CVE-2019-18261 is a missing limit on failed FTP logins in Omron CS, CJ and NJ series PLC CPU units, so an attacker who can reach the PLC's FTP service can brute-force its password. NVD scores it 9.8, CISA and Omron 6.5. Every version is affected and there is no firmware fix: block FTP port 21 and use strong passwords.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-18261 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Omron CS series CPU units | cpe:2.3:o:omron:plc_cs_firmware:*:*:*:*:*:*:*:* | All versions (NVD, CISA ICSA-19-346-03, Omron advisory); no fixed firmware, mitigations only |
| Omron CJ series CPU units | cpe:2.3:o:omron:plc_cj_firmware:*:*:*:*:*:*:*:* | All versions (NVD, CISA, Omron); no fixed firmware, mitigations only |
| Omron NJ series CPU units | cpe:2.3:o:omron:plc_nj_firmware:*:*:*:*:*:*:*:* | All versions (NVD, CISA, Omron); no fixed firmware, mitigations only |
| Omron NX series CPU units | — | All versions per Omron's advisory (revised 2023-01-10); not in the NVD CPE list or the CISA advisory |
What does this mean for affected devices?
CVE-2019-18261 is an improper restriction of excessive authentication attempts (CWE-307) in the FTP function of Omron programmable controllers. The CVE record, published by CISA on 2019-12-16, says that in the CS, CJ and NJ series, all versions, "the software does not implement sufficient measures to prevent multiple failed authentication attempts within in a short time frame, making it more susceptible to brute force attacks" (NVD, CVE record). NVD's Primary score is 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CWE-307. CISA's advisory and Omron both rate it much lower: 6.5, CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N, with low confidentiality and integrity impact and no availability impact. The CVE record itself carries no CNA score.
Which Omron PLCs are affected?
CISA's advisory ICSA-19-346-03, released on 2019-12-12, lists all versions of the CS, CJ and NJ series and says a successful attack could let an attacker brute-force login credentials and gain unauthorised access to the FTP interface. The sector is Critical Manufacturing, deployed worldwide; the researcher n0b0dy reported the flaw to CISA. Omron's own notice, Vulnerabilities in Omron PLCs (released 2019-12-06, last modified 2023-01-10), names all versions of the CS, CJ, NJ and NX series CPU units for this FTP issue. NVD's CPE list covers only CS, CJ and NJ firmware. The same Omron notice covers three FINS protocol flaws published in a separate CISA advisory: CVE-2019-13533 (capture-replay), CVE-2019-18259 (spoofing) and CVE-2019-18269 (the UM password lock).
How do you fix CVE-2019-18261?
There is no firmware update. CISA and Omron list mitigations only: protect the PLC with a firewall and block unneeded remote access to the FTP port (21 by default), filter devices that may connect to the PLC by IP address, and use strong passwords. Omron's notice also recommends VPN-restricted network access and using the PLC's own packet filtering or disabling unused protocols. If FTP is not needed in operation, turning it off removes the attack surface; if it is, a long, random password makes brute force much slower. The Omron FINS protocol guide explains how these controllers are exposed on plant networks, and the authentication bypass fix guide covers login rate limiting for device makers.
Is CVE-2019-18261 exploited?
CVE-2019-18261 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). CISA noted at release that no known public exploits specifically target it. FIRST EPSS gives it 0.01307, the 70.65th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified, published 2019-12-16; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 5.0; CWE-307 (NVD and ICS-CERT); CPEs omron plc_cs_firmware, plc_cj_firmware, plc_nj_firmware, no version. — NVD
- CISA ICSA-19-346-03 (2019-12-12): CS, CJ, NJ series all versions; CWE-307; CVSS v3 6.5 AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N; mitigations: filter FTP port 21, filter IP addresses, strong passwords; reported by n0b0dy; no known public exploits. — CISA CSAF
- Omron 'Vulnerabilities in Omron PLCs' (released 2019-12-06, last modified 2023-01-10): CVE-2019-18261 FTP brute force, CVSS 6.5, affects CS, CJ, NJ and NX CPU units; countermeasures include firewall, VPN, filtering FTP port 21, packet filtering, disabling unused protocols; also covers CVE-2019-18259, CVE-2019-13533, CVE-2019-18269. — Omron
- CVE record (CNA ICS-CERT): published 2019-12-16; CWE-307; no CNA CVSS metric. — CVE.org
- CISA KEV catalog 2026.11.25 (1,805 entries): CVE-2019-18261 not listed, checked 2026-11-27. — CISA KEV
- EPSS 0.01307, percentile 0.70648, dataset 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Omron controllers are affected by CVE-2019-18261?
All versions of the CS, CJ and NJ series CPU units (CISA ICSA-19-346-03, NVD). Omron's revised notice also lists all versions of the NX series CPU units.
Is there a firmware fix for CVE-2019-18261?
No. Omron and CISA give mitigations only: firewall the PLC, block remote access to FTP port 21, filter connecting devices by IP address and use strong passwords. Omron also recommends VPN access and disabling unused protocols.
Why does NVD score CVE-2019-18261 9.8 when CISA gives 6.5?
NVD assumes full loss of confidentiality, integrity and availability after a successful brute force. CISA and Omron score low confidentiality and integrity impact and no availability impact, which gives 6.5.
Is CVE-2019-18261 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01307, the 70.65th percentile, in the 2026-11-26 dataset.
Questions about this page?