Security Advisory

CVE-2022-2792: Emerson Machine Edition Project Folder ACLs

Last updated:
  • CVE-2022-2792

CVE-2022-2792 is an access control flaw in Emerson Proficy Machine Edition 9.00 and earlier, the engineering software for PACSystems PLCs: it stores project data in a folder whose access control lists let other users change it. NVD scores it CVSS 7.5 and CISA 6.6. CISA's advisory names no fixed build, only Emerson's hardening advice.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-2792 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Emerson Proficy Machine Editioncpe:2.3:a:emerson:electric\'s_proficy:*:*:*:*:machine:*:*:*Proficy Machine Edition 9.00 and earlier (CISA ICSA-22-228-06; NVD CPE up to and including 9.0.0); no fixed build named; Emerson recommends the latest PAC Machine Edition and physical security

What does this mean for affected devices?

NVD's description says that Emerson Electric's Proficy Machine Edition version 9.00 and prior "stores project data in a directory with improper access control lists." NVD's Primary analysis scores it 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N), a network attack with a confidentiality impact, and maps it to CWE-284; its CPE covers Machine Edition up to and including 9.0.0 (NVD). CISA, the CNA, scored it 6.6 (CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:N/I:H/A:H): a local, low-privileged user who tampers with project files, with integrity and availability impact (CVE record). The two scores model different harms, reading project data versus changing it.

Which Proficy Machine Edition versions are affected?

CISA advisory ICSA-22-228-06 (CSAF), released on 2022-08-16, lists Machine Edition 9.00 and earlier for this flaw among six Machine Edition flaws reported by Sharon Brizinov of Claroty Research. Project folders hold the PLC logic that Machine Edition compiles and downloads, so write access by the wrong user matters: CISA's risk summary for the set is hidden code execution on the connected PLC. It reported no known public exploits.

How do I fix CVE-2022-2792?

According to CISA, Emerson intends to fix this flaw in a later Machine Edition version; the advisory names no fixed build. Until then, Emerson recommends the latest PAC Machine Edition and good physical security of devices and transmission paths. Practical steps:

  • tighten the NTFS permissions on Machine Edition project folders so only the engineers who program PLCs can write to them;
  • install Machine Edition as an administrator but run it as a non-administrator, as the same advisory recommends;
  • keep engineering workstations single-purpose and program PLCs only from the trusted network.

The companion SRTP flaw is CVE-2022-2793, and CVE-2019-13524 is a PACSystems RX3i denial of service. The GE Proficy, CIMPLICITY and Historian guide covers all six Machine Edition flaws, and the small manufacturers OT/ICS guide covers engineering workstation hygiene.

Is CVE-2022-2792 exploited?

CVE-2022-2792 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.00517, the 37.28th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2022-08-19; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N; ICS-CERT Secondary 6.6 CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:N/I:H/A:H; CWE-284, NVD-CWE-Other; CPE emerson electric's_proficy (machine) up to and including 9.0.0. — NVD
  • CISA ICSA-22-228-06 CSAF (released 2022-08-16, read 2026-11-28): CVE-2022-2792 Machine Edition 9.00 and prior stores project data in a directory with improper ACLs; CWE-284; CVSS v3 6.6; mitigation: Emerson intends a fix in a later version, recommends latest PAC Machine Edition and good physical security; install as administrator, run as non-administrator (CVE-2022-2788/2791 advice); reported by Sharon Brizinov, Claroty Research; no known public exploits. — CISA ICSA-22-228-06
  • CVE record (read 2026-11-28): state PUBLISHED, assigner icscert, published 2022-08-19; affected Emerson Electric Proficy Machine Edition <= 9.00; CNA CVSS v3.1 6.6 AV:L; CWE-284. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.00517, percentile 0.37283, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-22-228-06: Emerson Proficy Machine Edition
  3. CISA ICSA-22-228-06 CSAF (machine-readable advisory)
  4. CVE record CVE-2022-2792 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is there a fixed version for CVE-2022-2792?

CISA ICSA-22-228-06 names none. It says Emerson intends to fix the flaw in a later version and recommends the latest PAC Machine Edition with good physical security of devices and transmission paths.

What should I do on engineering workstations now?

Restrict write access to Machine Edition project folders to the engineers who program PLCs, run Machine Edition as a non-administrator, and program PLCs only from the trusted control network.

Why does NVD score it higher than CISA?

NVD's 7.5 models a network attacker reading project data. CISA's 6.6 models a local, low-privileged user changing project files, with integrity and availability impact.

Is CVE-2022-2792 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.00517 (37.28th percentile) in the 2026-11-27 dataset.