Security Advisory

CVE-2014-0760: Festo CECX Controller FTP Backdoor

Last updated:
  • CVE-2014-0760

CVE-2014-0760 is an undocumented FTP access method, effectively a backdoor, in Festo's CECX-X-C1 and CECX-X-M1 CoDeSys-based modular controllers. A remote attacker can use it to run arbitrary code or crash the controller. NVD and CISA score it CVSS v2 9.3. Festo decided not to fix it, so the only defence is network isolation.

Vulnerability summary

CVSS base score

9.3

Critical severity

EPSS score (FIRST)

3.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-0760 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Festo CECX-X-C1 Modular Master Controller with CoDeSyscpe:2.3:h:festo:cecx-x-c1_modular_master_controller:-:*:*:*:*:*:*:*All versions (CISA ICSA-14-084-01); no fix, Festo decided not to resolve the vulnerabilities
Festo CECX-X-M1 Modular Controller with CoDeSys and SoftMotioncpe:2.3:h:festo:cecx-x-m1_modular_controller:-:*:*:*:*:*:*:*All versions (CISA ICSA-14-084-01); no fix, Festo decided not to resolve the vulnerabilities

What does this mean for affected devices?

NVD says the two Festo controllers "provide an undocumented access method involving the FTP protocol, which allows remote attackers to execute arbitrary code or cause a denial of service (application crash) via unspecified vectors." NVD and CISA both classify it as CWE-287, improper authentication. The record was assigned by ICS-CERT and published on 2014-04-25 (NVD, CVE record).

How severe is CVE-2014-0760?

NVD's Primary score is CVSS v2 9.3, AV:N/AC:M/Au:N/C:C/I:C/A:C, and the CNA score in the CVE record is the same 9.3. CISA's ICSA-14-084-01, released on 2014-03-25, credits K. Reid Wightman of IOActive and states that exploits targeting these flaws are publicly available and need little skill. CISA explains the stakes in manufacturing terms: the controller combines a PLC with a multi-axis motion controller, and an attacker could change assembly tolerances and remove the record of the change.

Which Festo controllers are affected?

The CECX-X-C1 Modular Master Controller with CoDeSys and the CECX-X-M1 Modular Controller with CoDeSys and SoftMotion, all versions. CISA lists their use in solar cell manufacturing, automobile and general assembly, parts control and airframe manufacturing, within the critical manufacturing sector. The same advisory covers three siblings: CVE-2014-0769 (unauthenticated debug and log services on TCP 4000 and 4001, CVSS v2 9.3) and the CoDeSys 2.3 runtime flaws CVE-2012-6068 and CVE-2012-6069 (CVSS v2 10.0 each).

Is there a fix for CVE-2014-0760?

No. The advisory CSAF records that "Festo has decided not to resolve these vulnerabilities". CISA's compensating measures are to keep the controllers off the internet, behind a firewall and isolated from business networks, use VPNs for remote access, deploy intrusion detection on the control network, and turn on port security and traffic logging. Block FTP and the CoDeSys runtime ports at the cell boundary and plan to replace the controllers. The CODESYS runtime guide covers the runtime these controllers embed, and the authentication bypass fix guide covers the class. Related CoDeSys 2.3 device pages: CVE-2018-5459 (WAGO PFC200 CODESYS port access) and CVE-2011-5007 (CoDeSys web server on ABB AC500).

Is CVE-2014-0760 exploited?

CVE-2014-0760 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.03345, the 89.43rd percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2014-04-25; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; ICS-CERT Secondary 9.3; CWE-287 (NVD and ICS-CERT); CPEs 3s-software codesys_runtime_system, festo cecx-x-c1_modular_master_controller, softmotion3d softmotion, festo cecx-x-m1_modular_controller. — NVD
  • CISA ICSA-14-084-01 CSAF (read 2026-11-27): CECX-X-C1 and CECX-X-M1 all versions; CVE-2014-0760 and CVE-2014-0769 CWE-287 9.3; CVE-2012-6068 and CVE-2012-6069 CWE-284 10.0; Festo has decided not to resolve these vulnerabilities; compensating measures listed. — CISA ICSA-14-084-01
  • CISA advisory page (read 2026-11-27 via a page fetch): released March 25, 2014; K. Reid Wightman of IOActive; exploits publicly available, low skill; PLC with multiaxis controller, attacker could modify assembly tolerances and remove record of change; solar cell, automobile, general assembly, parts control, airframe manufacturing; Critical Manufacturing. — CISA
  • CVE record (read 2026-11-27): CNA ICS-CERT; title Festo CECX-X-(C1/M1) Controller Improper Authentication; CNA CVSS v2 9.3. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.03345, percentile 0.89431, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-14-084-01: Festo CECX-X-(C1/M1) Controller Vulnerabilities (CSAF)
  3. CISA ICSA-14-084-01 advisory page
  4. CVE.org record CVE-2014-0760 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is there a firmware update for CVE-2014-0760?

No. CISA ICSA-14-084-01 states that Festo decided not to resolve the vulnerabilities in the CECX-X-C1 and CECX-X-M1 controllers, so only compensating network controls and replacement remain.

Which other flaws affect the same Festo controllers?

CVE-2014-0769 (unauthenticated debug and log services on TCP 4000 and 4001, CVSS v2 9.3) and the CoDeSys 2.3 runtime flaws CVE-2012-6068 and CVE-2012-6069 (CVSS v2 10.0), all in the same CISA advisory and all unfixed.

How should owners protect these controllers?

Keep them off the internet, behind a firewall and separate from the business network; use a VPN for remote access; block FTP and the CoDeSys runtime ports at the cell boundary; and monitor the control network with intrusion detection and traffic logging, as CISA recommends.

Is CVE-2014-0760 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.03345 (89.43rd percentile) in the 2026-11-26 dataset. CISA noted that public exploits exist.