Security Advisory

CVE-2021-27440: GE Reason DR60 Hard-Coded Password

Last updated:
  • CVE-2021-27440

CVE-2021-27440 is a hard-coded password (CWE-798) in the GE Reason DR60 digital fault recorder. All firmware before 02A04.1 contains a built-in password for authentication, so an attacker who knows it can log in. NVD and CISA score it 9.8. GE fixed it in firmware 02A04.1.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-27440 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
GE Reason DR60 digital fault recordercpe:2.3:o:ge:reason_dr60_firmware:*:*:*:*:*:*:*:*firmware before 02A04.1 (NVD versionEndExcluding 02a04.1, CISA ICSA-21-082-03); fix: firmware 02A04.1 or later

What does this mean for affected devices?

The CVE record from CISA says: "The software contains a hard-coded password it uses for its own inbound authentication or for outbound communication to external components on the Reason DR60 (all firmware versions prior to 02A04.1)." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CISA's advisory gives the same 9.8. NVD classifies it as CWE-798, use of hard-coded credentials; CISA as CWE-259, use of hard-coded password. NVD published the record on 2021-03-25; its configuration covers DR60 firmware before 02a04.1 (NVD, CVE record).

What is the impact on a DR60?

CISA's ICSA-21-082-03, released on 2021-03-23, says the flaws could let an attacker "take full control of the digital fault recorder (DFR), remotely execute code, or escalate privileges". The advisory has two more CVEs: code injection (CVE-2021-27438, CVSS 8.8) and execution with unnecessary privileges (CVE-2021-27454, CVSS 7.8). CISA lists the Communications, Critical Manufacturing, Energy, Healthcare, Transportation and Water sectors, and worldwide deployment. The Thales OT Security Team reported the issues to GE. CISA reported no known public exploits.

How do you fix CVE-2021-27440?

GE recommends upgrading DR60 units to firmware 02A04.1 or higher, which corrects all three flaws; upgrade and verification steps are in the product user's manual, and GE's publication GES-2021-002 has the details. GE also asks owners to:

  • place DR60 devices inside the control system network security perimeter;
  • add access controls and monitoring, such as an intrusion detection system;
  • follow the product secure deployment guide and, for utilities, their NERC CIP controls (see the NERC CIP-005 electronic security perimeter guide).

Other GE grid device flaws on this site are the UR relay factory-mode issue CVE-2021-27426 and the VxWorks allocator flaw in UR relays, CVE-2020-28895. The hard-coded credentials fix guide explains how device makers remove built-in passwords, and the GE Vernova UR relay guide covers GE grid devices.

Is CVE-2021-27440 exploited?

CVE-2021-27440 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01399, the 72.65th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2021-03-25; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 7.5; CWE-798 (NVD Primary), CWE-259 (ICS-CERT); CPE ge reason_dr60_firmware versionEndExcluding 02a04.1 on reason_dr60 hardware. — NVD
  • CISA ICSA-21-082-03 CSAF (released 2021-03-23, read 2026-11-27): GE DR60 firmware < 02A04.1; CVE-2021-27440 CWE-259 CVSS v3.0 9.8; siblings CVE-2021-27438 (CWE-94, 8.8), CVE-2021-27454 (CWE-250, 7.8); impact: full control of the DFR, remote code execution, privilege escalation; GE recommends upgrade to firmware v02A04.1 or higher, instructions in the user's manual, see GE publication GES-2021-002; defense in depth inside the control system security perimeter, access controls, IDS, NERC-CIP, secure deployment guide; reported by Thales OT Security Team; sectors Communications, Critical Manufacturing, Energy, Healthcare and Public Health, Transportation Systems, Water and Wastewater; no known public exploits. — CISA ICSA-21-082-03
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2021-03-25; the record carries no CNA CVSS metric; affected product Reason DR60; reference is the CISA advisory. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.01399, percentile 0.72654, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-21-082-03: GE Reason DR60 (CSAF)
  3. CISA ICSA-21-082-03 advisory page
  4. CVE.org record CVE-2021-27440
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which DR60 firmware fixes CVE-2021-27440?

Firmware 02A04.1 or higher. GE's publication GES-2021-002 and the DR60 user's manual describe the upgrade and how to verify it (CISA ICSA-21-082-03).

What else does the 02A04.1 update fix?

The same update corrects CVE-2021-27438, a code injection flaw (CVSS 8.8), and CVE-2021-27454, execution with unnecessary privileges (CVSS 7.8).

How should DR60 units be protected until they are upgraded?

GE recommends keeping them inside the control system security perimeter with access controls and monitoring such as an intrusion detection system, following the secure deployment guide and NERC CIP practice.

Is CVE-2021-27440 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01399 (72.65th percentile) in the 2026-11-26 dataset.