**CVE-2023-5390** is a file-read flaw in Honeywell controllers, published on 2024-01-31: an attacker could read files that expose limited information from the device. Honeywell's record names the ControlEdge UOC and VirtualUOC, while CISA names Experion controllers and the SMSC S300. NVD, Honeywell and CISA all score it 5.3.
Vulnerability summary
CVSS base score
5.3
Medium severity
EPSS score (FIRST)
0.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-5390 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell ControlEdge UOC and VirtualUOC | cpe:2.3:o:honeywell:controledge_unit_operations_controller_firmware:-:*:*:*:*:*:*:* | 510.1 to 510.2 HF13, 511.1 to 511.5 TCU4 HF3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU4 (CVE record); NVD CPE has no version range |
| Honeywell Experion PKS, Experion LX, PlantCruise (controllers) | — | Experion PKS before R510.2 HF14, R511.5 TCU4 HF4, R520.1 TCU5, R520.2 TCU4 HF2; LX and PlantCruise before R511.5 TCU4 HF4, R520.1 TCU5, R520.2 TCU4 HF2 (CISA ICSA-24-116-04) |
| Honeywell Safety Manager and Safety Manager SC (SMSC S300) | — | Safety Manager R15x, R16x to R162.10; Safety Manager SC R210.X, R211.1, R211.2, R212.1 (CISA ICSA-24-116-04) |
What does this mean for affected devices?
Honeywell, the CNA, says an attacker could exploit the flaw, "leading to files being read from the Honeywell Experion ControlEdge VirtualUOC and ControlEdge UOC", and that this "could be used to read files from the controller that may expose limited information from the device". It scores it CVSS 3.1 5.3 (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N), maps it to CWE-36, absolute path traversal, and lists 510.1 through 510.2 HF13, 511.1 through 511.5 TCU4 HF3, 520.1 through 520.1 TCU4 and 520.2 through 520.2 TCU4 (CVE record).
NVD's Primary score is the same 5.3 vector, with CWE-22, path traversal. Its configuration lists only ControlEdge UOC and VirtualUOC firmware, with no version range (NVD).
CISA's ICSA-24-116-04 of 2024-04-25 covers 16 CVEs reported by Claroty and Armis, and says this one could let an attacker "read from the Experion controllers or SMSC S300", scored 5.3 with CWE-36. It lists Experion PKS before R510.2 HF14, R511.5 TCU4 HF4, R520.1 TCU5 and R520.2 TCU4 HF2; Experion LX and PlantCruise before R511.5 TCU4 HF4, R520.1 TCU5 and R520.2 TCU4 HF2; Safety Manager R15x and R16x through R162.10; and Safety Manager SC R210.X, R211.1, R211.2 and R212.1. CISA's remedy is to upgrade to the version referenced in Honeywell's security notice or the CVE record. Honeywell's product security page lists it as "Experion Controller and SMSC S300 Modification Vulnerabilities", rated Critical for the advisory as a whole.
On its own the flaw leaks limited information, but it ships alongside file-modification flaws in the same advisory, and what an attacker reads can help plan those. A scanner that follows NVD will flag only UOC and vUOC, so check Experion controllers and Safety Manager SC against the fixed releases above as well.
CVE-2023-5390 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.0057, percentile 48.1, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Our Honeywell Experion and ControlEdge guide covers the rest of ICSA-24-116-04. CVE-2023-5389 is the matching file-modification flaw, and CVE-2022-30318 is an earlier ControlEdge flaw.
Evidence
- Honeywell CNA: files read from ControlEdge VirtualUOC and UOC, limited information; 5.3; CWE-36; ranges 510.1-510.2 HF13, 511.1-511.5 TCU4 HF3, 520.1-520.1 TCU4, 520.2-520.2 TCU4. — CVE.org record
- NVD Primary CVSS 3.1 5.3 C:L; CWE-22; CPE UOC and vUOC firmware without version. — NVD
- ICSA-24-116-04 (2024-04-25): Claroty and Armis; read from Experion controllers or SMSC S300; 5.3; CWE-36; product versions; upgrade per Security Notice or CVE record. — CISA ICSA-24-116-04: Honeywell Experion PKS, Experion LX, PlantCruise, Safety Manager (CSAF)
- Notice table lists Experion Controller and SMSC S300 Modification Vulnerabilities, ICSA-24-116-04, 16 CVEs, Critical. — Honeywell product security

Related advisories
Sources
Frequently asked questions
Which products does CVE-2023-5390 affect?
Honeywell's CVE record and NVD name ControlEdge UOC and VirtualUOC. CISA names Experion controllers and the SMSC S300 and lists Experion PKS, Experion LX, PlantCruise, Safety Manager and Safety Manager SC releases (per the CVE record, NVD and CISA ICSA-24-116-04).
What can an attacker get through CVE-2023-5390?
Files read from the controller that may expose limited information from the device. All three scorers rate confidentiality low and integrity and availability none (per the CVE record, NVD and CISA ICSA-24-116-04).
How do I fix CVE-2023-5390?
CISA advises upgrading to the version referenced in Honeywell's security notice or the CVE record, for example Experion PKS R510.2 HF14, R511.5 TCU4 HF4, R520.1 TCU5 or R520.2 TCU4 HF2 (per CISA ICSA-24-116-04).
Is CVE-2023-5390 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.0057, percentile 48.1, in the 2026-11-22 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?