CVE-2018-8872 is a memory-safety flaw in the firmware of the Schneider Electric Triconex Tricon MP model 3008 main processor, versions 10.0 to 10.4: system calls read addresses from the control program area without checking them, so manipulated data can be copied anywhere in memory. NVD scores it 8.1 and CISA 9.0. Schneider's remedy is an upgrade to Tricon CX v11.4 or later.
Vulnerability summary
CVSS base score
8.1
High severity
EPSS score (FIRST)
2.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-8872 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Triconex Tricon MP model 3008 (main processor) | cpe:2.3:o:schneider-electric:triconex_tricon_mp_3008_firmware:*:*:*:*:*:*:*:* | Firmware 10.0 to 10.4 (NVD CPE, CISA ICSA-18-107-02, Schneider SEVD-2017-347-01). Remediation: upgrade to the latest Tricon CX; v11.4 released October 2018 |
What does this mean for affected devices?
NVD carries the ICS-CERT description: "In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, system calls read directly from memory addresses within the control program area without any verification. Manipulating this data could allow attacker data to be copied anywhere within memory." NVD's Primary score is CVSS v3.0 8.1 (CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H), with CVSS v2 9.3, and both NVD and the ICS-CERT CNA class it CWE-119 (improper restriction of operations within the bounds of a memory buffer). The record was published on 2018-05-04 and is PUBLISHED on CVE.org (NVD, CVE record).
How is CVE-2018-8872 linked to the TRITON attack?
Schneider Electric's notice SEVD-2017-347-01 (V3, 14 December 2018) covers a "directed incident that affected a single customer's Triconex Tricon safety shutdown system". During that investigation Schneider "identified a vulnerability in the Tricon firmware, which is limited to a small number of older versions", and calls it "a part of a complex malware infection scenario". MITRE ATT&CK for ICS lists, under Triton (S1009) and technique T0890, that the malware "leverages a previously-unknown vulnerability" in Tricon MP3008 firmware 10.0 to 10.4, in which an insecurely written system call gives an arbitrary 2-byte write that is then used to gain supervisor privileges. Neither source names a CVE ID; CISA's ICSA-18-107-02 assigns CVE-2018-8872 and CVE-2018-7522 to the same MP 3008 firmware range. Schneider adds that the malware needed unrestricted access to the safety network and the Tricon keyswitch in PROGRAM mode.
Why do CISA and NVD score it differently?
CISA's ICSA-18-107-02 CSAF file (Update B, 18 December 2018) scores CVE-2018-8872 at CVSS v3.0 9.0 (CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H). NVD uses the same metrics except scope, which it sets to unchanged, and lands on 8.1. Both rate attack complexity high and require no privileges or user interaction. The CWE is CWE-119 in both.
Which Tricon systems are affected, and what fixes it?
| Product | Affected | Remediation |
|---|---|---|
| Triconex Tricon MP model 3008 (main processor) | firmware 10.0 to 10.4 | upgrade to the latest Tricon CX; Tricon CX v11.4 released October 2018 |
The range comes from SEVD-2017-347-01, the CISA CSAF product tree (10.0 to 10.4) and NVD's CPE (triconex_tricon_mp_3008_firmware 10.0 up to and including 10.4). Schneider "strongly recommends users upgrade to the latest Triconex Tricon CX version" and describes v11.4 as compliant with IEC 62443 with enhancements against the HatMan techniques. CISA republished that remediation with a detection offer: Schneider gathers data from each Tricon installation and reports whether the malware is present; since 1 February 2019 that service needs a support contract.
How do you reduce the risk on a Tricon you cannot upgrade?
Schneider and CISA list the same controls. Keep controllers in locked cabinets and never leave the keyswitch in PROGRAM; set operator stations to alarm whenever it is in PROGRAM; deploy the safety system on an isolated network; never connect a TriStation engineering workstation to any other network; and scan removable media before it touches that workstation. Our TriStation protocol guide covers monitoring TriStation traffic from a network tap, the IEC 61511 guide covers the SIS security risk assessment, and the memory corruption fix guide covers unchecked pointer and length handling. The TriStation 1131 software flaws CVE-2020-7483, CVE-2020-7484 and CVE-2020-7485 affect the engineering side of the same systems.
