Security Advisory

CVE-2023-0052: SAUTER Nova BACnet Controller Missing Auth

Last updated:
  • CVE-2023-0052

CVE-2023-0052 is a missing authentication flaw in SAUTER Controls Nova 200-220 Series building automation controllers and BACnet cards. Telnet and FTP are the only management protocols, and they let an unauthorized user execute commands without credentials. NVD scores it 8.8 and CISA 9.8. SAUTER discontinued the line in 2016 and offers no fix, only network protection and replacement.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

1.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-0052 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
SAUTER Nova 220 (EYK220F001), Nova 230 (EYK230F001), Nova 106 (EYK300F001), moduNet300 (EY-AM300F001, EY-AM300F002)cpe:2.3:o:sauter-controls:nova_220_eyk220f001_firmware:*:*:*:*:*:*:*:*firmware 3.3-006 and earlier with BACnetstac 4.2.1 and earlier (CISA ICSA-23-012-05, NVD CPE); no fix, product line discontinued in 2016

What does this mean for affected devices?

The CVE record from CISA says: "SAUTER Controls Nova 200–220 Series with firmware version 3.3-006 and prior and BACnetstac version 4.2.1 and prior allows the execution of commands without credentials. As Telnet and file transfer protocol (FTP) are the only protocols available for device management, an unauthorized user could access the system and modify the device configuration, which could result in the unauthorized user executing unrestricted malicious commands." NVD's Primary analysis scores it 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), assuming low privileges; CISA, the CNA, scored it 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with no privileges. Both map it to CWE-306, missing authentication for a critical function (NVD, CVE record).

Which SAUTER devices are affected?

CISA's ICSA-23-012-05, released on 2023-01-12, lists the Nova 220 (EYK220F001) and Nova 230 (EYK230F001) DDC controllers with BACnet connection, the Nova 106 (EYK300F001) BACnet communication card and the moduNet300 (EY-AM300F001, EY-AM300F002), each with firmware 3.3-006 and earlier and BACnetstac 4.2.1 and earlier. NVD's configuration lists the same five models. CISA names the Critical Manufacturing and Energy sectors and worldwide deployment, with SAUTER headquartered in Switzerland. Jairo Alonso Ortiz, Aarón Flecha Menéndez and Iñaki Lázaro Ayanz of S21Sec reported the issues. The same advisory carries CVE-2023-0053, cleartext transmission of sensitive information (CWE-319, CISA 7.5). SAUTER's cybersecurity page lists ICSA-23-012-05 among its advisories and says that since August 2025 new SAUTER advisories are published through CERT@VDE.

How do you protect Nova controllers from CVE-2023-0052?

There is no firmware fix. SAUTER told CISA that the product line is no longer supported, as it was discontinued in 2016, and recommends that users protect building automation network access and evaluate and upgrade legacy systems to current solutions, contacting SAUTER for upgrade instructions. Until the controllers are replaced:

  • block Telnet and FTP to the controllers from everything except a dedicated engineering workstation;
  • keep the BACnet network segmented from office IT and unreachable from the internet;
  • put the Nova replacement in the building's capital plan, since the devices will receive no further firmware.

Another BACnet controller page on this site is CVE-2016-4495 in the KMC BAC-5051E, and CVE-2023-22804 is another controller with missing authentication. The BACnet protocol security guide covers the network side, and the authentication bypass fix guide the device side.

Is CVE-2023-0052 exploited?

CVE-2023-0052 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01006, the 61.96th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2023-01-20; NVD Primary CVSS v3.1 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CWE-306; CPEs sauter-controls nova_220, nova_230, nova_106, modunet300 EY-AM300F001/F002 firmware up to 3.3-006. — NVD
  • CISA ICSA-23-012-05 (released 2023-01-12, read 2026-11-27): Nova 220, Nova 230, Nova 106, moduNet300 firmware 3.3-006 and prior with BACnetstac 4.2.1 and prior; CVE-2023-0052 CWE-306 9.8; CVE-2023-0053 CWE-319 7.5; product line discontinued in 2016, no longer supported; sectors Critical Manufacturing, Energy; worldwide; HQ Switzerland; reported by S21Sec. — CISA ICSA-23-012-05
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2023-01-20, CNA CVSS v3.1 9.8; affected Nova 220, 230, 106 and moduNet300 firmware up to 3.3-006, BACnetstac up to 4.2.1. — CVE.org
  • SAUTER cybersecurity page (read 2026-11-27) lists ICSA-23-012-05 (12 Jan 2023) among SAUTER advisories; since August 2025 SAUTER advisories are published via CERT@VDE. — SAUTER cybersecurity page
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.01006, percentile 0.61956, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-23-012-05: SAUTER Controls Nova 200 - 220 Series (PLC 6) (CSAF)
  3. CISA ICSA-23-012-05 advisory page
  4. CVE.org record CVE-2023-0052
  5. SAUTER cybersecurity and advisories page
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Is there a firmware fix for CVE-2023-0052?

No. SAUTER told CISA the Nova 200-220 Series (PLC 6) line was discontinued in 2016 and is no longer supported. SAUTER recommends protecting building automation network access and upgrading to current systems.

Why is NVD's score lower than CISA's?

NVD scores 8.8 assuming the attacker needs low privileges. CISA, the CNA, scores 9.8 with no privileges, matching "execution of commands without credentials" in the description.

Which SAUTER models are affected?

Nova 220 (EYK220F001), Nova 230 (EYK230F001), Nova 106 (EYK300F001) and moduNet300 (EY-AM300F001, EY-AM300F002) with firmware 3.3-006 and earlier and BACnetstac 4.2.1 and earlier.

Is CVE-2023-0052 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01006 (61.96th percentile) in the 2026-11-26 dataset.