Security Advisory

CVE-2024-27768: Unitronics UniStream Path Traversal

Last updated:
  • CVE-2024-27768

CVE-2024-27768 is a path traversal flaw in Unitronics UniStream PLC/HMI controllers that may allow remote code execution without authentication. Unitronics advisory 2024-002 lists all UniStream products with UniLogic before 1.35.227 as affected and names 1.35.227 or later as the fix. NVD and the CNA INCD both score it CVSS 3.1 9.8.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-27768 · Source: NVD

Affected components

ComponentCPEVersion range
Unitronics UniStream PLC/HMI series, all products (Unitronics advisory 2024-002), programmed with UniLogiccpe:2.3:a:unitronics:unilogic:*:*:*:*:*:*:*:*UniLogic before 1.35.227 (NVD CPE and Unitronics advisory); fixed in UniLogic 1.35.227 or later

What does this mean for affected devices?

The CVE record for CVE-2024-27768 reads "Unitronics Unistream Unilogic – Versions prior to 1.35.227 - CWE-22: 'Path Traversal' may allow RCE". The Israel National Cyber Directorate (INCD) published it as CNA on 2024-03-18 and credits Noam Moshe and Vera Mens of Claroty Team82. NVD's Primary score and INCD's score agree at CVSS 3.1 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H): network access, no privileges, no user interaction. NVD's CPE covers UniLogic before 1.35.227 (NVD, CVE record).

Which Unitronics products are affected?

Unitronics Cybersecurity Advisory 2024-002, titled "Remote Code Execution" and dated 18 March 2024, names the component as UniStream, the product as "All Products" and the affected version as UniLogic below 1.35.227. It describes the impact as "code can be executed by an attacker from a remote location". Neither the advisory nor the CVE record names the file or service that the traversal reaches, so this page does not guess at the endpoint.

How does it relate to the rest of the UniStream set?

Claroty Team82 found eight flaws, CVE-2024-27767 to CVE-2024-27774, and its write-up says some of them chain to let "an unauthorized attacker to connect to the UniStream PLC, fully control it, and execute arbitrary commands". CVE-2024-27768 and the authentication bypass CVE-2024-27767 are the two that NVD scores as needing no privileges. The command injection CVE-2024-27772 and the less trusted source flaw CVE-2024-27773 need a logged-in user. Team82 counted about 480 vulnerable UniStream devices reachable from the internet.

How do you fix or mitigate it?

Unitronics' advisory gives five steps: update to UniLogic 1.35.227 or later; verify that PLCs are not directly accessible from the internet and allow access only from defined addresses or through a VPN or ZTNA; apply long complex passwords and change the default installed password; use UniCloud for two-factor access, particularly for admin access; and keep devices on the latest security updates. The advisory does not say whether the controller needs a separate update, so after updating UniLogic, check the operating system version reported by each controller against Unitronics' release notes. Our Unitronics Vision and UniStream vulnerability guide covers the full Unitronics set, and the path traversal fix guide explains the weakness class.

Is it exploited?

CVE-2024-27768 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). The only Unitronics entry there is CVE-2023-6448, the Vision and Samba default password. FIRST EPSS gives CVE-2024-27768 0.00854, the 59.2nd percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Path traversal. Our practical guide covers how to detect, fix, verify and disclose it: How to fix path traversal in embedded firmware.

Evidence

  • NVD (read 2026-11-21): status Analyzed; published 2024-03-18, source [email protected]; description 'Unitronics Unistream Unilogic – Versions prior to 1.35.227 - CWE-22: Path Traversal may allow RCE'; NVD Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CNA Secondary 9.8, same vector; CWE-22 (CNA); CPE cpe:2.3:a:unitronics:unilogic versions before 1.35.227; references Claroty Team82 and the INCD advisory listing. — NVD
  • Unitronics Cybersecurity Advisory 2024-002 'Remote Code Execution', publication date 18 March 2024, read 2026-11-21: component UniStream, product All Products, affected UniLogic < 1.35.227; 'Code can be executed by an attacker from a remote location'; mitigations: update to UniLogic 1.35.227 or later, no direct internet access (defined addresses, VPN or ZTNA), long complex passwords and change the default, UniCloud 2FA, regular updates. — Unitronics
  • CVE record (CVE Services API, checked 2026-11-21): state PUBLISHED, CNA INCD, published 2024-03-18; affected 'Unitronics Unistream Unilogic' less than 1.35.227; CVSS 3.1 9.8; finder Noam Moshe, Vera Mens of Claroty Team82; solution 'Upgrade to version 1.35.227 or later.' — CVE.org
  • Claroty Team82 'New Critical Vulnerabilities in Unitronics UniStream Devices Uncovered', published 2024-03-18, read 2026-11-21: eight vulnerabilities that bypass UniStream authentication and authorization and can be chained to remote code execution; around 480 internet-exposed and vulnerable UniStream devices found with Shodan and Censys; devices are not preconfigured to be reachable online; disclosed to Unitronics, CISA and the Israel National Cyber Directorate; per-CVE list with CWE and CVSS v3. CVE-2024-27768 listed as CWE-22, CVSS v3 9.8, remote code execution. — Claroty Team82
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21; the only Unitronics entry is CVE-2023-6448 (added 2023-12-11). — CISA KEV
  • EPSS 0.00854, percentile 0.59203, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Unitronics Cybersecurity Advisory 2024-002: Remote Code Execution (CVE-2024-27768)
  3. Claroty Team82: New Critical Vulnerabilities in Unitronics UniStream Devices Uncovered
  4. CVE.org record (CNA: INCD, Israel National Cyber Directorate)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Does CVE-2024-27768 need a login?

No, according to the scores. NVD and INCD both use PR:N and UI:N, meaning no privileges and no user interaction, with network access. That puts it alongside the authentication bypass CVE-2024-27767 as the most exposed flaws in the 2024 UniStream set.

Which version fixes CVE-2024-27768?

UniLogic 1.35.227 or later. Unitronics advisory 2024-002, the CVE record and NVD's CPE all say UniLogic versions before 1.35.227 are affected, and Unitronics lists every UniStream product.

Which file or service does the path traversal reach?

None of the sources says. The CVE record, NVD and Unitronics' advisory describe only the weakness (CWE-22) and the result (remote code execution). Claroty's write-up names the classes of flaw and the chain to code execution but gives no technical details of the endpoint.

Is this the flaw used in the 2023 water utility attacks?

No. The 2023 attacks on US water facilities used Unitronics Vision controllers and the default password weakness CVE-2023-6448, the only Unitronics entry in the CISA KEV catalog as of 2026-11-21. Claroty Team82 says that campaign prompted its research into the newer UniStream series, which found this and seven other flaws.