Security Advisory

CVE-2020-7568: Modicon M221 Traffic Info Disclosure

Last updated:
  • CVE-2020-7568

CVE-2020-7568 is an information disclosure flaw (CWE-200) in Schneider Electric Modicon M221 nano PLCs (and the M100 and M200): an attacker who captured traffic between the EcoStruxure Machine Expert - Basic programming software and the controller gets non-sensitive information. NVD scores it 4.3, Schneider 3.1. No firmware fix exists; Schneider lists mitigations.

Vulnerability summary

CVSS base score

4.3

Medium severity

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-7568 · Source: NVD

Affected components

ComponentCPEVersion range
Modicon M221 (all references)cpe:2.3:o:schneider-electric:modicon_m221_firmware:-:*:*:*:*:*:*:*All versions; no fix as of 2026-11-21, mitigations only (Schneider SEVD-2020-315-05, CISA ICSA-20-343-04)
Modicon M200 (all references)—All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list
Modicon M100 (all references)—All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list

What does this mean for affected devices?

NVD carries the Schneider Electric description: "A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller." NVD's Primary score is CVSS v3.1 4.3 (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N), and the weakness is the Schneider CNA's CWE-200 (exposure of sensitive information to an unauthorized actor). The record was published on 2020-11-19 (NVD, CVE record).

How severe is CVE-2020-7568, and why do the scores differ?

Schneider Electric scores CVE-2020-7568 at CVSS v3.0 3.1 (CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N) in SEVD-2020-315-05, and CISA's ICSA-20-343-04 repeats 3.1. The CISA ADP container in the CVE record carries the same vector as CVSS v3.1 3.1, which NVD shows as a Secondary metric. The only difference is attack complexity: NVD rates it low, Schneider and CISA rate it high. All three put the attacker on the adjacent network with a low confidentiality impact and no integrity or availability impact. It is the lowest-scored flaw in the notice. CISA says no known public exploits specifically target these flaws.

What does CVE-2020-7568 expose?

Schneider describes the leak as "non sensitive information disclosure" from captured traffic between EcoStruxure Machine Expert - Basic and the controller; neither Schneider nor CISA says which fields leak. The more serious flaws in the same notice are on that same programming link: CVE-2020-7565 and CVE-2020-7566 (the encryption can be broken), CVE-2020-7567 (the password hash is then exposed) and CVE-2020-28214 (a predictable password salt). Schneider's overview says that without the mitigations, unauthorized users could "replay authentication sequences, which could result in an attacker taking control over the PLC." So the practical risk of CVE-2020-7568 is that an attacker who can capture this traffic is in place for the rest of the chain.

Which controllers are affected?

Product (Schneider wording) Affected Fixed
Modicon M221, all references all versions no fix
Modicon M200, all references all versions no fix
Modicon M100, all references all versions no fix

SEVD-2020-315-05 was first released on 2020-11-10; version 3.0.0 of 2021-01-12 added the M100 and M200. CISA's advisory of 2020-12-08 and NVD's CPE (modicon_m221_firmware, version -) still name only the M221.

How do you mitigate CVE-2020-7568?

There is no firmware fix as of 2026-11-21. Schneider's mitigations are the same for every CVE in the notice: set up network segmentation and a firewall that blocks all unauthorized access to port 502/TCP; within the M100/M200/M221 application, disable all unused protocols, especially the Programming protocol; set a password to protect the project, a password for read access and a different password for write access on the controller. Schneider's general recommendations add that programming software should never be connected to any network other than the one intended for the device. Our Modicon and UMAS security guide covers Schneider controller hardening, and the weak cryptography fix guide explains why the programming link leaks.

CVE-2020-7568 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00523, the 45.3rd percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-21): status Modified; published 2020-11-19; NVD Primary CVSS v3.1 4.3 CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N, v2 3.3; CISA-ADP Secondary 3.1 CVSS:3.1/AV:A/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N; CWE CWE-200 (Schneider); CPE modicon_m221_firmware version "-". — NVD
  • Schneider Electric SEVD-2020-315-05 version 3.0.0 (published 2020-11-10, updated 2021-01-12), CSAF read 2026-11-21: CVE-2020-7568 CWE-200, CVSS v3.0 3.1 CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N; non sensitive information disclosure from captured Machine Expert - Basic traffic to Modicon M100/M200/M221; all versions affected; mitigations only: firewall 502/TCP, disable unused protocols especially Programming protocol, project password, read password, different write password. — Schneider Electric SEVD-2020-315-05
  • CISA ICSA-20-343-04 CSAF (released 2020-12-08), read 2026-11-21: CVE-2020-7568 CWE-200, CVSS v3 3.1, Modicon M221 all versions; no known public exploits specifically target these vulnerabilities. — CISA CSAF ICSA-20-343-04
  • CVE record (checked 2026-11-21): state PUBLISHED, CNA Schneider Electric, published 2020-11-19; CNA CWE-200, no CNA CVSS metric; CISA-ADP CVSS v3.1 3.1 and SSVC (exploitation none, automatable no, technical impact partial). — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
  • EPSS 0.00523, 45.3rd percentile, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2020-315-05: Modicon M100/M200/M221 Programmable Logic Controller (PDF)
  3. Schneider Electric SEVD-2020-315-05 (CSAF)
  4. CISA CSAF: ICSA-20-343-04 Schneider Electric Modicon M221 Programmable Logic Controller (machine-readable advisory)
  5. CVE.org record CVE-2020-7568 (CNA: Schneider Electric)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Is there a firmware update for CVE-2020-7568?

No. Schneider lists all references and all versions of the Modicon M100, M200 and M221 as affected and gives mitigations only (per SEVD-2020-315-05, version 3.0.0).

Why do NVD and Schneider score CVE-2020-7568 differently?

Only attack complexity differs: NVD rates it low (4.3), Schneider and CISA rate it high (3.1). All agree on an adjacent-network attacker, low confidentiality impact and no integrity or availability impact.

Should I prioritise CVE-2020-7568?

On its own it is low severity, but it shares the attack position with CVE-2020-7565 to CVE-2020-7567 and CVE-2020-28214 on the same M221 programming link. Apply the notice's mitigations once and they cover all five.

What should I configure on the M221?

Disable all unused protocols, especially the Programming protocol, set a project password and separate read and write passwords on the controller, and block unauthorized access to port 502/TCP with a firewall (per Schneider SEVD-2020-315-05).