CVE-2023-1620 is a denial of service in the CODESYS V2 runtime on WAGO PFC200 controllers and 750-8xx Ethernet Controllers. An attacker who is logged in with high privileges can send a crafted packet that crashes the device until a full restart. NVD scores it 4.9. WAGO fixes it in FW22 Patch 2 for the PFC200 and FW11 or FW17 for the Ethernet Controllers.
Vulnerability summary
CVSS base score
4.9
Medium severity
EPSS score (FIRST)
0.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-1620 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| WAGO PFC200 750-8202/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8202_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8203/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8203_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8204/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8204_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8206/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8206_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8207/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8207_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8208/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8208_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8210/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8210_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8211/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8211_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8212/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8212_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8213/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8213_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8214/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8214_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8216/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8216_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO PFC200 750-8217/xxx-xxx (CODESYS 2.3 runtime) | cpe:2.3:o:wago:750-8217_firmware:*:*:*:*:*:*:*:* | up to and including FW22 Patch 1; fixed in FW22 Patch 2 (CERT@VDE VDE-2023-006, NVD before FW22 and FW22) |
| WAGO Ethernet Controller 4th Generation 750-823 | cpe:2.3:o:wago:750-823_firmware:*:*:*:*:*:*:*:* | up to and including FW10; fixed in FW11 (CERT@VDE VDE-2023-006, NVD before fw11) |
| WAGO Ethernet Controller 4th Generation 750-832 | cpe:2.3:o:wago:750-832_firmware:*:*:*:*:*:*:*:* | up to and including FW06; fixed in FW11 (CERT@VDE VDE-2023-006, NVD before fw11) |
| WAGO Ethernet Controller 4th Generation 750-862 | cpe:2.3:o:wago:750-862_firmware:*:*:*:*:*:*:*:* | up to and including FW10; fixed in FW11 (CERT@VDE VDE-2023-006, NVD before fw11) |
| WAGO Ethernet Controller 4th Generation 750-890 | cpe:2.3:o:wago:750-890_firmware:*:*:*:*:*:*:*:* | up to and including FW10; fixed in FW11 (CERT@VDE VDE-2023-006, NVD before fw11) |
| WAGO Ethernet Controller 4th Generation 750-891 | cpe:2.3:o:wago:750-891_firmware:*:*:*:*:*:*:*:* | up to and including FW10; fixed in FW11 (CERT@VDE VDE-2023-006, NVD before fw11) |
| WAGO Ethernet Controller 4th Generation 750-893 | cpe:2.3:o:wago:750-893_firmware:*:*:*:*:*:*:*:* | up to and including FW10; fixed in FW11 (CERT@VDE VDE-2023-006, NVD before fw11) |
| WAGO Ethernet Controller 4th Generation 750-332 | — | up to and including FW06; fixed in FW11 (CERT@VDE VDE-2023-006; no NVD CPE) |
| WAGO Ethernet Controller 3rd Generation 750-331 | cpe:2.3:o:wago:750-331_firmware:*:*:*:*:*:*:*:* | up to and including FW14; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-829 | cpe:2.3:o:wago:750-829_firmware:*:*:*:*:*:*:*:* | up to and including FW14; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-831 | cpe:2.3:o:wago:750-831_firmware:*:*:*:*:*:*:*:* | up to and including FW14; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-852 | cpe:2.3:o:wago:750-852_firmware:*:*:*:*:*:*:*:* | up to and including FW16; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-880 | cpe:2.3:o:wago:750-880_firmware:*:*:*:*:*:*:*:* | up to and including FW16; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-881 | cpe:2.3:o:wago:750-881_firmware:*:*:*:*:*:*:*:* | up to and including FW16; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-882 | cpe:2.3:o:wago:750-882_firmware:*:*:*:*:*:*:*:* | up to and including FW16; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-885 | cpe:2.3:o:wago:750-885_firmware:*:*:*:*:*:*:*:* | up to and including FW16; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
| WAGO Ethernet Controller 3rd Generation 750-889 | cpe:2.3:o:wago:750-889_firmware:*:*:*:*:*:*:*:* | up to and including FW16; fixed in FW17 (CERT@VDE VDE-2023-006, NVD before fw17) |
What does this mean for affected devices?
