.23, 489 before 4.06, 369 before 3.63; fixed in those versions (CISA ICSA-17-117-01B)
GE Multilin Universal Relay (UR)cpe:2.3:o:ge:multilin_universal_relay_firmware:*:*:*:*:*:*:*:*6.0 and earlier per NVD; GE released updates in UR firmware 5.83, 5.92 and 6.02 to 6.05; UR 7.xx not affected (CISA ICSA-17-117-01B)
GE Multilin URplus (D90, C90, B95)cpe:2.3:o:ge:multilin_urplus_d90_firmware:-:*:*:*:*:*:*:*all versions at release; CISA lists URplus 1.86 and 1.92 and B95Plus 1.03 as the versions receiving firmware updates in July 2017
GE MM300, MM200, MX350, RPTCS, 350, 345, 339 relays and T1000 switch—added in CISA Update B; fixed in MM300 1.71, MM200 1.25, MX350 1.27, RPTCS 1.29, 350/345/339 2.30, T1000 03A02 (not in the NVD configuration)

What does this mean for affected devices?

What is CVE-2017-7905?

NVD describes "a Weak Cryptography for Passwords issue" in GE Multilin SR 750 and 760 feeder relays before 7.47, SR 469 motor relays before 5.23, SR 489 generator relays before 4.06, SR 745 transformer relays before 5.23, all SR 369 motor relay versions, Multilin Universal Relay 6.0 and earlier and all Multilin URplus (D90, C90, B95) versions: "Ciphertext versions of user passwords were created with a non-random initialization vector leaving them susceptible to dictionary attacks. Ciphertext of user passwords can be obtained from the front LCD panel of affected products and through issued Modbus commands." NVD's Primary score is CVSS v3.0 9.8 (critical), vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CVSS v2 5.0, and NVD maps it to CWE-326, CWE-330 and CWE-522 (NVD).

Why do NVD and CISA score it differently?

CISA, the CNA, scores CVE-2017-7905 at CVSS v3 8.1 with AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H in its advisory, and its CVE record classifies it as CWE-261, Weak Encoding for Password. The only difference is attack complexity: CISA rates it high, because the attacker still has to recover the password from the ciphertext with a dictionary attack, while NVD rates it low. Either way, a recovered relay password gives full control of protection settings.

Which GE relays and firmware are affected?

CISA first published ICSA-17-117-01 on 2017-04-27, expanded it to UR and URplus in Update A (2017-05-18) and added further legacy products in Update B on 2017-07-25. Its CISA CSAF record lists these fixed versions:

  • 750 and 760 Feeder Protection Relay: 7.47
  • 745 Transformer and 469 Motor Protection Relay: 5.23
  • 489 Generator Protection Relay: 4.06
  • 369 Motor Protection Relay: 3.63
  • MM300: 1.71; MM200: 1.25; MX350: 1.27; RPTCS: 1.29
  • 350, 345 and 339 relays: 2.30; T1000 switch: 03A02
  • Universal Relay: GE released updates that remove the ability to obtain the password ciphertext in UR firmware 5.83, 5.92 and 6.02 to 6.05; UR 7.xx is not affected
  • URplus: CISA reported that GE would release updates in July 2017 for URplus 1.86 and 1.92 and B95Plus 1.03

NVD's CPE ranges end at older version numbers than the CISA fix list (for example the SR 750 range ends at 5.02 while the fix is 7.47), and they omit the products added in Update B, so check the installed version against CISA's list. CISA credits New York University researchers Anastasis Keliris, Charalambos Konstantinou, Marios Sazos and Michail Maniatakos, and knew of no public exploits that specifically targeted the flaw.

How do I fix CVE-2017-7905?

Install the fixed firmware for each relay model; GE's downloads need a login, and GE's own notices are SR-2017-00001 and UR-2017-00001. CISA quotes GE's additional measures: keep devices "in a locked and secure environment", remove passwords when decommissioning devices, monitor and block malicious network activity, and place relays inside the control system network behind firewalls, because "Protection and Control system devices should not be directly connected to the Internet or business networks." After updating, change the relay passwords, since old ciphertext may already have been read. The class fix, salted and randomised password storage, is in our weak cryptography fix guide.

Later UR relay advisories on this site: CVE-2021-27428 (unauthorised firmware upgrade) and CVE-2021-27426 (factory mode). The GE Vernova UR relay guide covers the current UR platform.

Is CVE-2017-7905 exploited?

CVE-2017-7905 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.01281, the 70th percentile, in the 2026-11-26 dataset, as of 2026-11-27 (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Weak cryptography. Our practical guide covers how to detect, fix, verify and disclose it: How to fix weak cryptography in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • Weak cryptography for passwords in GE Multilin SR 750/760 < 7.47, SR 469 < 5.23, SR 489 < 4.06, SR 745 < 5.23, SR 369 all, UR <= 6.0, URplus D90/C90/B95 all; non-random IV; ciphertext from front LCD panel and Modbus; NVD Primary CVSS v3.0 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; v2 5.0; NVD CWE-326, CWE-330, CWE-522; CNA CWE-261; CPE ranges e.g. SR 750 firmware up to 5.02. — NVD
  • ICSA-17-117-01 2017-04-27, Update A 2017-05-18, Update B 2017-07-25; CISA CVSS v3 8.1 AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H, CWE-261; fixed versions 750/760 7.47, 745/469 5.23, 489 4.06, 369 3.63, MM300 1.71, MM200 1.25, MX350 1.27, RPTCS 1.29, 350/345/339 2.30, T1000 03A02; UR updates 5.83, 5.92, 6.02-6.05, UR 7.xx not affected; URplus 1.86/1.92 and B95Plus 1.03 updates in July 2017; GE advisories SR-2017-00001 and UR-2017-00001 need an account; GE defensive measures; NYU researchers credited; no known public exploits. — CISA ICSA-17-117-01B (CSAF)
  • Not in the KEV catalog, version 2026.11.25, checked 2026-11-27. — CISA KEV
  • EPSS 0.01281, 70th percentile, 2026-11-26 dataset. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-17-117-01B: GE Multilin SR, UR, and URplus Protective Relays (Update B)
  3. CISA CSAF record for ICSA-17-117-01B
  4. CVE.org record
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2017-7905?

It depends on the relay: 7.47 for the 750 and 760, 5.23 for the 745 and 469, 4.06 for the 489, 3.63 for the 369, 2.30 for the 350, 345 and 339, and UR firmware 5.83, 5.92 or 6.02 to 6.05. UR 7.xx is not affected (per CISA ICSA-17-117-01B).

Why is CVE-2017-7905 9.8 on NVD but 8.1 at CISA?

CISA rates the attack complexity high, because the password must still be recovered from the ciphertext by a dictionary attack; NVD rates it low. The rest of the vector is identical (per NVD and CISA ICSA-17-117-01B).

How can an attacker get the password ciphertext?

From the relay's front LCD panel or by issuing Modbus commands. The ciphertext uses a non-random initialization vector, which makes it susceptible to dictionary attacks (per NVD and CISA).

Is CVE-2017-7905 in the CISA KEV catalog?

No. It is not listed in catalog version 2026.11.25, checked 2026-11-27, and FIRST EPSS gives it 0.01281, the 70th percentile, in the 2026-11-26 dataset (per CISA KEV and FIRST EPSS).