CVE-2022-41775 is an SQL injection in the Handler_CFG.ashx handler of Delta Electronics DIAEnergie, the industrial energy management software. Any logged-in user, even with low privileges, can inject SQL queries into the product's database. NVD scores it 8.8. Versions before v1.9.02.001 are affected; that fix came from Delta on request, and Delta's current advisory sets v1.11.00.022 as the release to run.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
0.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-41775 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Delta Electronics DIAEnergie | cpe:2.3:a:deltaww:diaenergie:*:*:*:*:*:*:*:* | Before v1.9.02.001 (CISA ICSA-22-298-06, NVD CPE); fix not publicly released, obtained from Delta; install v1.11.00.022 or later (Delta-PCSA-2026-00014) |
What does this mean for affected devices?
CISA's ICSA-22-298-06 says DIAEnergie "(versions prior to v1.9.02.001) is vulnerable to a SQL injection that exists in Handler_CFG.ashx. A low-privileged authenticated attacker could exploit this issue to inject arbitrary SQL queries" (CISA CSAF ICSA-22-298-06). Both NVD and CISA ICS, the CNA, assign CWE-89. The NVD record was published on 2022-11-17 (NVD).
How severe is CVE-2022-41775?
NVD's Primary score is CVSS v3.1 8.8, CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, identical to CISA's. The login requirement keeps it below 9.8, but DIAEnergie servers often have many user accounts, and CISA's risk summary for the advisory says the flaws let an attacker "retrieve and modify database contents and execute system commands." NVD's CPE data covers versions before 1.9.02.001.
ICSA-22-298-06 was published on 10 November 2022 and updated on 16 February 2023. It lists 14 DIAEnergie flaws reported by Michael Heinzl: five stored cross-site scripting flaws, eight SQL injections including this one, and the improper authorization CVE-2023-0822 added in the update.
How do you fix it?
CISA notes that Delta "did not publicly release v1.9.01.002, v1.9.02.001, and v1.9.03.001, which address these vulnerabilities", and asks users to contact Delta for them. Those builds are long superseded. The same handler was hit again by CVE-2024-42417 in 2024, and CVE-2024-25574 is another SQL injection in a later build. Delta's own advisory Delta-PCSA-2026-00014 of 18 September 2026 covers all DIAEnergie versions before v1.11.00.022 and tells users to contact Delta technical support for v1.11.00.022 or later, so that is the release to install; it also repeats Delta's general advice to keep DIAEnergie off the internet, behind a firewall isolated from the business network, and reachable remotely only through a VPN. Limit DIAEnergie accounts to the people who need them.
The Delta Electronics guide lists the DIAEnergie advisories with their fix versions, and the guide to OT/ICS security for small manufacturers covers the network separation that limits who can reach the server.
CVE-2022-41775 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0088, the 56.9th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): published 2022-11-17; status Modified; NVD Primary CVSS v3.1 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; CISA ICS (CNA) Secondary 8.8 same vector; CWE-89 (NVD Primary and CISA ICS); CPE deltaww diaenergie versionEndExcluding 1.9.02.001. — NVD
- ICSA-22-298-06 (published 2022-11-10, updated 2023-02-16): 14 DIAEnergie CVEs (5 CWE-79, 8 CWE-89, CVE-2023-0822 CWE-285); CVE-2022-41775 SQL injection in Handler_CFG.ashx before v1.9.02.001, low-privileged authenticated attacker, CVSS v3 8.8; v1.9.01.002, v1.9.02.001 and v1.9.03.001 not publicly released, contact Delta; reported by Michael Heinzl. — CISA CSAF
- CVE record (checked 2026-11-28): PUBLISHED, CNA icscert, published 2022-11-17; DIAEnergie affected 'All' in the CNA data; solution: v1.9.01.002 and v1.9.02.001 not publicly released, contact Delta. — CVE Program
- Delta-PCSA-2026-00014 (initial release and last revised 2026-09-18): DIAEnergie versions prior to v1.11.00.022 affected by CVE-2026-78308 to 78313; mitigation: contact Delta technical support to obtain v1.11.00.022 or later; general recommendations: no internet exposure, firewall isolation from the business network, VPN for remote access. — Delta Electronics
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.0088, percentile 0.56918, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which DIAEnergie versions are affected by CVE-2022-41775?
Versions before v1.9.02.001, per CISA ICSA-22-298-06 and NVD's CPE data.
Where do I get the fix?
CISA says Delta did not publicly release v1.9.02.001 and asks users to contact Delta. Delta-PCSA-2026-00014 now tells users to obtain v1.11.00.022 or later from Delta technical support.
Does an attacker need an account?
Yes, a low-privileged authenticated account, which is why the score is 8.8 rather than 9.8. Other DIAEnergie flaws from the same period need no login.
Is CVE-2022-41775 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27). FIRST EPSS gives it 0.0088, the 56.9th percentile, in the 2026-11-27 dataset.