CVE-2020-24686 is a denial of service in the web server of ABB AC500 V2 PLCs (PM554 to PM573): long URLs or a ping flood stop the web visualization, and a login attempt during the attack makes the PLC refuse Automation Builder. The PLC program keeps running. NVD and ABB score it 7.5. ABB lists no fix and says to disable web visualization.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
2.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-24686 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| ABB AC500 V2 PM554 | cpe:2.3:o:abb:pm554_firmware:-:*:*:*:*:*:*:* | all firmware; no fixed version in ABB 3ADR010645 Rev A (2021-02-02); NVD CPE has no version range |
| ABB AC500 V2 PM556 | cpe:2.3:o:abb:pm556_firmware:-:*:*:*:*:*:*:* | all firmware; no fixed version in ABB 3ADR010645 Rev A (2021-02-02); NVD CPE has no version range |
| ABB AC500 V2 PM564 | cpe:2.3:o:abb:pm564_firmware:-:*:*:*:*:*:*:* | all firmware; no fixed version in ABB 3ADR010645 Rev A (2021-02-02); NVD CPE has no version range |
| ABB AC500 V2 PM566 | cpe:2.3:o:abb:pm566_firmware:-:*:*:*:*:*:*:* | all firmware; no fixed version in ABB 3ADR010645 Rev A (2021-02-02); NVD CPE has no version range |
| ABB AC500 V2 PM572 | cpe:2.3:o:abb:pm572_firmware:-:*:*:*:*:*:*:* | all firmware; no fixed version in ABB 3ADR010645 Rev A (2021-02-02); NVD CPE has no version range |
| ABB AC500 V2 PM573 | cpe:2.3:o:abb:pm573_firmware:-:*:*:*:*:*:*:* | all firmware; no fixed version in ABB 3ADR010645 Rev A (2021-02-02); NVD CPE has no version range |
What does this mean for affected devices?
NVD carries ABB's description: the flaw "can be exploited to cause the web visualization component of the PLC to stop and not respond, leading to genuine users losing remote visibility of the PLC state." NVD's Primary score and ABB's score are both CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), and both list CWE-400, uncontrolled resource consumption. NVD's CPE list names the PM554, PM556, PM564, PM566, PM572 and PM573 firmware without a version range. The record was published on 2021-02-26 (NVD, CVE record).
What breaks, and what keeps running?
ABB's advisory 3ADR010645, Rev A of 2021-02-02, describes two triggers against the Java applet-based web interface, which needs no authentication. Sustained requests with "arbitrarily long URLs" make the server answer 400 Bad Request or stop the Web HMI applet from loading. A sustained ICMP ping flood stops the Web HMI, "requiring the PLC to be restarted for the Web Server to return." If a user tries to log in while the attack runs, "the PLC will show an error state and refuse connections to Automation Builder." ABB states that the PLC application itself keeps running. Richard Thomas and Tom Chothia of the University of Birmingham reported it.
Is there a fixed firmware?
Rev A, the revision ABB's library serves as of 2026-11-23, says "Currently there is no fix available" and that ABB found no workaround. Its instruction is to run the PLC as described in the "Cyber security in AC500 V2 products" chapter of the AC500 V2 manual, and, where secure operation cannot be established and the PLC might be reached from untrusted networks, to disable the web visualization in Automation Builder.
What should operators do?
Turn off the web server on PM554 to PM573 controllers that do not need it, and block web and ICMP traffic to the PLC from outside the control network. The ABB AC500, RTU500 and Relion guide covers the AC500 V2 web server alongside the crafted-packet stop CVE-2020-24685, which halts the PLC itself. A comparable controller crash is CVE-2023-1620 on WAGO devices. The input handling fix guide covers resource exhaustion in embedded web servers.
CVE-2020-24686 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.02607, the 85.8th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2021-02-26; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, ABB Secondary 7.5; CWE-400 (ABB and NVD); CPE abb pm554/pm556/pm564/pm566/pm572/pm573 firmware, version "-". — NVD
- ABB 3ADR010645 Rev A (2021-02-02), read 2026-11-23: affected PM554, PM556, PM564, PM566, PM572, PM573; no fix available; long URLs return 400 or stop the applet, ping flood stops the Web HMI until PLC restart; login during attack gives error state and refuses Automation Builder; PLC application not affected; no workaround; disable web visualization if reachable from untrusted networks; acknowledgment Richard Thomas and Tom Chothia (University of Birmingham). — ABB 3ADR010645
- CVE record (checked 2026-11-23): see body; state PUBLISHED. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.02607, percentile 0.85774, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Does CVE-2020-24686 stop the PLC program?
No. ABB says the execution of the PLC application is not affected. The web visualization stops, and a login attempt during the attack makes the PLC show an error state and refuse Automation Builder connections.
Which AC500 models are affected?
ABB 3ADR010645 lists the AC500 V2 PM554, PM556, PM564, PM566, PM572 and PM573 with onboard Ethernet.
Is there a firmware fix?
ABB 3ADR010645 Rev A (2021-02-02), the revision ABB serves as of 2026-11-23, lists no fix and no workaround. ABB says to disable the web visualization where the PLC might be reached from untrusted networks.
Is CVE-2020-24686 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.02607 (85.8th percentile) in the 2026-11-22 dataset.
Questions about this page?