Security Advisory

CVE-2016-5744: SIMATIC WinCC Station File Read

Last updated:
  • CVE-2016-5744

CVE-2016-5744 is an unauthenticated file-read flaw in Siemens SIMATIC WinCC V7.0 and V7.2. Crafted packets sent to a WinCC station let an attacker extract arbitrary files from it. NVD scores it CVSS v3.0 7.5, the same base score as Siemens. Siemens fixed it in WinCC V7.0 SP2 Update 12, V7.0 SP3 Update 8 and V7.2 Update 13.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

4.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2016-5744 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC V7.0 and V7.2cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*Siemens SSA-378531: only WinCC V7.0 and V7.2 are affected; fixed in V7.0 SP2 Update 12, V7.0 SP3 Update 8 and V7.2 Update 13. NVD CPEs list 7.0, 7.0 SP1 to SP3 and 7.2
Siemens SIMATIC PCS 7 V7.1 SP4 and V8.0 SP2 (WinCC incorporated)cpe:2.3:a:siemens:simatic_pcs_7:*:*:*:*:*:*:*:*Through the embedded WinCC V7.0 or V7.2: PCS 7 V7.1 SP4 and earlier take WinCC V7.0 SP2 Update 12, V8.0 SP2 takes WinCC V7.2 Update 13, plus the BATCH, Route Control and OpenPCS 7 updates in SSA-378531. Not in NVD's CPE list

What does this mean for affected devices?

NVD's description reads: "Siemens SIMATIC WinCC 7.0 through SP3 and 7.2 allows remote attackers to read arbitrary WinCC station files via crafted packets." NVD's Primary score is CVSS v3.0 7.5 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N), with a Primary CVSS v2 5.0 (AV:N/AC:L/Au:N/C:P/I:N/A:N) and CWE-200. NVD's CPEs cover WinCC 7.0, 7.0 SP1 to SP3 and 7.2. MITRE assigned the CVE, and the CVE record carries no CNA score or CWE (NVD, CVE record).

What does Siemens say?

Siemens advisory SSA-378531 (V1.3, last updated 2016-11-07, first published 2016-07-22) says "specially crafted packets sent to SIMATIC WinCC could allow unauthenticated users to extract arbitrary files from the WinCC station", and that this flaw "only affects WinCC V7.0 and WinCC V7.2". Siemens scores it CVSS v3.0 7.5 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C), the same base score as NVD. The advisory also covers CVE-2016-5743, an unauthenticated code execution flaw that reaches WinCC V7.3, V7.4 and WinCC Runtime Professional as well, which is why its product list is longer than the scope of CVE-2016-5744. Siemens credits Sergey Temnikov and Vladimir Dashchenko of Kaspersky Lab.

For the two affected lines the fixes are WinCC V7.0 SP2 Update 12, V7.0 SP3 Update 8 and V7.2 Update 13. PCS 7 V7.1 SP4 and earlier take WinCC V7.0 SP2 Update 12, and PCS 7 V8.0 SP2 takes WinCC V7.2 Update 13, each with the BATCH, Route Control and OpenPCS 7 updates listed in the advisory. Until updates are installed, Siemens recommends running WinCC and PCS 7 stations within a trusted network, communicating only over encrypted channels ("Encrypted Communications" in WinCC V7.3 and PCS 7 V8.1 SP1, or a VPN tunnel), restricting access to trusted entities, and using application whitelisting and virus scanners. The only mitigating factor it names is that the attacker must have network access to the affected system.

What does CISA say?

CISA advisory ICSA-16-208-01C (CSAF), "Siemens SIMATIC WinCC, PCS 7, and WinCC Runtime Professional Vulnerabilities (Update C)", scores CVE-2016-5744 CVSS v3.0 7.5 and classifies it as CWE-20 (improper input validation). Its CSAF lists the advisory's full product list as known affected for this CVE, including WinCC V7.3, V7.4 and Runtime Professional; Siemens' own text limits CVE-2016-5744 to WinCC V7.0 and V7.2.

What should a WinCC owner do?

  1. Find every station still on WinCC V7.0 or V7.2, including PCS 7 V7.1 and V8.0 systems that embed them.
  2. Install V7.0 SP2 Update 12, V7.0 SP3 Update 8 or V7.2 Update 13, or move to a newer line; on PCS 7 also install the add-on updates.
  3. Restrict WinCC station traffic to the stations that need it, and use encryption or a VPN between them.

The Siemens WinCC and PCS 7 guide groups this flaw with the other WinCC crafted-packet issues. CVE-2016-5743 is the code execution flaw from the same advisory, CVE-2014-8552 is the 2014 file-read flaw of the same kind, and CVE-2014-8551 its code execution twin. The KEV and EPSS prioritization guide explains how to read EPSS scores like this one.

CVE-2016-5744 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.04399, a percentile of 92.1, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2016-07-22; NVD Primary CVSS v3.0 7.5 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N and Primary CVSS v2 5.0 AV:N/AC:L/Au:N/C:P/I:N/A:N; CWE-200; CPEs simatic_wincc 7.0, 7.0 SP1 to SP3, 7.2. — NVD
  • Siemens SSA-378531 V1.3 PDF (read 2026-11-28): CVE-2016-5744 lets unauthenticated users extract arbitrary files from the WinCC station, only WinCC V7.0 and V7.2; CVSS v3.0 7.5 with E:P/RL:O/RC:C; fixed versions and mitigations; credit to Kaspersky Lab. — Siemens ProductCERT SSA-378531
  • CISA ICSA-16-208-01C CSAF (read 2026-11-28): CVSS v3.0 7.5, CWE-20; known_affected lists the full advisory product list. — CISA ICSA-16-208-01C
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, no CNA CVSS or CWE. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.04399, percentile 0.92103, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-378531: Vulnerabilities in SIMATIC WinCC, PCS 7 and WinCC Runtime Professional
  3. CISA ICSA-16-208-01C: Siemens SIMATIC WinCC, PCS 7, and WinCC Runtime Professional
  4. CISA ICSA-16-208-01C CSAF (machine-readable advisory)
  5. CVE record CVE-2016-5744 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which WinCC versions are affected by CVE-2016-5744?

Siemens SSA-378531 says the flaw only affects WinCC V7.0 and V7.2. PCS 7 V7.1 SP4 and earlier and PCS 7 V8.0 are affected through the WinCC versions they embed.

Which updates fix it?

WinCC V7.0 SP2 Update 12, V7.0 SP3 Update 8 and V7.2 Update 13. On PCS 7, Siemens also lists BATCH, Route Control and OpenPCS 7 updates for each release.

Is CVE-2016-5744 the same as CVE-2016-5743?

No. Both were fixed by SSA-378531, but CVE-2016-5743 allows unauthenticated code execution and also affects WinCC V7.3, V7.4 and Runtime Professional, while CVE-2016-5744 is a file-read flaw limited to V7.0 and V7.2.

Is CVE-2016-5744 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.04399 (percentile 92.1) in the 2026-11-27 dataset.