Security Advisory

CVE-2020-24685: ABB AC500 V2 PLC Stop by Packet

Last updated:
  • CVE-2020-24685

CVE-2020-24685 is a denial of service in ABB AC500 V2 PLCs with onboard Ethernet: one unauthenticated crafted packet over the network stops the PLC, the ERR LED flashes red, and someone has to be at the controller to restart the application. NVD and ABB score it 8.6. ABB fixes it in firmware 2.8.5.

Vulnerability summary

CVSS base score

8.6

High severity

EPSS score (FIRST)

1.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-24685 · Source: NVD

Affected components

ComponentCPEVersion range
ABB AC500 V2 CPUs with onboard Ethernetcpe:2.3:o:abb:ac500_cpu_firmware:*:*:*:*:*:*:*:*firmware 2.8.4 and earlier; fixed in 2.8.5, released first for PM573-ETH and PM583-ETH (ABB 3ADR010667 Rev C; NVD before 2.8.5)

What does this mean for affected devices?

NVD carries ABB's description: "An unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC." NVD's Primary score and ABB's score are both CVSS v3.1 8.6 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H); the changed scope reflects that the process the PLC runs stops with it. ABB, the CNA, lists CWE-789 (memory allocation with excessive size value); NVD lists CWE-770. NVD's CPE marks AC500 CPU firmware before 2.8.5. The record was published on 2021-02-09 (NVD, CVE record).

What happens to the PLC?

ABB's advisory 3ADR010667, Rev C of 2021-01-27, says a single crafted packet stops the PLC. "After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application." No login is needed. ABB answered yes to whether the issue was public when the advisory came out, and said it had no reports of exploitation. Yossi Reuven of SCADAfence reported it.

Which AC500 models get the fix?

ABB lists "All AC500 V2 products with onboard ethernet" as affected. Firmware 2.8.5 fixes the flaw and, at Rev C, was released for the PM573-ETH and PM583-ETH, through Automation Builder 2.4.0 or as an SD card image. For the other PLC types ABB says to update to 2.8.5 once it is available for them. ABB found no workaround and points to the chapter "Cyber security in AC500 V2 products" in the AC500 V2 manual for defense in depth.

How do you limit exposure?

Keep the AC500 V2 off any network that untrusted hosts can reach, since any host that can send the packet can stop the PLC. The ABB AC500, RTU500 and Relion guide lists the other AC500 V2 flaws, including the web visualization stop CVE-2020-24686 from the same period. A comparable controller crash is CVE-2023-1620 in WAGO's CODESYS 2.3 runtime. The input handling fix guide covers the class.

CVE-2020-24685 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01627, the 76.8th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Resource exhaustion. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2021-02-09; NVD Primary CVSS v3.1 8.6 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H, ABB Secondary 8.6; CWE-789 (ABB), CWE-770 (NVD); CPE abb ac500_cpu_firmware before 2.8.5. — NVD
  • ABB 3ADR010667 Rev C (2021-01-27), read 2026-11-23: all AC500 V2 with onboard Ethernet affected; single unauthenticated crafted packet stops the PLC, ERR LED flashing red, physical access needed to restart; fix firmware 2.8.5 released for PM573-ETH and PM583-ETH; no workaround; publicly disclosed yes, exploitation reports no; acknowledgment Yossi Reuven (SCADAfence). — ABB 3ADR010667
  • CVE record (checked 2026-11-23): see body; state PUBLISHED. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.01627, percentile 0.76804, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. ABB 3ADR010667: AC500 V2 unauthenticated crafted packet vulnerability
  3. CVE.org record CVE-2020-24685
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which AC500 firmware fixes CVE-2020-24685?

Firmware 2.8.5. In ABB 3ADR010667 Rev C (2021-01-27) it was released for the PM573-ETH and PM583-ETH, via Automation Builder 2.4.0 or as an SD card image; ABB says to update the other AC500 V2 types to 2.8.5 once it is available for them.

Does the PLC restart by itself after the attack?

No. ABB says the PLC stops with the ERR LED flashing red and that physical access to the PLC is required to restart the application.

Does the attacker need a password?

No. ABB and NVD describe an unauthenticated crafted packet sent over the network; both scores use PR:N.

Is CVE-2020-24685 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.01627 (76.8th percentile) in the 2026-11-22 dataset.