Security Advisory

CVE-2019-18247: ABB Relion 650/670 Reboot

Last updated:
  • CVE-2019-18247

CVE-2019-18247 is a denial of service in ABB Relion 650 and 670 series protection relays: a specially crafted message from the network forces the relay to reboot. NVD scores it 7.5, CISA 5.3. ABB fixed it in Relion 650 1.3.0.6 and Relion 670 1.2.3.19, 2.0.0.12 and 2.1.0.2; CISA advises blocking TCP port 7001.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-18247 · Source: NVD

Affected components

ComponentCPEVersion range
ABB Relion 650 seriescpe:2.3:o:hitachienergy:relion_650_firmware:*:*:*:*:*:*:*:*1.3.0.5 and earlier; fixed in 1.3.0.6 (CISA ICSA-19-330-02; NVD up to and including 1.3.0.5)
ABB Relion 670 seriescpe:2.3:o:hitachienergy:relion_670_firmware:*:*:*:*:*:*:*:*1.2.3.18 and earlier (fix 1.2.3.19); 2.0.0.11 and earlier (fix 2.0.0.12); 2.1.0.1 and earlier (fix 2.1.0.2) (CISA ICSA-19-330-02; NVD up to and including the same builds)

What does this mean for affected devices?

NVD carries CISA's description: "An attacker may use a specially crafted message to force Relion 650 series (versions 1.3.0.5 and prior) or Relion 670 series (versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior) to reboot, which could cause a denial of service." NVD's Primary score is CVSS v3.1 7.5 with high availability impact (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). CISA's ICSA-19-330-02 gives CVSS v3.0 5.3 with low availability impact (A:L). Both list CWE-20. The CNA is CISA ICS (icscert), and the record was published on 2019-11-27 (NVD, CVE record).

Which firmware fixes it?

CISA's advisory, released on 2019-11-26 and titled ABB Relion 650 and 670 Series (CSAF), lists:

  • Relion 650 series 1.3.0.5 and earlier: update to 1.3.0.6.
  • Relion 670 series 1.2.3.18 and earlier: update to 1.2.3.19.
  • Relion 670 series 2.0.0.11 and earlier: update to 2.0.0.12.
  • Relion 670 series 2.1.0.1 and earlier: update to 2.1.0.2.

CISA gave an ABB support email address for ordering the updates. NVD's CPE uses the same last affected builds as upper bounds, filed under hitachienergy, which now handles the Relion 650 and 670 lines.

What if the relay cannot be updated?

CISA quotes ABB: "ABB has not identified any workaround; however, firewall rules could be set to block incoming traffic to Port 7001/TCP that originate from outside the network." The same advisory adds that on Relion 650 version 1.3 the SPA protocol over TCP/IP "could be disabled if it is not in use." CISA lists the sectors as Critical Manufacturing and Energy, deployed worldwide, and noted no known public exploits.

The ABB AC500, RTU500 and Relion guide lists this flaw with the path traversal CVE-2019-18253 published the same day, and CVE-2018-20720, an SPA reboot command on Relion 630. The IEC 61850 security guide covers relay network segmentation, and the input handling fix guide covers the class.

CVE-2019-18247 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01551, the 75.7th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2019-11-27; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-20 (icscert and NVD); CPE relion_650_firmware up to and including 1.3.0.5, relion_670_firmware up to and including 1.2.3.18, 2.0.0 to 2.0.0.11, 2.1.0 to 2.1.0.1. — NVD
  • CISA ICSA-19-330-02 CSAF (released 2019-11-26), read 2026-11-23: ABB Relion 650 and 670 Series; CWE-20; CVSS v3.0 5.3 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L; fixes 650 1.3.0.6, 670 1.2.3.19, 2.0.0.12, 2.1.0.2; no workaround, block 7001/TCP from outside; SPA over TCP/IP can be disabled on 650 1.3; ABB advisory 1MRG027165. — CISA ICSA-19-330-02
  • CVE record (checked 2026-11-23): see body; state PUBLISHED. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.01551, percentile 0.75743, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-19-330-02: ABB Relion 650 and 670 Series
  3. CISA ICSA-19-330-02 CSAF (machine-readable advisory)
  4. CVE.org record CVE-2019-18247
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2019-18247?

Relion 650 1.3.0.6 and Relion 670 1.2.3.19, 2.0.0.12 and 2.1.0.2, per CISA ICSA-19-330-02.

Which port should be blocked?

CISA, quoting ABB, says firewall rules could block incoming traffic to TCP port 7001 from outside the network. On Relion 650 version 1.3, SPA over TCP/IP can also be disabled when it is not used.

Why do NVD and CISA scores differ?

NVD scores high availability impact (7.5); CISA scores low availability impact (5.3). The vectors are otherwise the same: network, low complexity, no privileges, no user interaction.

Is CVE-2019-18247 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.01551 (75.7th percentile) in the 2026-11-22 dataset.