NVD carries the CERT@VDE description: "Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a specifically crafted packet to the CODESYS V2 runtime." NVD's Primary score and the CERT@VDE score are both CVSS v3.1 4.9 (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H); the CWE is CWE-1288, improper validation of consistency within input, from CERT@VDE. The record was published on 2023-06-26 (NVD, CVE record).
What happens to the controller?
WAGO's VDE-2023-006, released on 2023-06-25 and updated on 2024-07-08 with new release dates for the fixes (CSAF), says a malformed packet triggers "a device crash via the CODESYS V2 runtime commands parsing". The impact "fully prevents the product to work as intended" until "a complete restart". The same advisory covers its twin, CVE-2023-1619, with the same score. Abdelrahman Hassanien and Daniel dos Santos of Forescout reported both.
Which devices and firmware are affected?
| Family | Affected | Fixed |
|---|---|---|
| PFC200, 750-8202 to 750-8217 | up to FW22 Patch 1 | FW22 Patch 2 |
| Ethernet Controller 4th generation: 750-823, 750-862, 750-890, 750-891, 750-893 | up to FW10 | FW11 |
| Ethernet Controller 4th generation: 750-332, 750-832 | up to FW06 | FW11 |
| Ethernet Controller 3rd generation: 750-331, 750-829, 750-831 | up to FW14 | FW17 |
| Ethernet Controller 3rd generation: 750-852, 750-880, 750-881, 750-882, 750-885, 750-889 | up to FW16 | FW17 |
For most 3rd generation models, WAGO's table marks FW17 as released "after BACnet certification"; only the 750-852 is shown as "already available". NVD's CPE list matches these limits but has no row for the 750-332.
What should operators do?
Install the fixed firmware. Where the CODESYS 2.3 runtime runs but is not needed, WAGO says to switch off its programming port in the web-based management under "Configuration > PLC Runtime Services > CODESYS 2 > communication enabled", and to keep the device away from untrusted networks and the internet. Since the attack needs a high-privilege login, strong and unique runtime passwords also limit it. The same port 2455 runtime carries the unauthenticated stack overflow CVE-2021-30188 and the older CVE-2018-5459, which matter more on unpatched devices. See the WAGO PFC controller guide and the input handling fix guide.
CVE-2023-1620 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.0085, the 59.1st percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2023-06-26; NVD Primary CVSS v3.1 4.9 CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H, CERT@VDE Secondary 4.9; CWE-1288 (CERT@VDE); CPE WAGO 750-8202..8217 firmware before fw22 and fw22, 4th gen before fw11, 3rd gen before fw17, no 750-332 row. — NVD
- CERT@VDE VDE-2023-006 (released 2023-06-25, updated 2024-07-08), HTML and CSAF read 2026-11-23: authenticated attacker crashes device via CODESYS V2 runtime command parsing; complete restart restores it; affected PFC200 <=FW22 SP1, 4th gen <=FW10 (750-332, 750-832 <=FW6), 3rd gen <=FW14/FW16; fixed FW22 Patch 2, FW11, FW17 (after BACnet certification except 750-852); mitigation: disable CODESYS 2 communication in WBM; acknowledgment Forescout (Abdelrahman Hassanien, Daniel dos Santos). — CERT@VDE VDE-2023-006
- CVE record (checked 2026-11-23): state PUBLISHED, CNA CERTVDE, published 2023-06-26, CNA CVSS v3.1 4.9. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.0085, percentile 0.59076, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which WAGO firmware fixes CVE-2023-1620?
FW22 Patch 2 for PFC200 750-8202 to 750-8217, FW11 for the 4th generation Ethernet Controllers and FW17 for the 3rd generation Ethernet Controllers (CERT@VDE VDE-2023-006).
Does the controller recover on its own?
No. WAGO says the crash fully prevents the product from working as intended and that the component works again only after a complete restart.
How do I switch off the CODESYS 2.3 runtime port?
In the web-based management, under Configuration > PLC Runtime Services > CODESYS 2 > communication enabled. WAGO recommends this when the runtime runs but is not needed.
Is CVE-2023-1620 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.0085 (59.1st percentile) in the 2026-11-22 dataset.