Security Advisory

CVE-2014-9195: Phoenix Contact ProConOs Missing Auth

Last updated:
  • CVE-2014-9195

CVE-2014-9195 is missing authentication (CWE-306) in Phoenix Contact Software's ProConOs PLC runtime and MultiProg engineering software: anyone who can reach the runtime over the network can send it commands using the normal protocol. NVD scores it 7.5 and CISA 10.0 (CVSS v2). There is no vendor fix, so network isolation is the control.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

81.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-9195 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Phoenix Contact Software ProConOs (eCLR runtime: single chip, SoftPLC, Visual Studio editions)cpe:2.3:o:phoenixcontact-software:proconos_eclr:*:*:*:*:*:*:*:*All versions (CISA ICSA-15-013-03; NVD CPE without a version bound); no fix released
Phoenix Contact Software MultiProg (incl. Express and Pro+ editions)cpe:2.3:a:phoenixcontact-software:multiprog:5.0:*:*:*:*:*:*:*All versions per CISA; NVD CPE lists MultiProg 5.0; no fix released

What does this mean for affected devices?

The CVE record says "Phoenix Contact ProConOs and MultiProg do not require authentication, which allows remote attackers to execute arbitrary commands via protocol-compliant traffic." CISA classifies it as CWE-306, missing authentication for a critical function; NVD files it under the older CWE-255 credentials category (NVD; the CVE.org record carries the same text).

Why do NVD and CISA score it differently?

NVD's Primary score is CVSS v2 7.5, AV:N/AC:L/Au:N/C:P/I:P/A:P, which rates the impact as partial. ICS-CERT, which assigned the CVE, scores 10.0 with AV:N/AC:L/Au:N/C:C/I:C/A:C, rating the impact on confidentiality, integrity and availability as complete. Both agree it needs no login and has low complexity. NVD has no CVSS v3 score for this 2015 record.

Which products are affected and is there a fix?

CISA's ICSA-15-013-03, released on 2015-01-13, lists all versions of ProConOs and MultiProg and credits Reid Wightman of Digital Bond. NVD's configuration names the ProConOs eCLR runtime (single chip, SoftPLC and Visual Studio editions) and MultiProg 5.0, Express and Pro+. Phoenix Contact Software told CISA that it designed the applications and protocol without authentication, expecting vendors that build the runtime into their own products to add their own authentication, and that it was considering adding authentication to future versions (CSAF). No patch is listed. Because ProConOs is embedded by other manufacturers, ask your controller vendor whether its product uses the runtime.

CISA's mitigations apply: keep controllers off the internet, put them behind firewalls separated from the business network, and allow engineering access only from known workstations, over a VPN where remote access is needed. The authentication bypass fix guide covers how runtimes add authentication, and the OT security guide for small manufacturers covers zoning. Other Phoenix Contact missing-authentication pages: CVE-2019-9201 (classic line controllers, port 1962) and CVE-2022-31800 (classic line logic upload).

Is CVE-2014-9195 exploited?

It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). CISA's advisory noted no known public exploit at release. FIRST EPSS gives it 0.81240, the 99.75th percentile, in the 2026-11-26 dataset, which is high for an OT CVE (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): published 2015-01-17, status Modified; NVD Primary CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; ICS-CERT Secondary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE-255 (NVD), CWE-306 (ICS-CERT); CPE multiprog 5.0 (incl. express, pro+), proconos_eclr (single_chip, softplc, visual_studio). — NVD
  • CISA ICSA-15-013-03 CSAF (read 2026-11-27): ProConOs all versions, MultiProg all versions; CWE-306; CVSS v2 10.0; vendor designed applications and protocol without authentication, expected integrators to add their own, considering authentication in future versions. — CISA ICSA-15-013-03
  • CISA advisory page (read 2026-11-27 via a page fetch): released 2015-01-13, last revised 2019-01-24; researcher Reid Wightman of Digital Bond; remotely exploitable; no known public exploits; low skill. — CISA
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.8124, percentile 0.99752, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-15-013-03: Phoenix Contact Software ProConOs and MultiProg Authentication Vulnerability (CSAF)
  3. CISA ICSA-15-013-03 advisory page
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Is there a patch for CVE-2014-9195?

No patch is listed in CISA ICSA-15-013-03. Phoenix Contact Software said the protocol was designed without authentication, that integrators were expected to add their own, and that it was considering authentication for future versions. Network isolation is the available control.

Which versions of ProConOs and MultiProg are affected?

CISA lists all versions of both. NVD's configuration names the ProConOs eCLR runtime in its single chip, SoftPLC and Visual Studio editions, and MultiProg 5.0 including the Express and Pro+ editions.

Why is the EPSS score so high?

FIRST EPSS rates it 0.81240, the 99.75th percentile, in the 2026-11-26 dataset. EPSS is a model of exploitation likelihood; CISA has not added the CVE to KEV as of 2026-11-27, and its advisory reported no known public exploit at release.

Why do NVD and CISA scores differ?

NVD scores CVSS v2 7.5 with partial confidentiality, integrity and availability impact. CISA, which assigned the CVE, scores 10.0 with complete impact on all three. Both rate it as network reachable with no authentication.