CVE-2013-6920 is a missing-authentication flaw in Siemens SINAMICS S/G drive firmware before 4.6.11: the FTP (21/tcp) and Telnet (23/tcp) services accept sessions without credentials, so anyone who can reach the drive can use administrative functions. NVD scores it 10.0 (CVSS v2); Siemens fixed it in firmware V4.6 HF11.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
3.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2013-6920 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SINAMICS S/G family firmware (G110, G110D, G120, G120C, G120D, G120P, G130, G150, G180, S110, S120, S120CM, S150 per NVD CPEs) | cpe:2.3:o:siemens:sinamics_s\/g_family_firmware:*:*:*:*:*:*:*:* | NVD CPE: up to and including 4.6; CISA ICSA-13-338-01: before 4.6.11; Siemens SSA-742938 V1.3: SINAMICS G120 (incl. SIPLUS) all versions before V4.6 HF11; fixed in V4.6 HF11 (CISA also names 4.7) |
What does this mean for affected devices?
NVD's description reads: "Siemens SINAMICS S/G controllers with firmware before 4.6.11 do not require authentication for FTP and TELNET sessions, which allows remote attackers to bypass intended access restrictions via TCP traffic to port (1) 21 or (2) 23." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-287; NVD has no CVSS v3 score for it. MITRE assigned the record with vendor and product n/a and no CNA score, and NVD published it on 2013-12-07 (NVD, CVE record).
What does Siemens say about the flaw?
Siemens ProductCERT published SSA-742938 ("Open Ports in SINAMICS S/G Firmware") on 2013-12-04; version 1.3 of 2020-02-10 is current. It states that the open FTP (21/tcp) and Telnet (23/tcp) services "might allow attackers to access administrative functions of the affected devices over the network without authentication". Siemens now scores it CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C) and classifies it as CWE-306, missing authentication for a critical function. SINAMICS S/G converters control drives in mechanical engineering and plant construction, so an open administrative service on the drive is an OT exposure, not only an IT one.
Which SINAMICS drives are affected?
The three sources word the scope differently. NVD's CPE configuration matches SINAMICS S/G family firmware up to and including 4.6 on G110, G110D, G120, G120C, G120D, G120P, G130, G150, G180, S110, S120, S120CM and S150 hardware. CISA's advisory ICSA-13-338-01 (CSAF) lists SINAMICS S/G family firmware before 4.6.11. Siemens' current SSA names SINAMICS G120, including SIPLUS variants, with all versions before V4.6 HF11. SIPLUS devices use the same firmware as the product they are based on.
How do I fix CVE-2013-6920?
Update the firmware. Siemens' SSA names V4.6 HF11 as the fix; CISA's advisory names SINAMICS S/G V4.6.11 and 4.7. The update comes from the local Siemens account manager or Siemens customer support. Siemens has not identified specific workarounds, and recommends protecting network access to the drives and following its operational guidelines for Industrial Security. CISA adds its usual practices: keep drives off the internet, behind firewalls separated from business networks, and use a VPN for remote access. Blocking 21/tcp and 23/tcp to the drive at the cell firewall is the obvious interim control.
Later SINAMICS exposure appears in the PROFINET DCP advisories CVE-2017-2680 and CVE-2017-2681, and the Siemens web authentication flaw CVE-2013-5944 is from the same period. The authentication bypass fix guide covers why maintenance services such as FTP and Telnet must not ship enabled without credentials.
CVE-2013-6920 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.03235, the 89.0th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2013-12-07; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-287; CPE SINAMICS S/G family firmware up to and including 4.6 on 13 SINAMICS G/S hardware models; references ICSA-13-338-01 and Siemens SSA-742938. — NVD
- Siemens SSA-742938 V1.3 (published 2013-12-04, updated 2020-02-10, read 2026-11-27): open FTP 21/tcp and Telnet 23/tcp might allow access to administrative functions without authentication; CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C; CWE-306; affected SINAMICS G120 (incl. SIPLUS variants) all versions < V4.6 HF11; remediation update to V4.6 HF11 from the local Siemens account manager; no specific workarounds identified. — Siemens ProductCERT SSA-742938
- CISA ICSA-13-338-01 CSAF (read 2026-11-27): affected SINAMICS S/G family firmware <4.6.11; CVSS v2 10.0; Siemens firmware update SINAMICS S/G V4.6.11 and 4.7 resolves it, obtained via Siemens customer support or the local account manager. — CISA ICSA-13-338-01
- CVE record (checked 2026-11-27): state PUBLISHED, CNA MITRE, published 2013-12-07, affected n/a / n/a, no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, checked 2026-11-27. — CISA KEV
- EPSS 0.03235, percentile 0.89035, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
- NVD
- Siemens ProductCERT SSA-742938: Open Ports in SINAMICS S/G Firmware (text)
- Siemens ProductCERT SSA-742938 (PDF)
- CISA ICSA-13-338-01: Siemens SINAMICS S/G Authentication Bypass Vulnerability
- CISA ICSA-13-338-01 CSAF (machine-readable advisory)
- CVE.org record CVE-2013-6920 (CVE Services JSON)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which firmware fixes CVE-2013-6920?
Siemens names SINAMICS firmware V4.6 HF11 as the fix, available from the local Siemens account manager; CISA's advisory describes the update as SINAMICS S/G V4.6.11 and 4.7 (per Siemens SSA-742938 and CISA ICSA-13-338-01).
Which SINAMICS drives are affected?
NVD's CPE data covers SINAMICS S/G family firmware up to 4.6 on G110, G110D, G120, G120C, G120D, G120P, G130, G150, G180, S110, S120, S120CM and S150 hardware, while Siemens' current advisory lists SINAMICS G120 including SIPLUS variants below V4.6 HF11. Check the firmware version on every S/G drive (per NVD and Siemens SSA-742938).
Is there a workaround if I cannot update the drive?
Siemens has not identified specific workarounds and recommends protecting network access to the devices. In practice that means keeping 21/tcp and 23/tcp on the drive unreachable from anything but trusted engineering hosts, behind a cell firewall, as CISA's general practices also advise (per Siemens SSA-742938 and CISA ICSA-13-338-01).
How severe is CVE-2013-6920 today?
NVD scores it CVSS v2 10.0 and Siemens CVSS v3.1 9.8. It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25), and FIRST EPSS rates it 0.03235, the 89.0th percentile, in the 2026-11-26 dataset (per NVD, Siemens, CISA KEV and FIRST EPSS).