Security Advisory

CVE-2021-22277: ABB AC 800M MMS denial of service

Last updated:
  • CVE-2021-22277

CVE-2021-22277 is a denial of service in the MMS protocol stack of ABB AC 800M controller firmware. A crafted message from anyone on the control network makes MMS communication unreachable for up to 30 seconds, and if it does not recover the controller stops. NVD and ABB score it 7.5. ABB lists no workaround; firmware 6.0.0-4, 6.1.1-2 and 6.2.0-0 correct it.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-22277 · Source: NVD

Affected components

ComponentCPEVersion range
ABB 800xA, Control Software for AC 800M (AC 800M and AC 800M High Integrity controller firmware)cpe:2.3:a:abb:800xa:*:*:*:*:*:*:ac_800m:*AC 800M firmware 5.1 all versions, 6.0.0-0 to 6.0.0-3, 6.1.0-0 to 6.1.1-1 (High Integrity 5.1.1-x, 6.0.0-0 to 6.0.0-3, 6.1.0-1 to 6.1.1-1); correcting revisions 6.0.0-4, 6.1.1-2 and 6.2.0-0 (ABB 7PAA001499 Rev A)
ABB Control Builder Safecpe:2.3:a:abb:control_builder_safe:*:*:*:*:*:*:*:*1.x, 2.0 and 3.0, including High Integrity firmware 5.1.1-1, 5.1.1-2 CC1, 6.0.0-1 and 6.1.1-0; corrected in the next version after 3.0 (ABB 7PAA001499 Rev A)
ABB Compact Product Suite - Control and I/Ocpe:2.3:a:abb:compact_product_suite:*:*:*:*:*:*:*:*AC 800M firmware 5.1 all versions, 6.0.0-0 to 6.0.0-3, 6.1.0-0 to 6.1.1-1; correcting revision 6.2.0-0 (ABB 7PAA001499 Rev A)
ABB Base Software for SoftControl (AC 800M SoftController)cpe:2.3:a:abb:base_software:*:*:*:*:*:softcontrol:*:*5.1 all versions, 6.0.0-0 to 6.0.0-3, 6.1.0-0 to 6.1.1-1 (ABB 7PAA001499 Rev A)

What does this mean for affected devices?

ABB's advisory 7PAA001499, Rev A of 2022-02-17, says the flaw "is caused by lack of input data validation in the MMS protocol stack" of the AC 800M controller firmware. MMS carries messages between controllers and between the engineering station and controllers. NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), with a CVSS v2 7.8; ABB, the CNA, gives the same 7.5 vector. Both list CWE-20. The CVE record was published on 2022-04-01 (NVD, CVE record); ABB's alerts and notifications page dates the advisory 2022-02-25.

Which controllers are affected?

ABB lists AC 800M controller firmware 5.1 (all versions), 6.0.0-0 to 6.0.0-3 and 6.1.0-0 to 6.1.1-1 as shipped with 800xA Control Software for AC 800M, Compact Product Suite - Control and I/O and the AC 800M SoftController in ABB Base Software for SoftControl. AC 800M High Integrity firmware 5.1.1-x, 6.0.0-0 to 6.0.0-3 and 6.1.0-1 to 6.1.1-1 is affected too, as are Control Builder Safe 1.x, 2.0 and 3.0. NVD's CPE configuration treats 6.0.0-4 and 6.1.1-2 as the first unaffected 800xA levels and includes Control Builder Safe up to 3.0.

What does an attack do?

The attacker needs network access to the system network, directly or through a misconfigured firewall, or malware on a system node. ABB answers "Yes" to remote exploitation from that position. A crafted message makes MMS in the controller unreachable for up to 30 seconds; if communication has not recovered by then, the controller stops. ABB says other protocols, application code execution and I/O copy are not affected, and that functional safety is not affected provided a controller stop leads to a safe shutdown.

Fix and mitigation

ABB names AC 800M firmware 6.0.0-4, 6.1.1-2 and 6.2.0-0 as the correcting revisions, and the next Control Builder Safe version after 3.0. Customers on 5.1 or older should move to a supported version that is not affected. "No workaround exists": ABB treats the control network as a trusted zone, so keep it physically protected, off the Internet and behind a firewall with a minimal number of ports. The ABB AC500, RTU500 and Relion guide covers the AC 800M and 800xA advisories, CVE-2021-22284 is the OPC Server for AC 800M flaw, and the IEC 61850 protocol security guide covers MMS exposure in general.

CVE-2021-22277 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00947, the 62.0th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2022-04-01; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H and CVSS v2 7.8; ABB Secondary 7.5; CWE-20; CPE 800xA ac_800m 5.1.0-0 to 5.1.0-3, 5.1.1-0 to 5.1.1-4, 6.0.0-0 up to excluding 6.0.0-4, 6.1.0-0 up to excluding 6.1.1-2; Control Builder Safe up to including 3.0; Compact Product Suite and Base Software for SoftControl ranges. — NVD
  • ABB 7PAA001499 Rev A (2022-02-17), read 2026-11-23: affected products and firmware versions; correcting revisions 6.2.0-0, 6.1.1-2, 6.0.0-4 and next Control Builder Safe after 3.0; CVSS v3.1 7.5; MMS unreachable up to 30 seconds then controller stops; other protocols not affected; remotely exploitable with network access; functional safety not affected if a stop leads to safe shutdown; no workaround; responsible disclosure, no exploitation known at issue. — ABB 7PAA001499
  • ABB cybersecurity alerts and notifications page, read 2026-11-23: lists '2022-02-25: Cyber Security Advisory - SECURITY - AC 800M MMS - Denial of Service vulnerability in MMS communication'. — ABB
  • CVE record (checked 2026-11-23): state PUBLISHED 2022-04-01; CNA ABB; affected product version ranges as in ABB 7PAA001499. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.00947, percentile 0.62036, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. ABB 7PAA001499: AC 800M MMS denial of service vulnerability
  3. ABB: Cyber security alerts and notifications
  4. CVE.org record CVE-2021-22277
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which AC 800M firmware fixes CVE-2021-22277?

ABB 7PAA001499 names firmware 6.0.0-4, 6.1.1-2 and 6.2.0-0 as the correcting revisions, and the next Control Builder Safe version after 3.0. Firmware 5.1 has no fix; ABB recommends moving to a supported, unaffected version.

What happens to the controller during an attack?

MMS communication becomes unreachable for up to 30 seconds. If it has not recovered after that, the controller stops. ABB says other protocols, application code execution and I/O copy keep working while MMS is down.

Is there a workaround for CVE-2021-22277?

No. ABB says no workaround exists and points to network protection: keep the control network physically protected, without direct Internet connections, and separated by a firewall that exposes a minimal number of ports.

Is CVE-2021-22277 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00947 (62.0th percentile) in the 2026-11-22 dataset.