Security Advisory

CVE-2011-3491: Progea Movicon PowerHMI Heap Overflow

Last updated:
  • CVE-2011-3491

CVE-2011-3491 is a heap-based buffer overflow in Progea Movicon and Movicon PowerHMI 11.2.1085 and earlier, HMI/SCADA software. A request with a negative Content-Length value can crash the runtime or possibly run code on the HMI station. NVD scores it 10.0 (CVSS v2). Progea released a hotfix through its support group.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

16.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2011-3491 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Progea Movicon 11 and Movicon PowerHMIcpe:2.3:a:progea:movicon_powerhmi:*:*:*:*:*:*:*:*NVD: movicon_powerhmi up to and including 11.2.1085 (plus 11 and 11.0.1017); CISA ICSA-11-294-01: Movicon 11.2.1085.3 and earlier, PowerHMI 11.2.1085 and earlier. Fix: Progea hotfix from Progea support

What does this mean for affected devices?

NVD's description reads: "Heap-based buffer overflow in Progea Movicon / PowerHMI 11.2.1085 and earlier allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a negative Content-Length field." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119. NVD published the record on 2011-09-16; MITRE assigned it with no CNA score (NVD, CVE record).

What does CISA say?

CISA advisory ICSA-11-294-01 (CSAF), "Progea Movicon Power HMI Vulnerabilities", lists Movicon 11.2.1085.3 and earlier and Movicon PowerHMI 11.2.1085 and earlier. It covers three flaws, all CVSS v2 10.0 with CWE-119: this one, a heap overflow triggered by a long request (CVE-2011-3498), and a memory corruption through an EIDP packet with a large size field (CVE-2011-3499). NVD also references the earlier ICS-CERT alert ICS-ALERT-11-256-01 for this CVE.

How do I fix it?

Progea developed and released a hotfix for all three flaws; CISA tells users to contact the Progea support group for installation instructions. The Progea support address CISA cites now redirects to an Emerson automation page, so ask your current Movicon support channel for a release that includes the fix. Until then, keep Movicon stations off the internet, allow access to their web and runtime ports only from the operator network, and watch for runtime crashes.

CVE-2011-3493 (Cogent DataHub) and CVE-2012-4711 (WellinTech KingView) are comparable remote overflows in SCADA and HMI software. The memory corruption guide explains how vendors remove this class of bug, and the OT/ICS security guide for small manufacturers covers segmenting HMIs.

CVE-2011-3491 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.1624, a percentile of 97.6, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2011-09-16; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE-119; CPEs movicon_powerhmi up to and including 11.2.1085, 11, 11.0.1017; references include ICS-ALERT-11-256-01. — NVD
  • CISA ICSA-11-294-01 CSAF (read 2026-11-28): CVE-2011-3491/3498/3499 all CWE-119 CVSS v2 10.0; Movicon <=11.2.1085.3, PowerHMI <=11.2.1085; Progea hotfix via Progea support group. — CISA ICSA-11-294-01
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre; affected n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.16240, percentile 0.97570, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-11-294-01: Progea Movicon Power HMI Vulnerabilities
  3. CISA ICSA-11-294-01 CSAF (machine-readable advisory)
  4. CVE record CVE-2011-3491 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Movicon versions have CVE-2011-3491?

Movicon 11.2.1085.3 and earlier and Movicon PowerHMI 11.2.1085 and earlier, per CISA ICSA-11-294-01. NVD lists PowerHMI up to and including 11.2.1085.

Is there a fix?

Yes. Progea released a hotfix covering CVE-2011-3491, CVE-2011-3498 and CVE-2011-3499; CISA directs users to Progea support for the installation steps.

What are the sibling CVEs?

CVE-2011-3498 is a heap overflow from a long request and CVE-2011-3499 is a memory corruption through an EIDP packet with a large size field. Both are CVSS v2 10.0 in the same CISA advisory and share the same hotfix.

Is CVE-2011-3491 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.1624 (percentile 97.6) in the 2026-11-27 dataset.