CVE-2023-22611 is an information disclosure flaw (CWE-200) in Schneider Electric EcoStruxure Geo SCADA Expert, formerly ClearSCADA. Specific messages sent to the server's database TCP port, 5481 by default, could expose information without authentication. NVD and Schneider both score it 7.5. The October 2022 updates of Geo SCADA Expert 2019, 2020 and 2021 fix it.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-22611 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric EcoStruxure Geo SCADA Expert 2019 | cpe:2.3:a:schneider-electric:ecostruxure_geo_scada_expert_2019:*:*:*:*:*:*:*:* | 81.8267.1 and prior (NVD lists builds 81.7268.1 to 81.8267.1); fixed in 81.8333.1 (October 2022 update) |
| Schneider Electric EcoStruxure Geo SCADA Expert 2020 | cpe:2.3:a:schneider-electric:ecostruxure_geo_scada_expert_2020:*:*:*:*:*:*:*:* | 83.8267.1 and prior; fixed in 83.8332.1 (October 2022 update) |
| Schneider Electric EcoStruxure Geo SCADA Expert 2021 | cpe:2.3:a:schneider-electric:ecostruxure_geo_scada_expert_2021:*:*:*:*:*:*:*:* | 84.8269.1 and prior; fixed in 84.8335.2 (October 2022 update) |
| Schneider Electric ClearSCADA (former product name) | — | All versions; Schneider advises upgrading to the latest Geo SCADA Expert release |
What does this mean for affected devices?
Schneider's notice SEVD-2023-010-02, released on 10 January 2023 and revised to V1.1 on 14 March 2023, describes "a CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability" "that could cause information disclosure when specific messages are sent to the server over the database server TCP port." Schneider describes Geo SCADA Expert as software for telemetry and remote SCADA solutions, and the notice warns that failure to apply the fix may expose SCADA configuration data. The UK National Cyber Security Centre reported it together with the denial-of-service flaw CVE-2023-22610 on the same port.
How severe is CVE-2023-22611?
NVD's Primary score is CVSS v3.1 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N: network, no privileges, confidentiality impact only (NVD). Schneider gives the identical score and vector, which the CVE.org record carries. Schneider's CWE is CWE-200; NVD's own analysis says NVD-CWE-noinfo.
Which versions are affected and what is the fix?
Affected are Geo SCADA Expert 2019 build 81.8267.1 and prior, 2020 build 83.8267.1 and prior, 2021 build 84.8269.1 and prior, and ClearSCADA in all versions. The October 2022 updates fix it: 2019 build 81.8333.1, 2020 build 83.8332.1 and 2021 build 84.8335.2. Installing new server software needs a system restart or a changeover of redundant servers. ClearSCADA owners should move to the latest Geo SCADA release.
Until updated, Schneider asks owners to restrict the database port (default 5481) so only ViewX clients reach it, use the Geo SCADA Expert 2021 server-side client certificate checks, disable "Allow guest user to execute SQL", and configure the Client Access Control list to block unauthorized IP addresses and restrict the web services port (default 443).
The Schneider EcoStruxure HMI and SCADA software guide covers Geo SCADA and ClearSCADA together, including the older ClearSCADA crash CVE-2017-6021. The OT security guide for small manufacturers explains how to limit who can reach a SCADA server port.
Is CVE-2023-22611 exploited?
It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0073, the 50th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): published 2023-01-31, status Modified; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N; Schneider Secondary CVSS v3.1 7.5 same vector; CWE-200 (Schneider), NVD-CWE-noinfo (NVD); CPE ecostruxure_geo_scada_expert_2019 builds 81.7268.1 to 81.8267.1, 2020 builds 83.7551.1 to 83.8267.1, 2021 builds 84.8027.1 to 84.8269.1. — NVD
- Schneider SEVD-2023-010-02 V1.1 (10 January 2023, revised 14 March 2023, PDF and Schneider CSAF read 2026-11-28): CVE-2023-22611 CWE-200 CVSS v3.1 7.5; affected Geo SCADA Expert 2019 <=81.8267.1, 2020 <=83.8267.1, 2021 <=84.8269.1, ClearSCADA all versions; fixed 81.8333.1, 83.8332.1, 84.8335.2 (October 2022 updates); restart or redundant changeover; mitigations port 5481 to ViewX clients, client certificate checks, disable Allow guest user to execute SQL, Client Access Control list, web port 443; credited to the UK NCSC. — Schneider Electric
- CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-200, CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N; affected Geo SCADA Expert 2019-2021 (formerly ClearSCADA) versions before October 2022. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.00734, percentile 0.50460, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Geo SCADA builds fix CVE-2023-22611?
The October 2022 updates: Geo SCADA Expert 2019 build 81.8333.1, 2020 build 83.8332.1 and 2021 build 84.8335.2, per Schneider's SEVD-2023-010-02. They also fix CVE-2023-22610.
Which port should I restrict?
The Geo SCADA server's database port, default TCP 5481. Schneider asks owners to allow it only from ViewX clients and to use the Client Access Control list, which can also restrict the web services port (default 443).
Does it need a login?
No. Both NVD and Schneider score it with no privileges and no user interaction over the network; the impact is confidentiality only.
Is CVE-2023-22611 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0073, the 50th percentile, in the 2026-11-27 dataset.