Security Advisory

CVE-2014-8552: SIMATIC WinCC Server Arbitrary File Read

Last updated:
  • CVE-2014-8552

CVE-2014-8552 is an unauthenticated file-read flaw in the server component of Siemens SIMATIC WinCC. Crafted packets sent to the WinCC server let an attacker extract arbitrary files from it, and PCS 7 V7.1 to V8.1 and TIA Portal V13 are affected through WinCC. NVD scores it CVSS v2 5.0; Siemens scores 7.8. Siemens fixed it in WinCC V7.2 Update 9, V7.3 Update 2 and TIA Portal V13 Update 6.

Vulnerability summary

CVSS base score

5

Medium severity

EPSS score (FIRST)

2.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-8552 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC (V7.0, V7.2, V7.3)cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*Siemens SSA-134508: V7.0 SP3 and earlier, V7.2 before Update 9, V7.3 before Update 2. Fixed in V7.0 SP2 Update 11, V7.0 SP3 Update 7, V7.2 Update 9 and V7.3 Update 2. NVD CPEs list 7.0 to 7.0 SP3, 7.2 Updates 1 to 8 and 7.3 Update 1
Siemens SIMATIC PCS 7 (WinCC incorporated)cpe:2.3:a:siemens:simatic_pcs7:*:*:*:*:*:*:*:*V7.1 SP4 and earlier; V8.0 before V8.0 SP2 with WinCC V7.2 Update 9; V8.1 before WinCC V7.3 Update 2. Fixed by the WinCC update plus the OpenPCS 7, Route Control and BATCH updates in SSA-134508
Siemens TIA Portal V13 (including WinCC Professional Runtime)cpe:2.3:a:siemens:simatic_tiaportal:13.0:*:*:*:*:*:*:*All versions before V13 Update 6; fixed in WinCC V13 Update 6

What does this mean for affected devices?

NVD's description reads: "The WinCC server in Siemens SIMATIC WinCC 7.0 through SP3, 7.2 before Update 9, and 7.3 before Update 2; SIMATIC PCS 7 7.1 through SP4, 8.0 through SP2, and 8.1; and TIA Portal 13 before Update 6 allows remote attackers to read arbitrary files via crafted packets." MITRE assigned the CVE, and the CVE record carries no CNA score or CWE (NVD, CVE record).

Which score applies?

NVD's only metric is a Primary CVSS v2 5.0 (AV:N/AC:L/Au:N/C:P/I:N/A:N): network access, no authentication, partial confidentiality impact. NVD classifies the flaw as CWE-200 (exposure of sensitive information) and has no v3 score. Siemens rates the same flaw higher, CVSS v2 base 7.8 (AV:N/AC:L/Au:N/C:C/I:N/A:N), temporal 6.1, because it treats the confidentiality impact as complete. CISA republishes Siemens' 7.8 and classifies the flaw as CWE-284 (improper access control). This page uses NVD's 5.0 as the headline score.

What does Siemens say?

Siemens advisory SSA-134508 (V1.4, last updated 2015-02-06, first published 2014-11-21) says "a component within WinCC could allow unauthenticated users to extract arbitrary files from the WinCC server if specially crafted packets are sent to the server". The only mitigating factor it names is that the attacker must have network access to the affected system. The same advisory covers CVE-2014-8551, a remote code execution flaw in the same server component.

The affected products are WinCC V7.0 SP3 and earlier, V7.2 before Update 9 and V7.3 before Update 2; PCS 7 V7.1 SP4 and earlier, V8.0 before V8.0 SP2 with WinCC V7.2 Update 9, and V8.1 before WinCC V7.3 Update 2; and TIA Portal V13, including WinCC Professional Runtime, before V13 Update 6. The fixes are WinCC V7.0 SP2 Update 11, V7.0 SP3 Update 7, V7.2 Update 9, V7.3 Update 2 and WinCC V13 Update 6. PCS 7 V7.1 SP4, V8.0 SP2 and V8.1 also need the OpenPCS 7, Route Control and BATCH updates listed per release. Until updates are installed, Siemens advises running WinCC servers and engineering stations only within a trusted network, letting them communicate only over encrypted channels ("Encrypted Communications" in WinCC V7.3, or a VPN tunnel), restricting access to the WinCC server to trusted entities, and using application whitelisting and virus scanners.