CVE-2018-8872 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.02204, the 82.9th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-20): status Modified; published 2018-05-04; NVD Primary CVSS v3.0 8.1 CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 9.3; CWE-119 (NVD Primary and ICS-CERT); CPE triconex_tricon_mp_3008_firmware 10.0 to 10.4 inclusive; references ICSA-18-107-02 and SEVD-2017-347-01. — NVD
- CVE record (checked 2026-11-20): state PUBLISHED, CNA ICS-CERT (icscert), published 2018-05-04; CWE-119; affected Triconex Tricon MP model 3008 firmware versions 10.0-10.4; no CNA CVSS metric. — CVE.org
- CISA ICSA-18-107-02 CSAF (Update B, version 3, current release 2018-12-18), read 2026-11-20: CVE-2018-8872 CWE-119, CVSS v3.0 9.0 CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H; product MP Model 3008 10.0 to 10.4; vendor fix: upgrade to the latest Tricon CX, v11.4 available; malware detection service needs a support contract from 2019-02-01; HatMan needs safety-network access and keyswitch in PROGRAM. — CISA CSAF ICSA-18-107-02
- Schneider Electric SEVD-2017-347-01 V3 (14 December 2018), read 2026-11-20: directed incident on one customer's Tricon safety shutdown system; vulnerability identified in Tricon firmware limited to a small number of older versions, part of a complex malware infection scenario; affected Tricon Model MP3008 versions 10.0-10.4; remediation upgrade to Tricon CX v11.4 (released October 2018); Security Considerations list (keyswitch, isolated networks, locked cabinets, EWS on safety network only, media scanning, PROGRAM alarm). — Schneider Electric SEVD-2017-347-01
- MITRE ATT&CK for ICS S1009 Triton, read 2026-11-20: T0890 Exploitation for Privilege Escalation, Triton leverages a previously-unknown vulnerability affecting Tricon MP3008 firmware 10.0 to 10.4 (insecure system call, arbitrary 2-byte write, supervisor privileges); no CVE ID named. — MITRE ATT&CK
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
- EPSS 0.02204, percentile 0.82932, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2018-8872
- CVE.org record CVE-2018-8872 (CNA: ICS-CERT)
- CISA ICS Advisory ICSA-18-107-02: Schneider Electric Triconex Tricon (Update B)
- CISA CSAF record for ICSA-18-107-02
- Schneider Electric Security Notification SEVD-2017-347-01: EcoStruxure Triconex Tricon V3 (PDF)
- MITRE ATT&CK for ICS: Software S1009, Triton
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2018-8872
Frequently asked questions
Which Tricon firmware does CVE-2018-8872 affect, and what fixes it?
Tricon MP model 3008 main processor firmware 10.0 to 10.4. Schneider's remedy is an upgrade to the latest Triconex Tricon CX; v11.4 was released in October 2018 (per Schneider SEVD-2017-347-01 and CISA ICSA-18-107-02).
Was CVE-2018-8872 the flaw TRITON exploited?
MITRE ATT&CK says TRITON used a previously unknown system-call flaw in MP3008 firmware 10.0-10.4 to get an arbitrary 2-byte write and supervisor privileges, which matches this CVE's description, but neither ATT&CK nor Schneider's notice names a CVE ID. CISA assigned CVE-2018-8872 and CVE-2018-7522 to that firmware range. Neither is in the CISA KEV catalog as of 2026-11-20.
Why is CISA's score 9.0 when NVD shows 8.1?
CISA scores a changed scope (S:C), NVD an unchanged one (S:U). The other metrics match: network vector, high attack complexity, no privileges, no user interaction and high impact on confidentiality, integrity and availability (per CISA ICSA-18-107-02 and NVD).
What should I do on a Tricon I cannot upgrade?
Keep the keyswitch out of PROGRAM and alarm on it at the operator station, keep controllers in locked cabinets, run the safety network isolated, connect the TriStation workstation to nothing else and scan removable media first. Schneider notes the malware needed safety-network access and PROGRAM mode to deploy (per SEVD-2017-347-01).
Questions about this page?