CVE-2011-4509 is a weak default administrator password in the HMI web server of Siemens WinCC flexible, WinCC V11 (TIA Portal) and the SIMATIC TP, OP, MP, Comfort and Mobile Panels. Anyone who reaches the web server can guess or brute-force it. NVD scores it 10.0 (CVSS v2). The fix is to set a strong password, as the documentation in WinCC V11 SP2 Update 1 and WinCC flexible 2008 SP3 explains.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
2.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2011-4509 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens WinCC flexible 2004, 2005, 2007, 2008; WinCC V11 (TIA Portal); WinCC V11 Runtime Advanced; WinCC flexible Runtime; SIMATIC HMI panels TP, OP, MP, Comfort Panels, Mobile Panels | cpe:2.3:a:siemens:wincc_flexible:2008:*:*:*:*:*:*:* | Siemens SSA-345442: WinCC flexible 2004, 2005, 2007, 2008, WinCC V11 (TIA Portal), WinCC V11 Runtime Advanced, WinCC flexible Runtime and the TP/OP/MP/Comfort/Mobile panels configured with them; not affected: WinCC V11 Basic, WinCC V11 Runtime Professional, WinCC V6.x and V7.x. Fix: set a strong password per the documentation in WinCC V11 (TIA Portal) SP2 Update 1 / WinCC flexible 2008 SP3 |
What does this mean for affected devices?
NVD's description reads: "The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account, which makes it easier for remote attackers to obtain access via a brute-force approach involving many HTTP requests." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-264; there is no NVD v3 score. CERT/CC assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-02-03 (NVD, CVE record).
What do Siemens and CISA say?
Siemens ProductCERT advisory SSA-345442 explains that the web server runs on SIMATIC HMI panels and PC-based HMI devices when it is activated in the engineering project, for example through the "HTML pages", "Web service (SOAP)", "SIMATIC HMI HTTP server" or "OPC server" runtime options; it then "allows data retrieval and administration of the corresponding HMI device". Siemens rates this flaw (vulnerability 2 of 12) CVSS v2 base 10, temporal 8.7, and lists WinCC V11 Basic, WinCC V11 Runtime Professional and WinCC V6.x/V7.x as not affected. CISA covered it first in ICSA-11-356-01 (CSAF), "Siemens Simatic HMI Authentication Vulnerabilities", credited to Billy Rios and Terry McCorkle, and again in the combined WinCC advisory ICSA-12-030-01A (CSAF). The CSAF files score it CVSS v2 10.0 and map it to CWE-1392 (use of default credentials).
How do I fix it?
There is no code patch for the password itself: Siemens updated the product documentation in WinCC V11 (TIA Portal) SP2 Update 1 and WinCC flexible 2008 SP3 to show how to set a proper password during initial setup, and recommends that "the default password of the web server should always be changed as soon as possible". The same updates fix the related web-server flaws, such as predictable session tokens (CVE-2011-4508). Siemens adds that the web-server flaws cannot be exploited if TCP ports 80 and 443 of the device are blocked, so switch off the web server runtime options where nobody uses them and keep the HMI behind the cell firewall. The panels' Telnet service has no authentication at all (CVE-2011-4514); it is disabled by default from WinCC flexible 2008 SP3 and WinCC V11 SP2.
CVE-2012-3020 (Siemens Synco OZW web server) and CVE-2012-3013 (WAGO 758 industrial PCs) are other default-password flaws from the same era. The hard-coded credentials guide explains how device makers avoid shared factory passwords, and the OT/ICS security guide for small manufacturers covers segmenting HMIs.
CVE-2011-4509 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0198, a percentile of 81.1, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2012-02-03; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-264; CPEs wincc_flexible 2004/2005/2007/2008, wincc v11, wincc_runtime_advanced v11, wincc_flexible_runtime, simatic_hmi_panels comfort/mobile/mp/op/tp. — NVD
- CISA ICSA-11-356-01 CSAF (read 2026-11-27): CVE-2011-4509, CWE-1392, CVSS v2 10.0; WinCC flexible RT 2004-2008 SP2, WinCC Runtime Advanced V11-V11 SP2, SIMATIC panels TP/OP/MP/Mobile/Comfort; documentation updated to explain setting a proper password. — CISA ICSA-11-356-01
- CISA ICSA-11-356-01 web page (read 2026-11-27): weak default administrator password, easily brute-forced or guessed; researchers Billy Rios and Terry McCorkle. — CISA ICSA-11-356-01
- CISA ICSA-12-030-01A CSAF (read 2026-11-27): CVE-2011-4509 CVSS v2 10.0 among the WinCC vulnerabilities; weak default passwords addressed by documentation in WinCC V11 SP2 Update 1 and WinCC flexible 2008 SP3; telnet disabled by default from WinCC flexible 2008 SP3 and WinCC V11 SP2. — CISA ICSA-12-030-01A
- Siemens SSA-345442 V1.5 (published 2012-01-24, read 2026-11-27): affected and not-affected products; web server enabled via runtime options; vulnerability 2 (CVE-2011-4509) CVSS base 10, temporal 8.7; block ports 80/443; change the default password; documentation updates in WinCC V11 SP2 Update 1 and WinCC flexible 2008 SP3. — Siemens ProductCERT SSA-345442
- CVE record (read 2026-11-27): state PUBLISHED, assigner certcc; affected n/a / n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.01975, percentile 0.81126, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
- NVD
- CISA ICSA-11-356-01: Siemens Simatic HMI Authentication Vulnerabilities
- CISA ICSA-11-356-01 CSAF (machine-readable advisory)
- CISA ICSA-12-030-01A CSAF: Siemens SIMATIC WinCC Vulnerabilities
- Siemens SSA-345442: Multiple Vulnerabilities in WinCC flexible and WinCC V11 (TIA Portal)
- CVE record CVE-2011-4509 (CVE Services JSON)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Is there a firmware patch for CVE-2011-4509?
Not as a code change. Siemens fixed it with documentation shipped in WinCC V11 (TIA Portal) SP2 Update 1 and WinCC flexible 2008 SP3 that tells you to set a strong web server password during setup. Changing the default password on every panel is the fix.
Which Siemens HMI products are not affected?
Siemens SSA-345442 lists WinCC V11 (TIA Portal) Basic, WinCC V11 Runtime Professional and WinCC V6.x and V7.x as not affected. The affected panels are the TP, OP, MP, Comfort and Mobile Panels configured with WinCC flexible or WinCC V11.
Is the panel exposed if the web server is off?
Siemens says the web-server flaws need the HMI web server to be activated and reachable; if TCP ports 80 and 443 are blocked they cannot be exploited. Disable the HTML pages, SOAP, HTTP server and OPC server options where they are not needed.
Is CVE-2011-4509 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0198 (percentile 81.1) in the 2026-11-26 dataset.