**CVE-2023-5389** is a file-modification flaw in Honeywell controllers, published on 2024-01-30: an attacker could write files that change behaviour or lead to a malicious application being run. Honeywell's record names the ControlEdge UOC and VirtualUOC, while CISA names Experion controllers and the SMSC S300. NVD scores it 7.5, Honeywell and CISA 9.1.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-5389 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell ControlEdge UOC and VirtualUOC | cpe:2.3:o:honeywell:controledge_unit_operations_controller_firmware:-:*:*:*:*:*:*:* | 510.1 to 510.2 HF13, 511.1 to 511.5 TCU4 HF3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU4 (CVE record); NVD CPE has no version range |
| Honeywell Experion PKS, Experion LX, PlantCruise (controllers) | — | Experion PKS before R510.2 HF14, R511.5 TCU4 HF4, R520.1 TCU5, R520.2 TCU4 HF2; LX and PlantCruise before R511.5 TCU4 HF4, R520.1 TCU5, R520.2 TCU4 HF2 (CISA ICSA-24-116-04) |
| Honeywell Safety Manager and Safety Manager SC (SMSC S300) | — | Safety Manager R15x, R16x to R162.10; Safety Manager SC R210.X, R211.1, R211.2, R212.1 (CISA ICSA-24-116-04) |
What does this mean for affected devices?
Honeywell, the CNA, says an attacker could "modify files on Honeywell Experion ControlEdge VirtualUOC and ControlEdge UOC", and that this "could be used to write a file that may result in unexpected behavior based on configuration changes or updating of files that could result in subsequent execution of a malicious application if triggered". It scores the flaw CVSS 3.1 9.1 (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H), maps it to CWE-749, exposed dangerous method or function, and lists 510.1 through 510.2 HF13, 511.1 through 511.5 TCU4 HF3, 520.1 through 520.1 TCU4 and 520.2 through 520.2 TCU4 (CVE record).
NVD's Primary score is 7.5 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N, with NVD-CWE-Other. Its configuration lists only ControlEdge UOC and VirtualUOC firmware, with no version range (NVD).
CISA's ICSA-24-116-04 of 2024-04-25 covers 16 CVEs reported by Claroty and Armis, and describes this one as letting an attacker "modify files on Experion controllers or SMSC S300", scored 9.1 with CWE-749. It lists Experion PKS before R510.2 HF14, R511.5 TCU4 HF4, R520.1 TCU5 and R520.2 TCU4 HF2; Experion LX and PlantCruise before R511.5 TCU4 HF4, R520.1 TCU5 and R520.2 TCU4 HF2; Safety Manager R15x and R16x through R162.10; and Safety Manager SC R210.X, R211.1, R211.2 and R212.1. CISA's remedy is to upgrade to the version referenced in Honeywell's security notice or the CVE record. Honeywell's product security page lists it as "Experion Controller and SMSC S300 Modification Vulnerabilities", rated Critical.
For asset matching the gap matters: a scanner that follows NVD will flag only UOC and vUOC, while CISA's list adds Experion controllers and Safety Manager SC. Check all three product families against the fixed releases above.
CVE-2023-5389 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0078, percentile 56.8, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
Our Honeywell Experion and ControlEdge guide covers the rest of ICSA-24-116-04. CVE-2022-30318 is an earlier ControlEdge flaw, and CVE-2023-25178 is a C300 firmware-integrity flaw.
Evidence
- Honeywell CNA: modify files on ControlEdge VirtualUOC and UOC, possible malicious application execution; 9.1; CWE-749; ranges 510.1-510.2 HF13, 511.1-511.5 TCU4 HF3, 520.1-520.1 TCU4, 520.2-520.2 TCU4. — CVE.org record
- NVD Primary CVSS 3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N; NVD-CWE-Other; CPE UOC and vUOC firmware without version. — NVD
- ICSA-24-116-04 (2024-04-25): Claroty and Armis; modify files on Experion controllers or SMSC S300; 9.1; CWE-749; product versions; upgrade per Security Notice or CVE record. — CISA ICSA-24-116-04 (CSAF)
- Honeywell notice table lists Experion Controller and SMSC S300 Modification Vulnerabilities, ICSA-24-116-04, 16 CVEs, Critical. — Honeywell product security

Related advisories
Sources
Frequently asked questions
Which products does CVE-2023-5389 affect?
Honeywell's CVE record and NVD name ControlEdge UOC and VirtualUOC. CISA names Experion controllers and the SMSC S300 and lists Experion PKS, Experion LX, PlantCruise, Safety Manager and Safety Manager SC releases (per the CVE record, NVD and CISA ICSA-24-116-04).
Why does NVD score CVE-2023-5389 at 7.5 when Honeywell gives 9.1?
NVD rates integrity high but availability none. Honeywell and CISA rate both integrity and availability high, which gives 9.1 (per NVD and CISA ICSA-24-116-04).
How do I fix CVE-2023-5389?
CISA advises upgrading to the version referenced in Honeywell's security notice or the CVE record, for example Experion PKS R510.2 HF14, R511.5 TCU4 HF4, R520.1 TCU5 or R520.2 TCU4 HF2 (per CISA ICSA-24-116-04).
Is CVE-2023-5389 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0078, percentile 56.8, in the 2026-11-21 dataset (per CISA KEV and FIRST EPSS).