CVE-2011-3489 is a denial-of-service flaw in RsvcHost.exe, the FactoryTalk service host that ships with Rockwell RSLogix 5000. A crafted packet to TCP port 4446 makes RnaUtility.dll mishandle a size field and crash the service on the engineering workstation. NVD scores it 5.0 (CVSS v2). Rockwell patch AID 458689 fixes RSLogix 5000 V17 to V19 and FactoryTalk Services Platform CPR9 to CPR9-SR4.
Vulnerability summary
CVSS base score
5
Medium severity
EPSS score (FIRST)
8.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2011-3489 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation RSLogix 5000 V17, V18, V19; FactoryTalk Services Platform CPR9 and CPR9-SR1 to SR4 (RsvcHost.exe / RnaUtility.dll) | cpe:2.3:a:rockwellautomation:rslogix:*:*:*:*:*:*:*:* | NVD: RSLogix up to and including 19; CISA ICSA-11-273-03A: RSLogix 5000 V17, V18, V19 and FactoryTalk Services Platform CPR9, CPR9-SR1 to SR4 affected; RSLogix 5000 V16 and earlier and CPR7 and earlier not affected. Fix: Rockwell patch AID 458689 (KB 456144) |
What does this mean for affected devices?
NVD's description reads: "RnaUtility.dll in RsvcHost.exe 2.30.0.23 in Rockwell RSLogix 19 and earlier allows remote attackers to cause a denial of service (crash) via a crafted rna packet with a long string to TCP port 4446 that triggers (1) "a memset zero overflow" or (2) an out-of-bounds read, related to improper handling of a 32-bit size field." NVD's Primary score is CVSS v2 5.0 (AV:N/AC:L/Au:N/C:N/I:N/A:P) with CWE-119: availability only. NVD published the record on 2011-09-16; MITRE assigned it with no CNA score (NVD, CVE record).
Which Rockwell versions are affected?
CISA advisory ICSA-11-273-03A (CSAF), "Rockwell RSLogix Overflow Vulnerability", lists RSLogix 5000 V17, V18 and V19 and all FactoryTalk-branded software built on FactoryTalk Services Platform CPR9 and CPR9-SR1 through SR4. Customers on FactoryTalk Services Platform CPR7 and earlier, and on RSLogix 5000 V16 and earlier, are not affected. CISA scores it CVSS v2 5.0 with CWE-119.
How do I fix it?
Rockwell Automation recommends that customers on FactoryTalk Services Platform CPR9 to CPR9-SR4 and on RSLogix 5000 V17, V18 and V19 apply patch AID 458689; full patching instructions are in Rockwell security advisory KB 456144. Both answers are on Rockwell's knowledge base, which needs a Rockwell account. Until the patch is in place, block TCP port 4446 from outside the engineering network and keep programming workstations away from business and internet traffic.
CVE-2016-5814 is a later RSLogix 500/Micro project-file overflow, and CVE-2014-0755 covers RSLogix 5000 project passwords. The memory corruption guide explains this class of bug, and the OT/ICS security guide for small manufacturers covers protecting engineering workstations.
CVE-2011-3489 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0875, a percentile of 95.9, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2011-09-16; NVD Primary CVSS v2 5.0 AV:N/AC:L/Au:N/C:N/I:N/A:P; CWE-119; CPE rockwellautomation rslogix up to and including 19. — NVD
- CISA ICSA-11-273-03A CSAF (read 2026-11-28): CWE-119, CVSS v2 5.0; RSLogix 5000 17/18/19 and FactoryTalk CPR9, CPR9-SR1 to SR4; patch AID 458689; KB 456144; CPR7 and earlier and RSLogix 5000 V16 and earlier not affected. — CISA ICSA-11-273-03A
- CVE record (read 2026-11-28): state PUBLISHED, assigner mitre; affected n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.08746, percentile 0.95908, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which patch fixes CVE-2011-3489?
Rockwell Automation patch AID 458689, for RSLogix 5000 V17, V18 and V19 and FactoryTalk Services Platform CPR9 to CPR9-SR4. Patching instructions are in Rockwell security advisory KB 456144, both on Rockwell's knowledge base.
Is RSLogix 5000 V16 affected?
No. CISA ICSA-11-273-03A says RSLogix 5000 V16 and earlier and FactoryTalk Services Platform CPR7 and earlier are not affected.
Can CVE-2011-3489 change a PLC program?
The published impact is a crash of RsvcHost.exe on the workstation. NVD scores availability only (A:P, no confidentiality or integrity impact), so it is a denial of service against the engineering software, not a way to change controller logic.
Is CVE-2011-3489 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0875 (percentile 95.9) in the 2026-11-27 dataset.