CVE-2019-18243 is a permissions flaw in GE Digital HMI/SCADA iFIX 6.1 and earlier: a local authenticated user can modify systemwide iFIX configuration through the Windows registry, which may allow privilege escalation. NVD scores it CVSS 5.5 and CISA 6.1. GE Digital recommends upgrading to iFIX 6.5 and following the iFIX Secure Deployment Guide.
Vulnerability summary
CVSS base score
5.5
Medium severity
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-18243 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| GE Digital HMI/SCADA iFIX | cpe:2.3:a:ge:ifix:*:*:*:*:*:*:*:* | iFIX 6.1 and earlier (CISA ICSA-21-040-01; NVD CPE up to and including 6.1); fix: iFIX 6.5 and the iFIX Secure Deployment Guide |
What does this mean for affected devices?
NVD's description says HMI/SCADA iFIX 6.1 and prior "allows a local authenticated user to modify system-wide iFIX configurations through the registry. This may allow privilege escalation." NVD's Primary analysis scores it 5.5 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N) and CVSS v2 2.1, maps it to CWE-732 and covers iFIX up to and including 6.1 (NVD). CISA's advisory scores it 6.1 (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:N), adding a low confidentiality impact; the CVE record from CISA's ICS team lists CWE-732 and "Versions 6.1 and prior" without a CNA score.
Which iFIX versions are affected?
CISA advisory ICSA-21-040-01 (CSAF), released on 2021-02-09, lists HMI/SCADA iFIX 6.1 and prior and pairs this flaw with CVE-2019-18255, the same configuration change through section objects, also scored 6.1 by CISA. William Knowles of Applied Risk reported the flaws to CISA, and Sharon Brizinov of Claroty reported them separately to GE. CISA names multiple sectors, worldwide deployment and a US headquarters; the flaws are not exploitable remotely and had no known public exploits.
How do I fix CVE-2019-18243?
GE Digital recommends upgrading all instances to iFIX 6.5, which it says contains security enhancements that mitigate the risk, and following the iFIX Secure Deployment Guide. Details are in GE's security advisory GED-21-01 behind a GE support login. Practical steps:
- upgrade iFIX nodes to 6.5 or a later supported release;
- review registry and file permissions on iFIX nodes against the Secure Deployment Guide;
- keep interactive logins on SCADA nodes to the operators and administrators who need them.
A later iFIX flaw is the web server code injection CVE-2023-0598, and the CIMPLICITY privilege flaw CVE-2020-6992 shows the same local escalation pattern in GE's other HMI. The GE Proficy, CIMPLICITY and Historian guide covers every iFIX advisory, and the small manufacturers OT/ICS guide covers account and permission hygiene on HMI nodes.
Is CVE-2019-18243 exploited?
CVE-2019-18243 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.00214, the 6.65 percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2021-02-18; NVD Primary CVSS v3.1 5.5 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N; NVD Primary CVSS v2 2.1; CWE-732; CPE ge ifix up to and including 6.1. — NVD
- CISA ICSA-21-040-01 CSAF (released 2021-02-09, read 2026-11-28): HMI/SCADA iFIX 6.1 and prior; CVE-2019-18243 and CVE-2019-18255 CWE-732, CVSS v3 6.1 CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:N; fix: upgrade to iFIX 6.5, iFIX Secure Deployment Guide, GE advisory GED-21-01; reported by William Knowles, Applied Risk, and separately Sharon Brizinov, Claroty; not exploitable remotely; no known public exploits. — CISA ICSA-21-040-01
- CVE record (read 2026-11-28): state PUBLISHED, assigner icscert, published 2021-02-18; product HMI/SCADA iFIX versions 6.1 and prior; CWE-732; no CNA CVSS metric. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.00214, percentile 0.06646, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which iFIX version fixes CVE-2019-18243?
GE Digital recommends iFIX 6.5 together with the iFIX Secure Deployment Guide, per CISA ICSA-21-040-01.
Can CVE-2019-18243 be exploited remotely?
No. CISA says the flaws are not exploitable remotely; the attacker needs an authenticated local session on the iFIX node.
What is the difference from CVE-2019-18255?
Both let a local user change systemwide iFIX configuration in iFIX 6.1 and earlier. CVE-2019-18243 works through the registry, CVE-2019-18255 through section objects.
Is CVE-2019-18243 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.00214 (6.65 percentile) in the 2026-11-27 dataset.
Questions about this page?