Security Advisory

CVE-2022-29834: Mitsubishi Electric GENESIS64 / ICONICS Suite Mobile-Monitoring Path Traversal (Water/Wastewater SCADA-HMI)

Last updated:
  • CVE-2022-29834

CVE-2022-29834 is a path traversal vulnerability (CWE-22) in the mobile monitoring function of Mitsubishi Electric GENESIS64 and ICONICS Suite, a SCADA/HMI platform ICONICS markets for the water and wastewater industry among other critical infrastructure sectors: a remote, unauthenticated attacker can embed a malicious URL parameter in a monitoring-screen URL served to the mobile monitoring application to disclose arbitrary files from the GENESIS64/ICONICS Suite server, and NVD rates the flaw 7.5 (high) on CVSS v3.1.

Vulnerability summary

7.5

High

1.7%

EPSS score (FIRST)

No

CISA KEV catalog

2022-07-20

Published

Vulnerability ID: CVE-2022-29834 · Source: NVD

Affected components

ComponentCPEVersion range
Mitsubishi Electric GENESIS64 / ICONICS Suite SCADA-HMI software (mobile monitoring function)cpe:2.3:a:iconics:genesis64:10.97:*:*:*:*:*:*:*GENESIS64 and ICONICS Suite versions 10.97 to 10.97.1 (fixed by the 10.97 "Critical Fixes Rollup 4" and 10.97.1 "Critical Fixes Rollup 3" security updates, per Mitsubishi Electric vulnerability advisory 2022-008)

What does this mean for affected devices?

CVE-2022-29834 (CWE-22, path traversal) affects Mitsubishi Electric GENESIS64 and ICONICS Suite, SCADA/HMI software that ICONICS lists as serving the "Water and Wastewater" industry alongside energy, transportation and other smart-infrastructure verticals (ICONICS Digital Solutions).

NVD's description states: "Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1 ... allows a remote unauthenticated attacker to access to arbitrary files in the GENESIS64 server or ICONICS suite server and disclose information stored in the files by embedding a malicious URL parameter in the URL of the monitoring screen delivered to the GENESIS64 or ICONICS Suite mobile monitoring application and accessing the monitoring screen" (NVD).

NVD's Primary CVSS v3.1 score is 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N — network-reachable, low attack complexity, no privileges or user interaction required, confidentiality-only impact consistent with file disclosure rather than modification or denial of service; Mitsubishi Electric's own PSIRT submission recorded an identical Secondary score and vector (NVD).

Mitsubishi Electric's Vulnerability Advisory 2022-008 (released 19 July 2022) bundles CVE-2022-29834 with six related CVEs disclosed the same day — CVE-2022-33315, -33316, -33317, -33318, -33319 and -33320, covering deserialization, script-inclusion and out-of-bounds-read flaws across GENESIS64, ICONICS Suite, MC Works64 and GENESIS32 — and states that exploiting the path traversal "may result in information disclosure" by an attacker who leads a user to open a crafted monitoring-screen link. The advisory's remediation for GENESIS64/ICONICS Suite is to apply the "10.97 Critical Fixes Rollup 4" or "10.97.1 Critical Fixes Rollup 3" security updates via the ICONICS Community Portal, and recommends isolating control-system networks behind firewalls and not clicking links or opening attachments from untrusted sources as an interim mitigation (Mitsubishi Electric Vulnerability Advisory 2022-008).

The vulnerability is also tracked by Japan's JPCERT/CC-IPA coordinated vulnerability database as JVNVU#96480474, which cross-references CISA's ICS advisory ICSA-22-202-04, "ICONICS Suite and Mitsubishi Electric MC Works64 Products" (JVN JVNVU#96480474).

This CVE is not listed in the CISA Known Exploited Vulnerabilities catalog as of catalog version 2026.11.06, and FIRST scores the probability of exploitation at 0.01715 (77.6th percentile) as of 2026-11-08 (CISA KEV, FIRST EPSS).

Operators running GENESIS64 or ICONICS Suite 10.97 through 10.97.1 — including water/wastewater utilities using it for SCADA visualization and mobile monitoring — should apply the vendor's Critical Fixes Rollup updates and avoid opening monitoring-screen links from untrusted sources in the mobile monitoring app until patched.

How to fix this class of issueThis advisory's weakness class is Path traversal. Our practical guide covers how to detect, fix, verify and disclose it: How to fix path traversal in embedded firmware.

Evidence

  • A path traversal vulnerability in the mobile monitoring function of GENESIS64/ICONICS Suite 10.97 to 10.97.1 lets a remote unauthenticated attacker disclose arbitrary server files via a malicious URL parameter in a monitoring-screen URL. — NVD
  • NVD Primary CVSS v3.1 score 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N; Mitsubishi Electric PSIRT recorded an identical Secondary score and vector. — NVD
  • Mitsubishi Electric Vulnerability Advisory 2022-008 (19 July 2022) bundles CVE-2022-29834 with six related CVEs and directs GENESIS64/ICONICS Suite users to the 10.97 Critical Fixes Rollup 4 / 10.97.1 Critical Fixes Rollup 3 security updates. — Mitsubishi Electric Vulnerability Advisory 2022-008
  • Tracked as JVNVU#96480474, which cross-references CISA ICS advisory ICSA-22-202-04, "ICONICS Suite and Mitsubishi Electric MC Works64 Products." — JVN JVNVU#96480474
  • ICONICS lists "Water and Wastewater" among the Smart Infrastructure industries its SCADA/HMI products, including GENESIS64/ICONICS Suite, serve. — ICONICS Digital Solutions
  • Not present in the CISA KEV catalog as of catalog version 2026.11.06; EPSS score is 0.01715 (77.6th percentile) as of 2026-11-08. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Mitsubishi Electric Vulnerability Advisory 2022-008
  3. JVN JVNVU#96480474
  4. ICONICS Digital Solutions
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

What can an unauthenticated attacker actually retrieve by exploiting CVE-2022-29834?

By embedding a malicious URL parameter in a monitoring-screen link delivered to the GENESIS64 or ICONICS Suite mobile monitoring app, an attacker can disclose arbitrary files stored on the GENESIS64/ICONICS Suite server, without needing valid credentials (per NVD).

Which versions are affected and how is it fixed?

GENESIS64 and ICONICS Suite versions 10.97 through 10.97.1 are affected; Mitsubishi Electric's remediation is the '10.97 Critical Fixes Rollup 4' or '10.97.1 Critical Fixes Rollup 3' security updates via the ICONICS Community Portal (per Mitsubishi Electric Vulnerability Advisory 2022-008).

Was CVE-2022-29834 disclosed alongside other vulnerabilities?

Yes — Mitsubishi Electric's Vulnerability Advisory 2022-008 bundles it with six related CVEs (CVE-2022-33315 through -33320) disclosed the same day, covering deserialization, script-inclusion and out-of-bounds-read flaws across GENESIS64, ICONICS Suite, MC Works64 and GENESIS32 (per Mitsubishi Electric Vulnerability Advisory 2022-008).

Why does this vulnerability matter for critical infrastructure specifically?

ICONICS markets GENESIS64/ICONICS Suite as SCADA/HMI software for the water and wastewater industry among other smart-infrastructure sectors, so a file-disclosure flaw reachable without authentication is a direct risk to utility operators using the mobile monitoring function (per ICONICS Digital Solutions; per JVN JVNVU#96480474).