Security Advisory

CVE-2020-7485: TriStation 1131 Support Account

Last updated:
  • CVE-2020-7485

CVE-2020-7485 is a legacy support account in Schneider Electric TriStation 1131, the Triconex safety controller engineering software, that could give improper access to the TriStation host or, per the vendor, its project file. NVD scores it 9.8, CISA 5.5. Versions 1.0 to 4.9.0 and 4.10.0 are affected; 4.9.1 and 4.10.1, released in May 2013, fix it.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-7485 · Source: NVD

Affected components

ComponentCPEVersion range
Schneider Electric TriStation 1131 (Triconex engineering software on Windows NT, XP or 7)cpe:2.3:a:schneider-electric:tristation_1131:*:*:*:*:*:*:*:*1.0 to 4.9.0 and 4.10.0; fixed in 4.9.1 and 4.10.1, released 2013-05-30 (Schneider SESB-2020-105-01 V2.1, CISA ICSA-20-205-01). NVD's CPE also lists 4.12.0

What does this mean for affected devices?

NVD carries Schneider Electric's current CNA description, tagged "VERSION NOT SUPPORTED WHEN ASSIGNED": "A legacy support account in the TriStation software version v4.9.0 and earlier could cause improper access to the TriStation host machine. This was addressed in TriStation version v4.9.1 and v4.10.1 released on May 30, 2013." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), with CVSS v2 7.5, and NVD lists the weakness as NVD-CWE-noinfo. The record was published on 2020-04-16 and is PUBLISHED on CVE.org (NVD, CVE record).

Why is NVD's 9.8 so far from CISA's 5.5?

The two scorers read the account differently. CISA's ICSA-20-205-01 CSAF (23 July 2020) follows the vendor bulletin, which says the legacy support account "could allow inappropriate access to the TriStation 1131 project file", and scores CVSS v3.0 5.5 (CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N): local access, low privileges, integrity impact only, CWE-912 (hidden functionality). NVD scores the CNA text about access to the TriStation host machine as a network attack with no privileges and full impact. Schneider's bulletin gives no score. Either way, the account sits on the engineering workstation that holds the safety controller's TriStation project.

Which TriStation 1131 versions are affected?

Product Affected (SESB-2020-105-01 V2.1, CISA) Fixed
TriStation 1131 on Windows NT, XP or 7 1.0 to 4.9.0, and 4.10.0 4.9.1 and 4.10.1 (30 May 2013)

Schneider's SESB-2020-105-01 (V2.1, 23 June 2020) and the CISA CSAF give this range. NVD's CPE lists 1.0.0 to 4.9.0, 4.10.0, and also 4.12.0 as vulnerable, which the bulletin does not; the CVE.org record lists "v4.0.0 to v4.9.0, v4.10.0". Any workstation on 4.9.1, 4.10.1 or later is outside the vendor's range for this CVE, but versions up to 4.12.0 remain affected by CVE-2020-7483 and CVE-2020-7484, so 4.13.0 or later covers all three.

Where does this fit in the Triconex story?

Schneider says the then-Invensys Triconex team found and fixed these issues before the acquisition, notified customers directly, and issued CVEs in 2020 after an independent researcher reported the same flaws in 2019. The bulletin also covers two Tricon Communication Module flaws, CVE-2020-7486 and CVE-2020-7491. The controller firmware flaws found after the TRITON incident are CVE-2018-8872 and CVE-2018-7522.

How do you fix or mitigate it?

Upgrade TriStation 1131 to at least 4.9.1 or 4.10.1, and to 4.13.0 or later to clear the other two TriStation CVEs; Schneider says fixed versions are on its Process Automation support portal and recommends current Windows versions on the host. Keep the engineering workstation on the safety network only, scan removable media before use, and keep controllers in locked cabinets and out of PROGRAM mode. Our TriStation protocol guide covers the engineering link, the hard-coded credentials fix guide covers removing vendor support accounts, and the IEC 61511 guide covers the SIS security risk assessment.

CVE-2020-7485 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01859, the 79.7th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2020-04-16; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 7.5; CWE NVD-CWE-noinfo; CPE tristation_1131 1.0.0 to 4.9.0, 4.10.0 and 4.12.0 on Windows NT, XP or 7; description tagged VERSION NOT SUPPORTED WHEN ASSIGNED, legacy support account in v4.9.0 and earlier, improper access to the TriStation host machine, addressed in v4.9.1 and v4.10.1 (May 30, 2013). — NVD
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2020-04-15; problem type improper access; affected 'TriStation TS1131 (v4.0.0 to v4.9.0, v4.10.0)'; no CNA CVSS metric. — CVE.org
  • Schneider Electric SESB-2020-105-01 V2.1 (updated 23 June 2020), read 2026-11-20: CVE-2020-7485, legacy support account in TriStation 1131 versions 1.0 through 4.9.0 and 4.10.0 could allow inappropriate access to the TriStation 1131 project file; remediated in 4.9.1 and 4.10.1 (5/30/2013); found by the Invensys Triconex team, re-reported by an independent researcher in 2019. — Schneider Electric SESB-2020-105-01
  • CISA ICSA-20-205-01 CSAF (2020-07-23), read 2026-11-20: CVE-2020-7485 CWE-912 hidden functionality, CVSS v3.0 5.5 CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N; TriStation 1131 1.0 through 4.9.0 and 4.10.0; v4.9.1 and v4.10.1 released May 30, 2013. — CISA CSAF ICSA-20-205-01
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
  • EPSS 0.01859, percentile 0.79678, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD: CVE-2020-7485
  2. CVE.org record CVE-2020-7485 (CNA: Schneider Electric)
  3. Schneider Electric Security Bulletin SESB-2020-105-01: Legacy Triconex Product Vulnerabilities (V2.1, PDF)
  4. CISA ICS Advisory ICSA-20-205-01: Schneider Electric Triconex TriStation and Tricon Communication Module
  5. CISA CSAF record for ICSA-20-205-01
  6. CISA Known Exploited Vulnerabilities catalog
  7. FIRST EPSS score for CVE-2020-7485

Frequently asked questions

Which TriStation 1131 versions fix CVE-2020-7485?

Versions 4.9.1 and 4.10.1, released on 30 May 2013. Affected are 1.0 to 4.9.0 and 4.10.0 (per Schneider SESB-2020-105-01 V2.1 and CISA ICSA-20-205-01). Version 4.13.0 or later also fixes CVE-2020-7483 and CVE-2020-7484.

Why does NVD say 9.8 while CISA says 5.5?

NVD scores the CNA text, improper access to the TriStation host machine, as a network attack with no privileges and full impact. CISA follows the vendor bulletin, access to the TriStation 1131 project file, and scores local access with low privileges and integrity impact only (per NVD and CISA ICSA-20-205-01).

Does NVD's CPE match the vendor range?

Not exactly. As of 2026-11-20 NVD's CPE marks 1.0.0 to 4.9.0, 4.10.0 and also 4.12.0 as vulnerable, while Schneider's bulletin lists 4.12.0 only under CVE-2020-7483 and CVE-2020-7484 (per NVD and Schneider SESB-2020-105-01).

Is CVE-2020-7485 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18). FIRST EPSS gives it 0.01859, the 79.7th percentile, in the 2026-11-19 dataset.