CVE-2021-22284 is a code execution flaw in ABB OPC Server for AC 800M, the OPC server shipped with 800xA, Control Builder Safe and Compact Product Suite. Weak access control on its COM interfaces lets a low-privileged user run code on the OPC Server node. NVD scores it 8.8, ABB and CISA 8.4. Version 6.1.0-0 and later and 6.0.0-4 correct it.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
0.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-22284 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| ABB OPC Server for AC 800M in 800xA, Control Software for AC 800M | cpe:2.3:a:abb:opc_server_for_ac_800m:*:*:*:*:*:*:*:* | 5.1.0-x, 5.1.1-x, 6.0.0-1 to 6.0.0-3; corrected in 6.1.0-0 and later and 6.0.0-4 (ABB 7PAA000908 Rev A); NVD CPE 5.1.0-0 up to excluding 6.0.0-4 |
| ABB OPC Server for AC 800M in Control Builder Safe | — | Control Builder Safe 1.x (OPC Server 5.1.1-1) and 2.0 (OPC Server 6.0.0-1) (ABB 7PAA000908 Rev A) |
| ABB OPC Server for AC 800M in Compact Product Suite - Control and I/O | — | 5.1.0-x, 5.1.1-x, 6.0.0-x (ABB 7PAA000908 Rev A) |
What does this mean for affected devices?
ABB's advisory 7PAA000908, Rev A of 2022-01-24, says the flaw "is caused by improper configuration of access control list for COM interfaces" in OPC Server for AC 800M. An authenticated user with low privileges can insert and execute arbitrary code in the node that runs the OPC Server. NVD's Primary score is CVSS v3.1 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), with a CVSS v2 6.5. ABB, the CNA, scores 8.4 (AV:A/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H): adjacent network, user interaction and changed scope. CISA's ICSA-22-074-01 of 2022-03-15 uses ABB's 8.4. ABB and NVD list CWE-732; CISA lists CWE-250. The CVE record was published on 2022-02-04 (NVD, CVE record).
Which installations are affected?
ABB lists OPC Server for AC 800M 5.1.0-x, 5.1.1-x and 6.0.0-1 to 6.0.0-3 in 800xA Control Software for AC 800M, the OPC Server 5.1.1-1 and 6.0.0-1 builds in Control Builder Safe 1.x and 2.0, and 5.1.0-x, 5.1.1-x and 6.0.0-x in Compact Product Suite - Control and I/O. NVD's CPE covers OPC Server for AC 800M from 5.1.0-0 up to, but not including, 6.0.0-4. ABB states that neither the AC 800M High Integrity nor the process automation controllers are affected, and that functional safety is not affected because the OPC Server is non-SIL. William Knowles at Applied Risk reported the flaw.
Fix and mitigation
ABB says the issue is corrected in 800xA Control Software for AC 800M 6.1.0-0 and later and in 6.0.0-4; customers on 5.1 or older should move to a supported version such as 6.1 or later. ABB lists no workaround. Because the weakness sits in a COM interface, ABB recommends COM/DCOM hardening: turn off DCOM and make sure only valid users can access the OPC Server COM objects locally. ABB answers "Yes" to remote exploitation for an attacker with network access to a system node. The ABB AC500, RTU500 and Relion guide covers the AC 800M and 800xA advisories, CVE-2021-22277 is the AC 800M MMS denial of service, and the OPC UA security guide covers moving away from DCOM-based OPC.
CVE-2021-22284 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00831, the 58.5th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2022-02-04; NVD Primary CVSS v3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H and CVSS v2 6.5; ABB Secondary 8.4 AV:A/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H; CWE-732; CPE opc_server_for_ac_800m 5.1.0-0 up to excluding 6.0.0-4. — NVD
- ABB 7PAA000908 Rev A (2022-01-24), read 2026-11-23: affected versions per product; corrected in 6.1.0-0 and later and 6.0.0-4; CVSS v3.1 8.4; cause: improper ACL configuration for COM interfaces; COM/DCOM hardening mitigation; no workarounds; remotely exploitable with network access; functional safety not affected (OPC Server non-SIL); AC 800M HI and PA controllers not affected. — ABB 7PAA000908
- CISA ICSA-22-074-01 CSAF (released 2022-03-15), read 2026-11-23: CWE-250, CVSS v3 8.4 AV:A/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H; update to 6.1.0-0 or later or 6.0.0-4. — CISA ICSA-22-074-01
- CVE record (checked 2026-11-23): state PUBLISHED; CNA ABB; credit William Knowles at Applied Risk. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.00831, percentile 0.585, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which OPC Server for AC 800M version fixes CVE-2021-22284?
ABB 7PAA000908 says the flaw is corrected in 800xA Control Software for AC 800M 6.1.0-0 and later and in 6.0.0-4. Users on 5.1 or older should move to a supported version such as 6.1 or later.
Are AC 800M controllers affected?
No. ABB states that neither the AC 800M High Integrity nor the process automation controllers are affected. The code runs on the Windows node that hosts the OPC Server, and ABB says functional safety is not affected because the OPC Server is non-SIL.
Why do NVD and ABB give different scores?
NVD scores a network attack vector with no user interaction (8.8). ABB and CISA score an adjacent-network attack that needs user interaction but changes scope (8.4).
What can be done before updating?
ABB lists no workaround but recommends COM/DCOM hardening: turn off DCOM and make sure only valid users can access the OPC Server COM objects locally. As of 2026-11-23 the CVE is not in CISA KEV (catalog 2026.11.20) and EPSS is 0.00831 (2026-11-22).