CVE-2021-22283 is an MMS file handling flaw in ABB Relion 611, 615, 620 and REX640 protection relays and related Distribution Automation devices. An MMS client that opens files without closing them puts the relay into internal fault 7 and stops communication to SCADA. NVD scores it 5.5, ABB 6.2. Fixed firmware exists for some series only.
Vulnerability summary
CVSS base score
5.5
Medium severity
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-22283 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| ABB Relion 615 series protection relays (IEC, CN) | cpe:2.3:o:abb:relion_615_iec_firmware:*:*:*:*:*:*:*:* | IEC 4.0 FP1 before 4.1.9 (Fix 2), CN 4.0 FP1 before 4.1.8 (Fix 2), IEC 5.0 before 5.0.12 (Fix 1), IEC 5.0 FP1 before 5.1.20 (Fix 2); IEC/CN 2.0 to 4.0, CN 5.0 FP1 and REF615/RED615 1.x: all firmware, no fix listed (ABB 2NGA001147 Rev B) |
| ABB Relion 615 series ANSI and 620 series ANSI protection relays | cpe:2.3:o:abb:relion_615_ansi_firmware:*:*:*:*:*:*:*:* | 615 ANSI 2.0, 4.0, 4.0 FP1, 4.0 FP2, 5.0 FP1 and 620 ANSI: all firmware, no fix listed (ABB 2NGA001147 Rev B) |
| ABB Relion 620 series IEC/CN protection relays | cpe:2.3:o:abb:relion_620_iec_firmware:*:*:*:*:*:*:*:* | IEC/CN 2.0 before 2.0.11 (Fix 1), IEC/CN 2.0 FP1 before 2.1.15 (Fix 2); RER620: all firmware, no fix listed (ABB 2NGA001147 Rev B) |
| ABB Relion REX640 protection relay | cpe:2.3:o:abb:rex640_pcl3_firmware:*:*:*:*:*:*:*:* | PCL1 before 1.0.8, PCL2 before 1.1.4, PCL3 before 1.2.1 (all Fix 2) (ABB 2NGA001147 Rev B) |
| ABB Relion 611 series, RER615, REC615 and SMU615 | cpe:2.3:o:abb:relion_611_firmware:*:*:*:*:*:*:*:* | 611 series before 2.0.3 (Fix 1), RER615 before 2.0.3 (Fix 1), REC615 before 2.0.3 (Fix 1), SMU615 before 1.0.2 (Fix 2); REF615R and eVD4 with RBX615: all firmware, no fix listed (ABB 2NGA001147 Rev B) |
What does this mean for affected devices?
ABB's advisory 2NGA001147, Rev B of 2022-12-19, traces the flaw to on-site substation testing: disturbance records could not be retrieved after a few attempts and the relay raised internal fault code 7. ABB found that MMS clients opening multiple files without closing them hit the open file handle limit, which then "blocked other protocols and internal file handling from accessing the file system." An attacker with a crafted MMS client can stop communication to the SCADA system and set the relay to internal fault state. NVD's Primary score is CVSS v3.1 5.5 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H); ABB, the CNA, scores 6.2 with no privileges required (AV:L/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). Both list CWE-665. The CVE record was published on 2023-02-28, more than a year after ABB's first advisory revision of 2021-11-29, which ABB's alerts and notifications page dates 2021-12-16 (NVD, CVE record).
Which devices have a fix?
