CVE-2020-7483 is a cleartext exposure in Schneider Electric's TriStation 1131, the engineering software for Triconex safety controllers: when the optional 'password' check is enabled, its data crosses the network in clear text. NVD scores it 7.5 and CISA 5.3. Schneider's bulletin lists versions 1.0 to 4.12.0 as affected and 4.13.0 as the fix.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-7483 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric TriStation 1131 (Triconex engineering software on Windows NT, XP or 7) | cpe:2.3:a:schneider-electric:tristation_1131:*:*:*:*:*:*:*:* | 1.0 to 4.12.0; fixed in 4.13.0, released 2015-01-26 (Schneider SESB-2020-105-01 V2.1, CISA ICSA-20-205-01; NVD CPE 1.0 to 4.12.0 inclusive). The NVD description names v4.9.1 and v4.10.1 as the fix |
What does this mean for affected devices?
NVD carries Schneider Electric's current CNA description, tagged "VERSION NOT SUPPORTED WHEN ASSIGNED": "A vulnerability could cause certain data to be visible on the network when the 'password' feature is enabled." It explains that the 'password' feature "is an additional optional check performed by TS1131 that it is connected to a specific controller" and that the data "is sent as clear text and is visible on the network." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N), with CVSS v2 5.0, and NVD classes it CWE-319 (cleartext transmission of sensitive information). The record was published on 2020-04-16 and is PUBLISHED on CVE.org (NVD, CVE record).
Which TriStation 1131 versions are affected?
The sources disagree, and the vendor bulletin is the most conservative. Schneider's SESB-2020-105-01 (V2.1, 23 June 2020) says the flaw affects TriStation 1131 "versions 1.0 through 4.12.0" and "was remediated in version 4.13.0", released 26 January 2015. V2 and V2.1 of the bulletin updated the affected and fixed versions. CISA's ICSA-20-205-01 CSAF (23 July 2020) uses the same 1.0 to 4.12.0 range. NVD's CPE also runs from 1.0 up to and including 4.12.0. The NVD description, however, says the issue was remediated in v4.9.1 and v4.10.1 on 30 May 2013, and the CVE.org record lists "v4.0.0 to v4.9.0, v4.10.0". Treat any TriStation 1131 workstation below 4.13.0 as affected.
| Product | Affected (SESB-2020-105-01 V2.1, CISA) | Fixed |
|---|---|---|
| TriStation 1131 on Windows NT, XP or 7 | 1.0 to 4.12.0 | 4.13.0 (26 January 2015) |
How severe is it, and why do the scores differ?
NVD rates it 7.5 with high confidentiality impact: the data sent by the password check is readable by anyone on the network path. CISA scores it CVSS v3.0 5.3 (CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:U/C:N/I:H/A:N), with high attack complexity, user interaction and integrity rather than confidentiality impact. Schneider's bulletin gives no score. The flaw only matters when the optional feature is enabled and someone can observe traffic between the TriStation workstation and the controller.
What is the device angle?
TriStation 1131 is the engineering software of Schneider Electric's Triconex safety instrumented system offer, run on the engineering workstation that programs the safety controllers. Schneider says the then-Invensys Triconex team found and fixed this and the other SESB-2020-105-01 issues before the acquisition, and that an independent researcher reported them again in 2019. The same bulletin covers CVE-2020-7484 (denial of service through the same feature), CVE-2020-7485 (legacy support account) and two Tricon Communication Module issues. On the controller firmware side, see CVE-2018-8872 and CVE-2018-7522.
How do you fix or mitigate it?
Upgrade TriStation 1131 to 4.13.0 or later; Schneider says fixed versions are on its Process Automation support portal. Schneider and CISA also list: keep safety networks behind firewalls and isolated from the business network, keep controllers in locked cabinets and out of PROGRAM mode, connect TriStation workstations to no network other than the safety network, and alarm whenever the keyswitch is in PROGRAM. Our TriStation protocol guide covers watching TriStation traffic from a network tap, and the weak cryptography fix guide covers protecting credentials and checks in transit.
CVE-2020-7483 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.00912, the 60.8th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-20): status Modified; published 2020-04-16; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N, v2 5.0; CWE-319 (NVD); CPE tristation_1131 1.0 to 4.12.0 inclusive running on Windows NT, XP or 7; description tagged VERSION NOT SUPPORTED WHEN ASSIGNED and names remediation in v4.9.1 and v4.10.1 on May 30, 2013. — NVD
- CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2020-04-15; problem type cleartext; affected 'TriStation TS1131 (v4.0.0 to v4.9.0, v4.10.0)'; no CNA CVSS metric. — CVE.org
- Schneider Electric SESB-2020-105-01 V2.1 (14 April 2020, updated 23 June 2020), read 2026-11-20: CVE-2020-7483, password feature in TriStation 1131 versions 1.0 through 4.12.0 could cause certain data to be visible on the network; remediated in 4.13.0 (released 1/26/2015); V2 and V2.1 updated affected and fixed versions; issues found by Invensys Triconex team and re-reported by an independent researcher in 2019. — Schneider Electric SESB-2020-105-01
- CISA ICSA-20-205-01 CSAF (2020-07-23), read 2026-11-20: CVE-2020-7483 CWE-319, CVSS v3.0 5.3 CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:U/C:N/I:H/A:N; TriStation 1131 1.0 through 4.12.0; TriStation 4.13.0 released January 26, 2015; mitigations as in the Schneider bulletin. — CISA CSAF ICSA-20-205-01
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
- EPSS 0.00912, percentile 0.60752, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2020-7483
- CVE.org record CVE-2020-7483 (CNA: Schneider Electric)
- Schneider Electric Security Bulletin SESB-2020-105-01: Legacy Triconex Product Vulnerabilities (V2.1, PDF)
- CISA ICS Advisory ICSA-20-205-01: Schneider Electric Triconex TriStation and Tricon Communication Module
- CISA CSAF record for ICSA-20-205-01
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2020-7483
Frequently asked questions
Which TriStation 1131 version fixes CVE-2020-7483?
Version 4.13.0, released on 26 January 2015, according to Schneider's SESB-2020-105-01 V2.1 and CISA ICSA-20-205-01, which list 1.0 to 4.12.0 as affected. The NVD description names v4.9.1 and v4.10.1 instead; use the bulletin's wider range.
Is my workstation exposed if the password feature is off?
The flaw concerns data sent when the optional 'password' feature is enabled, so the exposure is tied to that feature. Upgrading to 4.13.0 still removes the question, and the TriStation workstation should sit only on the isolated safety network (per Schneider SESB-2020-105-01 and NVD).
Why is CISA's score 5.3 when NVD gives 7.5?
NVD scores an easy network attack with high confidentiality impact. CISA scores high attack complexity, required user interaction and high integrity impact with no confidentiality impact. Schneider's bulletin gives no CVSS score (per NVD and CISA ICSA-20-205-01).
Is CVE-2020-7483 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18). FIRST EPSS gives it 0.00912, the 60.8th percentile, in the 2026-11-19 dataset.
Questions about this page?