CVE-2018-7522 is a privilege escalation flaw in Schneider Electric Triconex Tricon MP model 3008 firmware 10.0 to 10.4: registers are saved to a fixed memory location on every system call, so code that can overwrite it can gain supervisor-level access and change system states. NVD scores it 6.7 and CISA 7.9. Schneider's remedy is an upgrade to Tricon CX v11.4 or later.
Vulnerability summary
CVSS base score
6.7
Medium severity
EPSS score (FIRST)
0.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-7522 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Triconex Tricon MP model 3008 (main processor) | cpe:2.3:o:schneider-electric:triconex_tricon_mp_3008_firmware:*:*:*:*:*:*:*:* | Firmware 10.0 to 10.4 (CISA ICSA-18-107-02, Schneider SEVD-2017-347-01; NVD's CPE upper bound is the text "10.0-10.4"). Remediation: upgrade to the latest Tricon CX; v11.4 released October 2018 |
What does this mean for affected devices?
NVD carries the ICS-CERT description: "In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states." NVD's Primary score is CVSS v3.0 6.7 (CVSS:3.0/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H), with CVSS v2 7.2. NVD lists the weakness as NVD-CWE-noinfo; the ICS-CERT CNA and CISA class it CWE-119. The record was published on 2018-05-04 and is PUBLISHED on CVE.org (NVD, CVE record).
What does an attacker gain from the fixed register location?
Supervisor-level access on the safety controller's main processor. Each system call stores the registers at the same, predictable address; per the advisory text, an attacker who modifies the data there could gain supervisor-level access and control system states. Writing to that location already requires a foothold on the controller, which is why the attack vector is local and high privileges are required in both scores. MITRE ATT&CK for ICS (Triton, S1009, technique T0890) records that the TRITON malware gained supervisor privileges on Tricon MP3008 firmware 10.0 to 10.4 through a "previously-unknown vulnerability" in a system call; ATT&CK names no CVE ID, and CISA assigned both CVE-2018-7522 and CVE-2018-8872 to that firmware range.
How do the CISA and NVD scores compare?
CISA's ICSA-18-107-02 CSAF file (Update B, 18 December 2018) scores CVE-2018-7522 at CVSS v3.0 7.9 (CVSS:3.0/AV:L/AC:L/PR:H/UI:N/S:C/C:N/I:H/A:H): changed scope, no confidentiality impact. NVD scores the scope unchanged and adds high confidentiality impact, which gives 6.7. Both agree on a local attack that needs high privileges and no user interaction.
Which firmware is affected, and what does Schneider recommend?
| Product | Affected | Remediation |
|---|---|---|
| Triconex Tricon MP model 3008 (main processor) | firmware 10.0 to 10.4 | upgrade to the latest Tricon CX; Tricon CX v11.4 released October 2018 |
Schneider's SEVD-2017-347-01 (V3, 14 December 2018) and the CISA CSAF give the same range and the same remediation. NVD's CPE stores the upper bound of triconex_tricon_mp_3008_firmware as the text "10.0-10.4" instead of a version number, so check MP 3008 firmware against the advisory range rather than relying on automated CPE range matching.
What protects a Tricon that stays on 10.x firmware?
The controls that kept TRITON out apply here too. Schneider says the malware needed unrestricted access to the safety network and the Tricon keyswitch in PROGRAM mode to deploy its payload. Keep the keyswitch out of PROGRAM and alarm on it, keep controllers in locked cabinets, isolate the safety network, and keep the TriStation engineering workstation off every other network. Our TriStation protocol guide and IEC 61511 guide cover those controls, and the memory corruption fix guide covers the firmware design side. On the engineering software, see CVE-2020-7485 and CVE-2020-7484.
CVE-2018-7522 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.00417, the 36.7th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-20): status Modified; published 2018-05-04; NVD Primary CVSS v3.0 6.7 CVSS:3.0/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H, v2 7.2; CWE NVD-CWE-noinfo (NVD), CWE-119 (ICS-CERT); CPE triconex_tricon_mp_3008_firmware from 10.0 with versionEndIncluding "10.0-10.4"; references ICSA-18-107-02 and SEVD-2017-347-01. — NVD
- CVE record (checked 2026-11-20): state PUBLISHED, CNA ICS-CERT (icscert), published 2018-05-04; CWE-119; affected Triconex Tricon MP model 3008 firmware versions 10.0-10.4; no CNA CVSS metric. — CVE.org
- CISA ICSA-18-107-02 CSAF (Update B, current release 2018-12-18), read 2026-11-20: CVE-2018-7522 CWE-119, CVSS v3.0 7.9 CVSS:3.0/AV:L/AC:L/PR:H/UI:N/S:C/C:N/I:H/A:H; registers stored to a fixed memory location on a system call; MP Model 3008 10.0 to 10.4; vendor fix upgrade to the latest Tricon CX, v11.4 available. — CISA CSAF ICSA-18-107-02
- Schneider Electric SEVD-2017-347-01 V3 (14 December 2018), read 2026-11-20: affected Tricon Model MP3008 versions 10.0-10.4; remediation upgrade to Tricon CX v11.4 (released October 2018); the malware requires unrestricted access to the safety network and the keyswitch in PROGRAM mode. — Schneider Electric SEVD-2017-347-01
- MITRE ATT&CK for ICS S1009 Triton, read 2026-11-20: T0890, a previously-unknown vulnerability in Tricon MP3008 firmware 10.0 to 10.4 (insecure system call, arbitrary 2-byte write) used to gain supervisor privileges; no CVE ID named. — MITRE ATT&CK
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
- EPSS 0.00417, percentile 0.36721, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2018-7522
- CVE.org record CVE-2018-7522 (CNA: ICS-CERT)
- CISA ICS Advisory ICSA-18-107-02: Schneider Electric Triconex Tricon (Update B)
- CISA CSAF record for ICSA-18-107-02
- Schneider Electric Security Notification SEVD-2017-347-01: EcoStruxure Triconex Tricon V3 (PDF)
- MITRE ATT&CK for ICS: Software S1009, Triton
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2018-7522
Frequently asked questions
Which firmware does CVE-2018-7522 affect, and what fixes it?
Triconex Tricon MP model 3008 main processor firmware 10.0 to 10.4. Schneider and CISA tell owners to upgrade to the latest Tricon CX; v11.4 was released in October 2018 (per Schneider SEVD-2017-347-01 and CISA ICSA-18-107-02).
Can CVE-2018-7522 be exploited over the network on its own?
No. Both scores use a local attack vector with high privileges: the attacker must already run code on the controller to overwrite the saved registers. Schneider notes that the TRITON malware first needed unrestricted access to the safety network and the keyswitch in PROGRAM mode to deploy its payload (per CISA ICSA-18-107-02 and Schneider SEVD-2017-347-01).
Why do CISA (7.9) and NVD (6.7) disagree?
CISA scores a changed scope with no confidentiality impact; NVD scores an unchanged scope with high confidentiality, integrity and availability impact. Both use a local vector, low complexity, high privileges and no user interaction (per CISA ICSA-18-107-02 and NVD).
Will a CPE-based scanner flag my MP 3008 firmware?
Possibly not reliably. As of 2026-11-20 NVD's CPE stores the upper bound as the text "10.0-10.4" instead of a version number, so compare the installed firmware with the 10.0 to 10.4 range in the advisories directly (per NVD).