Security Advisory

CVE-2022-2788: Proficy Machine Edition ZipSlip Flaw

Last updated:
  • CVE-2022-2788

CVE-2022-2788 is a ZipSlip path traversal in Emerson Proficy Machine Edition 9.80 and earlier: an attacker who implants a malicious .BLZ file on the PLC can have it travel through the engineering station onto Windows in a way that executes code. NVD scores it CVSS 7.3 and CISA 3.9. Emerson recommends non-administrator use and PLC authentication.

Vulnerability summary

CVSS base score

7.3

High severity

EPSS score (FIRST)

0.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-2788 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Emerson Proficy Machine Editioncpe:2.3:a:emerson:electric\'s_proficy:*:*:*:*:machine:*:*:*Proficy Machine Edition 9.80 and earlier (CISA ICSA-22-228-06; NVD CPE up to and including 9.80); mitigation: run as non-administrator, program PLCs only over a trusted network, enable PLC authentication

What does this mean for affected devices?

NVD's description says Proficy Machine Edition 9.80 and prior "is vulnerable to CWE-29 Path Traversal: '\..\Filename', also known as a ZipSlip attack, through an upload procedure which enables attackers to implant a malicious .BLZ file on the PLC. The file can transfer through the engineering station onto Windows in a way that executes the malicious code." NVD's Primary analysis scores it 7.3 (CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H) with CWE-22; its CPE covers Machine Edition up to and including 9.80 (NVD). CISA, the CNA, scored it 3.9 (CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:N/I:L/A:L) with CWE-29 (CVE record). The direction matters: here the PLC is the source and the engineering workstation is the target.

Which Machine Edition versions are affected?

CISA advisory ICSA-22-228-06 (CSAF), released on 2022-08-16, lists Proficy Machine Edition 9.80 and prior and covers six flaws, among them the project permissions flaw CVE-2022-2792 and the SRTP flaw CVE-2022-2793. CISA lists sectors from critical manufacturing and energy to water and wastewater, worldwide deployment and a US headquarters. Sharon Brizinov of Claroty Research reported the flaws. CISA's risk summary is that exploitation could allow hidden code execution on the connected PLC and malicious files being uploaded from the PLC to connected workstations. It reported no known public exploits.

How do I fix CVE-2022-2788?

The advisory names no fixed build. Emerson recommends installing Proficy Machine Edition as an administrator but running it as a non-administrator unless a specific function needs more rights, programming PLCs only over a trusted network rather than an untrusted one, and enabling authentication on the PLCs. It also points to the controls for the file upload flaw CVE-2022-2791: verified operators and restricted upload rights. Practical steps:

  • run Machine Edition under a standard Windows account on the engineering workstation;
  • turn on PLC authentication, which limits who can place files on the controller;
  • upload projects from PLCs only on the control network, never across untrusted segments.

The GE Proficy, CIMPLICITY and Historian guide covers Machine Edition next to the GE Proficy HMI products, and the path traversal fix guide explains how archive extraction paths escape the target folder.

Is CVE-2022-2788 exploited?

CVE-2022-2788 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.00292, the 14.32 percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Path traversal. Our practical guide covers how to detect, fix, verify and disclose it: How to fix path traversal in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2022-08-19; NVD Primary CVSS v3.1 7.3 CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H; ICS-CERT Secondary 3.9 CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:N/I:L/A:L; CWE-22 (NVD), CWE-29 (ICS-CERT); CPE emerson electric's_proficy (machine) up to and including 9.80. — NVD
  • CISA ICSA-22-228-06 CSAF (released 2022-08-16, read 2026-11-28): Proficy Machine Edition 9.80 and prior; CVE-2022-2788 CWE-29 ZipSlip via .BLZ file on the PLC, CVSS v3 3.9; mitigation: install as administrator, run as non-administrator, program PLCs only over a trusted network, enable PLC authentication, plus CVE-2022-2791 recommendations; reported by Sharon Brizinov, Claroty Research; no known public exploits. — CISA ICSA-22-228-06
  • CVE record (read 2026-11-28): state PUBLISHED, assigner icscert, published 2022-08-19; affected Emerson Electric Proficy Machine Edition <= 9.80; CNA CVSS v3.1 3.9 AV:L/AC:L/PR:L/UI:R/S:U/C:N/I:L/A:L; CWE-29. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.00292, percentile 0.14323, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-22-228-06: Emerson Proficy Machine Edition
  3. CISA ICSA-22-228-06 CSAF (machine-readable advisory)
  4. CVE record CVE-2022-2788 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is there a Machine Edition update that fixes CVE-2022-2788?

CISA ICSA-22-228-06 names no fixed build. Emerson recommends running Machine Edition as a non-administrator, programming PLCs only over a trusted network and enabling PLC authentication.

What is a ZipSlip flaw?

It is a path traversal during archive extraction: file names inside the archive point outside the target folder. Here the archive is a .BLZ file that the engineering station takes from the PLC.

Why does NVD score it 7.3 and CISA only 3.9?

NVD scores full confidentiality, integrity and availability impact on the workstation. CISA scores low integrity and availability impact and no confidentiality impact. Use the higher score for planning.

Is CVE-2022-2788 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.00292 (14.32 percentile) in the 2026-11-27 dataset.