ABB distinguishes two fixes. Fix 1 limits the number of files an MMS client can open at once, but the fault can still appear when a client reads files quickly, for example once per second. Fix 2 changes how the MMS server component is initialized, includes Fix 1 and "completely solves the problem". Fix 2 firmware: 615 series IEC 4.0 FP1 4.1.9, CN 4.0 FP1 4.1.8, IEC 5.0 FP1 5.1.20, 620 series IEC/CN 2.0 FP1 2.1.15, REX640 PCL1 1.0.8, PCL2 1.1.4, PCL3 1.2.1 and SMU615 1.0.2. Fix 1 firmware: 611 series 2.0.3, 615 IEC 5.0 5.0.12, 620 IEC/CN 2.0 2.0.11, RER615 2.0.3 and REC615 2.0.3. All firmware of the older 615 IEC/CN/ANSI releases, the ANSI 4.0 FP1 to 5.0 FP1 releases, 620 ANSI, RER620, REF615R and eVD4 with RBX615 is listed as affected with no fix. The CVE record lists only the series that have fixed firmware; NVD's CPE configuration also covers the unfixed ones.
What if there is no fixed firmware?
ABB answers "No" to remote exploitation because the station network is normally local, but an attacker with access to the control system network can use a crafted MMS client. Its defensive measures: keep the relays off the Internet and use a VPN for remote access, put the control network behind a firewall, read disturbance records over the file transfer protocol instead of MMS file transfer, use the latest MMS file transfer client when MMS file transfer has to act as a proxy, and on REX640 disable MMS on ports that do not need it. The ABB AC500, RTU500 and Relion guide covers the Relion advisories, CVE-2019-18253 is an earlier Relion 670 MMS flaw, and the IEC 61850 protocol security guide covers MMS exposure in substations.
CVE-2021-22283 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00171, the 6.5th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2023-02-28; NVD Primary CVSS v3.1 5.5 AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H; ABB Secondary 6.2 AV:L/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-665; CPE covers 611, 615 IEC/CN/ANSI, 620 IEC/CN/ANSI, REX640 PCL1-3, RER615, RER620, REC615, REF615R, RED615, REF615, SMU615, eVD4 firmware with the fixed-version boundaries. — NVD
- ABB 2NGA001147 Rev B (2022-12-19; Rev A 2021-11-29), read 2026-11-23: affected products and versions table with Fix 1 / Fix 2 firmware; Fix 1 limits concurrent files, Fix 2 changes MMS server initialization and completely solves the problem; fault code 7; CVSS v3.1 6.2; not remotely exploitable per ABB; defensive measures (no Internet exposure, VPN, firewall, file transfer protocol for disturbance records, latest MMS file transfer client, REX640 disable unused MMS ports). — ABB 2NGA001147
- ABB cybersecurity alerts and notifications page, read 2026-11-23: '2021-12-16 (Updated 2022-12-19): Cyber Security Advisory - MMS File Transfer Vulnerability impact on Distribution Automation products'. — ABB
- CVE record (checked 2026-11-23): state PUBLISHED 2023-02-28; CNA ABB; affected list covers 611, 615 IEC 4.0 FP1/CN 4.0 FP1/IEC 5.0/IEC 5.0 FP1, 620 IEC/CN 2.0 and 2.0 FP1, REX640 PCL1-3, RER615, REC615, SMU615 with 'before' fixed versions. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.00171, percentile 0.06533, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What is the difference between Fix 1 and Fix 2?
Fix 1 limits how many files an MMS client can open at once; ABB says the fault can still appear when a client reads files quickly. Fix 2 changes how the MMS server is initialized, includes Fix 1 and solves the problem completely.
Which relays have no fixed firmware for CVE-2021-22283?
ABB 2NGA001147 Rev B lists all firmware of REF615 and RED615 1.x, 615 IEC/CN 2.0 to 4.0, 615 ANSI 2.0 to 5.0 FP1, 615 CN 5.0 FP1, 620 ANSI, RER620, REF615R and eVD4 with RBX615 as affected with no fix.
How can the fault be avoided without a firmware update?
ABB recommends reading disturbance records over the file transfer protocol instead of MMS file transfer, using the latest MMS file transfer client, keeping the relays behind a firewall and off the Internet, and on REX640 disabling MMS on ports that do not need it.
Is CVE-2021-22283 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00171 (6.5th percentile) in the 2026-11-22 dataset.
Questions about this page?