Security Advisory

CVE-2026-12819: Delta Electronics DVP12SE PLC Unauthenticated Modbus TCP Access

Last updated:
  • CVE-2026-12819

CVE-2026-12819 is a missing-authentication vulnerability (CWE-306) in Delta Electronics' DVP12SE programmable logic controller: its Modbus TCP service accepts commands over the network with no authentication or access control at all, so any attacker who can reach the PLC can read and write coils, holding registers and relay states, and because Delta had not shipped a fix when the advisory was published, NVD has not assigned its own Primary CVSS score to this CVE.

Vulnerability summary

CVSS base score

N/A

No NVD score published as of

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2026-12819 · Source: NVD

Affected components

ComponentCPEVersion range
Delta Electronics DVP12SE Programmable Logic Controller—All firmware versions; Delta had not released a fixed version at the time CISA published its advisory and documented interim mitigations only

What does this mean for affected devices?

CVE-2026-12819 (CWE-306, missing authentication for critical function) affects Delta Electronics' DVP12SE programmable logic controller. NVD's description states: "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions" (NVD).

CISA's advisory ICSA-26-181-07, published June 30, 2026, states the impact: "Successful exploitation of these vulnerabilities could allow an attacker to remotely issue commands, modify operational values, interfere with control logic, and alter device behavior without authentication or privilege enforcement," and credits researcher Adm Bin Harbi (0xnoag) of Corvo Security with reporting the issue. The same advisory describes a companion flaw bundled with the same disclosure, CVE-2026-12818 (CWE-770, resource allocation without limits), which lets an attacker flood the same Modbus port "with a continuous stream of raw network packets" to exhaust the device's resources (CISA ICS Advisory ICSA-26-181-07).

CISA's advisory lists CVSS v3.1 9.8 (critical), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, and CVSS v4.0 9.3 (critical) for CVE-2026-12819. NVD's own record carries only the vendor-submitted Secondary CVSS v4.0 score of 9.3, sourced from Delta's own vulnerability notice; NVD's status for this CVE is "Deferred," meaning it has published no Primary score of its own, so this page does not present the 9.8 figure as an NVD-confirmed rating (NVD).

At the time the CISA advisory was published, Delta Electronics had released no patch: the advisory states Delta is "currently working on a fix" and recommends interim mitigations instead — enabling the DVP12SE's IP filter feature, setting PLC password protection, and implementing network isolation and firewall protection around the device (CISA ICS Advisory ICSA-26-181-07).

This CVE is not listed in the CISA Known Exploited Vulnerabilities catalog as of catalog version 2026.11.06, and FIRST scores the probability of exploitation at 0.0054 (45.8th percentile) as of 2026-11-06 (CISA KEV, FIRST EPSS).

Any DVP12SE PLC reachable from an untrusted network should have its IP filter and password protection enabled immediately, and should sit behind a firewall that blocks unsolicited Modbus TCP traffic, until Delta ships a patched firmware version.

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions. — NVD
  • "Successful exploitation of these vulnerabilities could allow an attacker to remotely issue commands, modify operational values, interfere with control logic, and alter device behavior without authentication or privilege enforcement." Reported by Adm Bin Harbi (0xnoag), Corvo Security. Companion flaw CVE-2026-12818 is a resource-allocation (CWE-770) DoS via flooding the same Modbus port. — CISA ICS Advisory ICSA-26-181-07
  • CISA lists CVSS v3.1 9.8 (critical) and v4.0 9.3 (critical) for CVE-2026-12819; NVD's own record carries only a vendor-submitted Secondary CVSS v4.0 score of 9.3, with NVD status 'Deferred' (no NVD Primary score published). — NVD
  • No fixed firmware was available at the time of the advisory; Delta is 'currently working on a fix.' Interim mitigations: enable the IP filter feature, set PLC password protection, implement network isolation and firewall protection. — CISA ICS Advisory ICSA-26-181-07
  • Not present in the CISA KEV catalog as of catalog version 2026.11.06; EPSS score is 0.0054 (45.8th percentile) as of 2026-11-06. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-26-181-07
  3. Delta Electronics Vulnerability Notice PCSA-2026-00011
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

What is CVE-2026-12819?

CVE-2026-12819 is a missing-authentication vulnerability (CWE-306) in Delta Electronics' DVP12SE programmable logic controller: its Modbus TCP service accepts commands over the network with no authentication or access control at all, so any attacker who can reach the PLC can read and write coils, holding registers and relay states, and because Delta had not shipped a fix when the advisory was published, NVD has not assigned its own Primary CVSS score to this CVE.

How severe is CVE-2026-12819?

CVE-2026-12819 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.

Is CVE-2026-12819 being actively exploited?

CVE-2026-12819 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.54%.

What is affected by CVE-2026-12819?

CVE-2026-12819 affects Delta Electronics DVP12SE Programmable Logic Controller.

Where does this CVE-2026-12819 information come from?

This advisory is based on NVD, CISA ICS Advisory ICSA-26-181-07, Delta Electronics Vulnerability Notice PCSA-2026-00011, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.