Security Advisory

CVE-2017-6021: ClearSCADA Server Crash via Network

Last updated:
  • CVE-2017-6021

CVE-2017-6021 is an improper input validation flaw (CWE-20) in Schneider Electric ClearSCADA, the SCADA server now sold as EcoStruxure Geo SCADA Expert. An attacker with network access can send crafted command and data sequences that terminate the server and communications driver processes. NVD scores it 7.5. ClearSCADA 2014 and 2015 hotfixes fix it.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2017-6021 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric ClearSCADA 2014 R1cpe:2.3:a:schneider-electric:clearscada:2014:r1:*:*:*:*:*:*Build 75.5210 and prior; move to the 2014 R1.1 hotfix build 75.6239
Schneider Electric ClearSCADA 2014 R1.1cpe:2.3:a:schneider-electric:clearscada:2014:r1.1:*:*:*:*:*:*Build 75.5387 and prior; fixed in hotfix build 75.6239
Schneider Electric ClearSCADA 2015 R1cpe:2.3:a:schneider-electric:clearscada:2015:r1:*:*:*:*:*:*Build 76.5648 and prior; fixed in the 2015 R1.1 Service Pack, build 76.6191
Schneider Electric ClearSCADA 2015 R2cpe:2.3:a:schneider-electric:clearscada:2015:r2:*:*:*:*:*:*Build 77.5882 and prior; fixed in hotfix build 77.6181
ClearSCADA 2013 R2 and earliercpe:2.3:a:aveva:clearscada:*:*:*:*:*:*:*:*NVD also lists ClearSCADA up to 2010; CISA asks 2013 R2 and earlier users to upgrade to the latest 2015 R2 hotfix

What does this mean for affected devices?

CISA's ICS advisory ICSA-17-068-01, published on 9 March 2017, says "an attacker with network access to the ClearSCADA server can send specially crafted sequences of commands and data packets to the ClearSCADA server that can cause the ClearSCADA server process and ClearSCADA communications driver processes to terminate." CISA credits Sergey Temnikov and Vladimir Dashchenko of Kaspersky Lab's critical infrastructure defense team, and points to Schneider's notice SEVD-2017-060-01.

How severe is CVE-2017-6021?

NVD's Primary score is CVSS v3.0 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H: network, no privileges, no user interaction, availability impact only. NVD also keeps a Primary CVSS v2 score of 5.0, AV:N/AC:L/Au:N/C:N/I:N/A:P (NVD). CISA gives the same 7.5 and NVD and CISA agree on CWE-20. The CVE.org record, assigned by ICS-CERT, carries no separate score.

Which ClearSCADA versions are affected and what is the fix?

Affected are ClearSCADA 2014 R1 build 75.5210 and prior, 2014 R1.1 build 75.5387 and prior, 2015 R1 build 76.5648 and prior and 2015 R2 build 77.5882 and prior. NVD's configuration also matches ClearSCADA releases up to 2010. The fixes are the 2014 R1.1 hotfix build 75.6239, the 2015 R1.1 Service Pack build 76.6191 and the 2015 R2 hotfix build 77.6181. Users of ClearSCADA 2013 R2 and earlier should upgrade to the latest 2015 R2 hotfix.

CISA's listed mitigations are to secure the physical and network interfaces of the ClearSCADA system, put firewalls between network segments to limit ports and protocols, use VPNs with secure authentication on any externally reachable network, audit user security, and for critical accounts use the ClearSCADA security policy to disable the invalid logon count and delayed lockout and use logon throttling instead.

The Schneider EcoStruxure HMI and SCADA software guide lists this crash with the later Geo SCADA flaws. Its successor product's database-port bugs are CVE-2023-22610 and CVE-2023-22611, and the Citect crash CVE-2013-2824 is the closest relative on the HMI side. The OT security guide for small manufacturers covers segmenting SCADA servers.

Is CVE-2017-6021 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0164, the 77th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2018-05-14, status Modified; NVD Primary CVSS v3.0 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; NVD Primary CVSS v2 5.0 AV:N/AC:L/Au:N/C:N/I:N/A:P; CWE-20 (NVD Primary and ICS-CERT); CPE schneider-electric:clearscada 2014 r1, 2014 r1.1, 2015 r1, 2015 r2 and aveva:clearscada up to and including 2010. — NVD
  • CISA ICSA-17-068-01 CSAF (initial release 2017-03-09, read 2026-11-28): affected 2014 R1 build 75.5210 and prior, 2014 R1.1 build 75.5387 and prior, 2015 R1 build 76.5648 and prior, 2015 R2 build 77.5882 and prior; fixes 2014 R1.1 hotfix 75.6239, 2015 R1.1 SP 76.6191, 2015 R2 hotfix 77.6181; 2013 R2 and prior upgrade to latest 2015 R2 hotfix; CVSS v3 7.5, CWE-20; mitigations (physical/network interfaces, firewalls, VPN, user security, logon throttling); vendor notice SEVD-2017-060-01; credit Sergey Temnikov and Vladimir Dashchenko (Kaspersky Lab). — CISA
  • CVE.org record (read 2026-11-28): assigner ICS-CERT, CWE-20, affected ClearSCADA 2014 R1 (build 75.5210) and prior, 2014 R1.1 (75.5387) and prior, 2015 R1 (76.5648) and prior, 2015 R2 (77.5882) and prior; no CNA CVSS metric. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01635, percentile 0.76738, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-17-068-01: Schneider Electric ClearSCADA (CSAF)
  3. CVE.org record (JSON)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which ClearSCADA builds fix CVE-2017-6021?

CISA's ICSA-17-068-01 names the ClearSCADA 2014 R1.1 hotfix build 75.6239, the 2015 R1.1 Service Pack build 76.6191 and the 2015 R2 hotfix build 77.6181. Users of 2013 R2 and earlier should move to the latest 2015 R2 hotfix.

What does an attacker need?

Only network access to the ClearSCADA server. NVD's vector needs no privileges and no user interaction, and the impact is availability only: the server and communications driver processes terminate.

How can I reduce exposure before patching?

CISA lists firewalls between network segments to limit ports and protocols, VPNs with secure authentication on externally reachable networks, securing physical and network interfaces, and logon throttling for critical accounts in the ClearSCADA security policy.

Is CVE-2017-6021 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0164, the 77th percentile, in the 2026-11-27 dataset.