Security Advisory

CVE-2022-30318: ControlEdge Hard-Coded SSH Root Login

Last updated:
  • CVE-2022-30318

**CVE-2022-30318** is a hard-coded root credential for the SSH service of Honeywell ControlEdge PLC and RTU firmware through R151.1, published on 2022-08-31. The credential is not changed when the device is first commissioned, so anyone who can reach port 22 can get a root shell. NVD and CISA score it 9.8, and 151.2 fixes it.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-30318 · Source: NVD

Affected components

ComponentCPEVersion range
Honeywell ControlEdge PLC firmwarecpe:2.3:o:honeywell:controledge_plc_firmware:*:*:*:*:*:*:*:*before R151.2 (NVD CPE); through R151.1 (CVE record); fixed in 151.2 (CISA ICSA-22-242-06)
Honeywell ControlEdge RTU firmwarecpe:2.3:o:honeywell:controledge_rtu_firmware:*:*:*:*:*:*:*:*before R151.2 (NVD CPE); through R151.1 (CVE record); fixed in 151.2 (CISA ICSA-22-242-06)

What does this mean for affected devices?

The CVE record, filed by MITRE from Forescout's report FSCT-2022-0056, says the ControlEdge PLC and RTU product line "exposes an SSH service on port 22/TCP. Login as root to this service is permitted and credentials for the root user are hardcoded without automatically changing them upon first commissioning." It adds that the credentials "grant an attacker access to a root shell on the PLC/RTU, allowing for remote code execution, configuration manipulation and denial of service" (CVE record).

NVD's CVSS 3.1 score is 9.8 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CWE-798; MITRE, the CNA, gave no score. NVD's configuration lists ControlEdge PLC firmware and ControlEdge RTU firmware before R151.2 (NVD).

CISA's ICSA-22-242-06 of 2022-08-30 credits Daniel dos Santos and Jos Wetzels of Forescout Technologies, scores the flaw 9.8 and lists ControlEdge before 151.2. Its summary matches the CVE record: the root credentials "are hard-coded and not changed automatically when first commissioned", which may let an attacker with SSH access gain full control. The remedy is to upgrade to 151.2 or later. Honeywell's product security page lists the notice as "ControlEdge Hard-coded Credentials" for ControlEdge products, rated Critical.

The credential is in the firmware, so changing a password in the configuration is not a fix. Until devices run 151.2, allow SSH to ControlEdge PLCs and RTUs only from named engineering hosts and alert on any other SSH session to them.

CVE-2022-30318 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.019, percentile 80.2, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).

Our Honeywell Experion and ControlEdge guide covers ControlEdge alongside Experion PKS and LX. CVE-2022-30317 is the Experion LX flaw from the same Forescout research, and CVE-2023-5389 is a later file-modification flaw whose CVE record names the ControlEdge UOC.

How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.

Evidence

  • ControlEdge through R151.1; FSCT-2022-0056; SSH on 22/TCP, root login permitted, hard-coded credentials not changed at commissioning, root shell. — CVE.org record
  • NVD Primary CVSS 3.1 9.8; CWE-798; CPE controledge_plc_firmware and controledge_rtu_firmware before r151.2. — NVD
  • ICSA-22-242-06 (2022-08-30): ControlEdge before 151.2, CVSS 9.8, Forescout credit; upgrade to 151.2 or later. — CISA ICSA-22-242-06 (CSAF)
  • Honeywell notice table: ControlEdge Hard-coded Credentials, ICSA-22-242-06, ControlEdge Products, Critical, 2022-08-30. — Honeywell product security

Related advisories

Sources

  1. NVD
  2. CVE.org record
  3. CISA ICSA-22-242-06: Honeywell ControlEdge (CSAF)
  4. Honeywell product security notices
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which ControlEdge versions are affected by CVE-2022-30318?

The CVE record says ControlEdge through R151.1, NVD lists PLC and RTU firmware before R151.2, and CISA lists ControlEdge before 151.2 (per the CVE record, NVD and CISA ICSA-22-242-06).

How do I fix CVE-2022-30318?

CISA says Honeywell fixed it and advises upgrading to version 151.2 or later. Because the credential is hard-coded in the firmware, a configuration change does not remove it (per CISA ICSA-22-242-06 and the CVE record).

What access does CVE-2022-30318 give an attacker?

The CVE record says the credentials give a root shell on the PLC or RTU, allowing remote code execution, configuration manipulation and denial of service. CISA describes it as full control of the device (per the CVE record and CISA ICSA-22-242-06).

Is CVE-2022-30318 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.019, percentile 80.2, in the 2026-11-21 dataset (per CISA KEV and FIRST EPSS).