Security Advisory

CVE-2023-25178: Honeywell C300 Malicious Firmware Load

Last updated:
  • CVE-2023-25178

**CVE-2023-25178** is a firmware-integrity flaw in the Honeywell C300 process controller, published on 2023-07-13: the controller may be loaded with malicious firmware, which could enable remote code execution. NVD and Honeywell score it 9.8, while CISA scores it 7.5. CISA lists Experion PKS, LX and PlantCruise before R520.2 and recommends R520.2.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-25178 · Source: NVD

Affected components

ComponentCPEVersion range
Honeywell C300 controller firmwarecpe:2.3:o:honeywell:c300_firmware:*:*:*:*:*:*:*:*501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (NVD CPE, CVE record)
Honeywell Experion PKS, Experion LX and PlantCruise (C300 platforms)—before R520.2 per CISA ICSA-23-194-06; update to R520.2

What does this mean for affected devices?

Honeywell, the CNA, describes it in one line: "Controller may be loaded with malicious firmware which could enable remote code execution." Its record lists C300 releases 501.1 through 501.6 HF8, 510.1 through 510.2 HF12, 511.1 through 511.5 TCU3, 520.1 through 520.1 TCU4 and 520.2 through 520.2 TCU2 (CVE record).

NVD agrees with Honeywell on the score: both give CVSS 3.1 9.8 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, NVD's labelled Primary. Both map it to CWE-345, insufficient verification of data authenticity, and NVD's C300 firmware configuration uses the same five ranges (NVD).

CISA's ICSA-23-194-06 of 2023-07-13 covers nine Experion CVEs reported by Armis. It says "C300 may be loaded with malicious firmware which could enable remote code execution" but scores it lower, 7.5 with the CVSS 3.0 vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N. CISA lists Experion PKS, Experion LX and PlantCruise before R520.2 and recommends R520.2 for all three, downloaded from Honeywell's support portal. It also asks users to keep backup files on a drive or network location that only authorised users can reach. Honeywell's product security page lists the advisory as Critical, covering nine CVEs in versions before R520.2.

For an asset owner the risk is a controller that runs code the vendor did not sign. Until the C300 runs a fixed release, limit which hosts can reach controllers on the control network, keep firmware loads inside scheduled maintenance windows, and watch for unexpected transfers to controllers.

CVE-2023-25178 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0052, percentile 45.0, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).

Our Honeywell Experion and ControlEdge guide lists the other eight CVEs from the same advisory. CVE-2023-24480 and CVE-2023-25770 are C300 denial-of-service flaws from it, and CVE-2022-30317 is an earlier Experion LX firmware-manipulation flaw.

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • Honeywell CNA: controller may be loaded with malicious firmware enabling RCE; C300 ranges 501.1-501.6HF8, 510.1-510.2HF12, 511.1-511.5TCU3, 520.1-520.1TCU4, 520.2-520.2TCU2; CVSS 9.8. — CVE.org record
  • NVD Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; Honeywell 9.8; CWE-345; c300_firmware CPE ranges. — NVD
  • ICSA-23-194-06 (2023-07-13): Armis; C300 malicious firmware; CVSS 3.0 7.5 C:H/I:N/A:N; Experion PKS, LX, PlantCruise before R520.2; update to R520.2; restrict backup files. — CISA ICSA-23-194-06 (CSAF)
  • Honeywell notice table lists ICSA-23-194-06, Experion PKS, LX and PlantCruise versions prior to R520.2, 9 CVEs, Critical. — Honeywell product security

Related advisories

Sources

  1. NVD
  2. CVE.org record
  3. CISA ICSA-23-194-06: Honeywell Experion PKS, LX and PlantCruise (CSAF)
  4. Honeywell product security notices
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Why does CISA score CVE-2023-25178 at 7.5 when NVD gives 9.8?

CISA uses the CVSS 3.0 vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N, which counts only confidentiality impact. NVD and Honeywell rate confidentiality, integrity and availability all high, which gives 9.8 (per CISA ICSA-23-194-06 and NVD).

Which C300 releases are affected by CVE-2023-25178?

Honeywell and NVD list C300 501.1 through 501.6 HF8, 510.1 through 510.2 HF12, 511.1 through 511.5 TCU3, 520.1 through 520.1 TCU4 and 520.2 through 520.2 TCU2 (per the CVE record and NVD).

How do I fix CVE-2023-25178?

CISA recommends updating Experion PKS, Experion LX or PlantCruise to R520.2, available from the Honeywell support portal under Product Documents and Downloads (per CISA ICSA-23-194-06).

Is CVE-2023-25178 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0052, percentile 45.0, in the 2026-11-21 dataset (per CISA KEV and FIRST EPSS).