CVE-2022-3864 is a flaw in the update package signature check of Hitachi Energy Relion 670, 650 and SAM600-IO protection relays. A privileged user who loads a tampered update package makes the relay crash and restart, a temporary denial of service. NVD and Hitachi Energy score it 4.5. Fixed revisions are 2.2.1.9, 2.2.2.6, 2.2.3.7, 2.2.4.4 and 2.2.5.6.
Vulnerability summary
CVSS base score
4.5
Medium severity
EPSS score (FIRST)
0.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-3864 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Hitachi Energy Relion 670 series | cpe:2.3:o:hitachienergy:relion_670_firmware:*:*:*:*:*:*:*:* | 2.2.0 all revisions (no fixed revision listed); 2.2.1 up to 2.2.1.8, 2.2.2 up to 2.2.2.5, 2.2.3 up to 2.2.3.6, 2.2.4 up to 2.2.4.3, 2.2.5 up to 2.2.5.5; fixed in 2.2.1.9, 2.2.2.6, 2.2.3.7, 2.2.4.4, 2.2.5.6 (CISA ICSA-23-068-05) |
| Hitachi Energy Relion 650 series | cpe:2.3:o:hitachienergy:relion_650_firmware:*:*:*:*:*:*:*:* | 2.2.0 all revisions (no fixed revision listed); 2.2.1 up to 2.2.1.8, 2.2.4 up to 2.2.4.3, 2.2.5 up to 2.2.5.5; fixed in 2.2.1.9, 2.2.4.4, 2.2.5.6 (CISA ICSA-23-068-05) |
| Hitachi Energy SAM600-IO series | cpe:2.3:o:hitachienergy:relion_sam600-io_firmware:*:*:*:*:*:*:*:* | 2.2.1 up to 2.2.1.8; fixed in 2.2.1.9 (CISA ICSA-23-068-05) |
What does this mean for affected devices?
NVD carries Hitachi Energy's description: "A vulnerability exists in the Relion update package signature validation. A tampered update package could cause the IED to restart. After restart the device is back to normal operation." NVD's Primary score and Hitachi Energy's score are both CVSS v3.1 4.5 (CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:U/C:N/I:N/A:H). NVD and the CVE record name CWE-347, improper verification of cryptographic signature; CISA's advisory uses CWE-345, insufficient verification of data authenticity. The record was published on 2024-01-04 (NVD, CVE record).
What does a tampered package do?
According to CISA's ICSA-23-068-05, an attacker "who manages to get access with security privileges to the device" can start the update mechanism and supply a malicious update package. When the IED tries to verify it, it crashes and reboots, then returns to normal operation. The result is a temporary denial of service while the relay restarts; the description and vector give no confidentiality or integrity impact. The attacker needs high privileges and user interaction, which keeps the score at 4.5. Dimitri Gasser of Nozomi Networks, Johannes Willbold of Ruhr-Universität Bochum, William Blonay and Flavio Avato reported it.
Which Relion versions are affected and fixed?
| Series and version | Affected revisions | Fixed revision |
|---|---|---|
| Relion 670, 650: 2.2.0 | all | none listed; apply the general mitigations |
| Relion 670, 650, SAM600-IO: 2.2.1 | up to 2.2.1.8 | 2.2.1.9 |
| Relion 670: 2.2.2 | up to 2.2.2.5 | 2.2.2.6 |
| Relion 670: 2.2.3 | up to 2.2.3.6 | 2.2.3.7 |
| Relion 670, 650: 2.2.4 | up to 2.2.4.3 | 2.2.4.4 |
| Relion 670, 650: 2.2.5 | up to 2.2.5.5 | 2.2.5.6 |
The CISA advisory, based on Hitachi Energy's advisory 8DBD000146, was last updated on 2026-02-03; the 2.2.1.9 fix was added in the 2026-01-27 revision. The CVE record and NVD's CPE list still mark all revisions of each version as affected.
What should substation operators do?
Install the fixed revision for each version branch. For 2.2.0 relays, the advisory lists only the general mitigation factors: no direct internet connection, a firewall with a minimal number of exposed ports, physical protection, and proper password policies, which matter most here because the attack starts with a privileged login. The same advisory points to the product technical manual for disabling "Field Service Tool access". Limit who holds security-level accounts on the relays.
Other controllers that accept unverified code or packages include CVE-2022-31207 on Omron CS/CJ/CP PLCs and CVE-2019-10943 on Siemens S7 PLCs. See the ABB AC500, RTU500 and Relion guide and the weak cryptography fix guide.
CVE-2022-3864 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00353, the 29.5th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2024-01-04; NVD Primary CVSS v3.1 4.5 AV:N/AC:L/PR:H/UI:R/S:U/C:N/I:N/A:H, Hitachi Energy Secondary 4.5; CWE-347; CPE relion_670_firmware 2.2.0-2.2.5, relion_650_firmware 2.2.0, 2.2.1, 2.2.4, 2.2.5, relion_sam600-io_firmware 2.2.1. — NVD
- CISA ICSA-23-068-05, CSAF read 2026-11-23 (revisions 2023-02-28, 2025-05-27, 2026-01-27, 2026-02-03): CWE-345, CVSS v3.1 4.5; affected 670/650 2.2.0 all revisions, 2.2.1 up to 2.2.1.8 (incl. SAM600-IO), 670 2.2.2 up to 2.2.2.5, 2.2.3 up to 2.2.3.6, 2.2.4 up to 2.2.4.3, 2.2.5 up to 2.2.5.5; fixes 2.2.1.9, 2.2.2.6, 2.2.3.7, 2.2.4.4, 2.2.5.6; 2.2.0: general mitigation factors; Field Service Tool access note; references Hitachi Energy 8DBD000146; acknowledgments Nozomi Networks (Dimitri Gasser), Johannes Willbold, William Blonay, Flavio Avato. — CISA ICSA-23-068-05
- CVE record (checked 2026-11-23): state PUBLISHED, CNA Hitachi Energy, published 2024-01-04; Relion 670/650/SAM600-IO 2.2.0-2.2.5 all revisions; CWE-347; CNA CVSS v3.1 4.5. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.00353, percentile 0.29543, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Relion firmware fixes CVE-2022-3864?
2.2.1.9, 2.2.2.6, 2.2.3.7, 2.2.4.4 and 2.2.5.6 for the matching version branch (CISA ICSA-23-068-05). Version 2.2.0 has no fixed revision listed; the advisory gives general mitigations for it.
Can an attacker install malicious firmware this way?
The advisory describes a crash during verification of the tampered package, followed by a restart and a return to normal operation. It reports no confidentiality or integrity impact, only a temporary denial of service.
What does an attacker need?
Access to the IED with security privileges, so that the update mechanism can be started, plus user interaction according to the CVSS vector. Strict control of privileged relay accounts is therefore the main mitigation.
Is CVE-2022-3864 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00353 (29.5th percentile) in the 2026-11-22 dataset.