What does CISA say?

CISA advisory ICSA-14-329-02D (CSAF), "Siemens SIMATIC WinCC, PCS7, and TIA Portal Vulnerabilities", lists the same products and updates with CVSS v2 7.8 and CWE-284, and adds its standard practices: keep control system devices off the internet, put control networks behind firewalls and use up-to-date VPNs for remote access.

What should a WinCC or PCS 7 owner do?

  1. Check the WinCC Update level on every server and engineering station, not only the PCS 7 release number.
  2. Install the WinCC Update for the line, plus the PCS 7 add-on updates, which also close CVE-2014-8551.
  3. Keep the WinCC server reachable only from the stations that need it, and treat project files and archives on it as data an attacker on the plant network could read.

The Siemens WinCC and PCS 7 guide places this flaw among the WinCC crafted-packet issues. CVE-2014-8551 is the code execution flaw fixed by the same updates, and CVE-2016-5744 is the 2016 file-read flaw of the same kind. The OT/ICS security guide for small manufacturers covers segmenting SCADA servers.

CVE-2014-8552 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.02047, a percentile of 81.9, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2014-11-26; NVD Primary CVSS v2 5.0 AV:N/AC:L/Au:N/C:P/I:N/A:N; no v3 metric; CWE-200; CPEs simatic_wincc 7.0 to 7.0 SP3, 7.2 Updates 1 to 8, 7.3 Update 1, simatic_pcs7 7.1 SP1 to 8.1, simatic_tiaportal 13.0. — NVD
  • Siemens SSA-134508 V1.4 PDF (read 2026-11-28): CVE-2014-8552 lets unauthenticated users extract arbitrary files via crafted packets; CVSS v2 base 7.8, temporal 6.1 AV:N/AC:L/Au:N/C:C/I:N/A:N/E:POC/RL:OF/RC:C; affected and fixed versions; mitigations. — Siemens ProductCERT SSA-134508
  • CISA ICSA-14-329-02D CSAF (read 2026-11-28): CVSS v2 7.8, CWE-284; same affected products and Siemens updates. — CISA ICSA-14-329-02D
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, no CNA CVSS or CWE. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.02047, percentile 0.81885, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-134508: Vulnerabilities in SIMATIC WinCC, PCS 7 and WinCC in TIA Portal
  3. CISA ICSA-14-329-02D: Siemens SIMATIC WinCC, PCS7, and TIA Portal Vulnerabilities
  4. CISA ICSA-14-329-02D CSAF (machine-readable advisory)
  5. CVE record CVE-2014-8552 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which WinCC versions fix CVE-2014-8552?

Siemens SSA-134508 lists WinCC V7.0 SP2 Update 11, V7.0 SP3 Update 7, V7.2 Update 9 and V7.3 Update 2, and WinCC V13 Update 6 for TIA Portal V13 including WinCC Professional Runtime. The same updates fix CVE-2014-8551.

Why do NVD and Siemens give different scores?

NVD scores CVSS v2 5.0 with a partial confidentiality impact. Siemens and CISA score 7.8 because they rate the confidentiality impact as complete. Both agree the attack works over the network without authentication.

Does an attacker need credentials?

No. Siemens says the flaw lets unauthenticated users extract files when crafted packets are sent to the WinCC server. The only mitigating factor it names is that the attacker needs network access to the system.

Is CVE-2014-8552 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.02047 (percentile 81.9) in the 2026-11-27 dataset.