Security Advisory

CVE-2022-33971: Omron NJ/NX Active Debug Code

Last updated:
  • CVE-2022-33971

CVE-2022-33971 is an unintended entry point in Omron NJ and NX machine automation controllers, NJ and NX1 at 1.48 and earlier and NX7 at 1.28 and earlier, reachable by an attacker who can analyze the communication between the controller and software OMRON uses internally; it allows denial of service or running a malicious program. NVD scores it 7.5 (adjacent network), CISA and JPCERT/CC 8.3. Fixes are NX7 1.29, NX1 1.50 and NJ 1.49 or 1.50.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-33971 · Source: NVD

Affected components

ComponentCPEVersion range
Omron NX7-series Machine Automation Controller (all models, e.g. NX701)cpe:2.3:o:omron:nx701-1600_firmware:*:*:*:*:*:*:*:*1.28 and earlier; fixed in 1.29 or later (NVD, CISA, JVN)
Omron NX1-series Machine Automation Controller (all models, e.g. NX102, NX1P2, NX1W)cpe:2.3:o:omron:nx102-1200_firmware:*:*:*:*:*:*:*:*1.48 and earlier; fixed in 1.50 or later (NVD, CISA, JVN)
Omron NJ-series Machine Automation Controller (all models, e.g. NJ501, NJ301, NJ101)cpe:2.3:o:omron:nj501-1300_firmware:*:*:*:*:*:*:*:*1.48 and earlier; fixed in 1.49 or later for NJ501-1300/-1400/-1500 and 1.50 or later for all other NJ models (CISA)

What does this mean for affected devices?

NVD's description: "Authentication bypass by capture-replay vulnerability exists in Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, and Machine automation controller NJ series all models V 1.48 and earlier, which may allow an adjacent attacker who can analyze the communication between the controller and the specific software used by OMRON internally to cause a denial-of-service (DoS) condition or execute a malicious program." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-294. A CISA-ADP secondary submission scores it 8.3 (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H) with CWE-489 (Active Debug Code). NVD's CPE configuration lists 52 controller firmware entries; Sysmac Studio and the NA terminals are not in it (NVD).

How do the sources classify it?

JPCERT/CC's JVNVU#97050784, updated on 2022-11-08, lists it as Active Debug Code (CWE-489) with the 8.3 vector, and its impact line speaks of "an adjacent attacker" who analyzes the communication between the controller and "the specific software used by OMRON internally". CISA's ICSA-22-314-07, released on 2022-11-10, also uses CWE-489 and 8.3, says an attacker who performs capture-replay can find unintended entry points into the product, notes that the flaw has high attack complexity, and credits Reid Wightman of Dragos (CISA CSAF). NVD's CWE matches the original CVE description, while JVN's revised description and CISA use CWE-489; the affected products and fixes are the same in all three sources.

Which versions fix it?

CISA lists NX7 series 1.29 or later, NX1 series 1.50 or later, NJ501-1300, NJ501-1400 and NJ501-1500 1.49 or later, and all other NJ models 1.50 or later, available through OMRON sales offices or distributors, and points to OMRON advisory OMSR-2022-002. The same controller versions also fix CVE-2022-33208 and CVE-2022-34151, so one firmware update closes all three. Older Omron FINS spoofing, such as CVE-2019-18259, has no firmware fix and needs the network controls in our OMRON FINS protocol security guide.

Until the update, CISA recommends firewalls that close unused ports and separate the controllers from the IT network, VPN and multifactor authentication for remote access, and backups. CVE-2022-33971 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01271, the 70th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD description as quoted; NVD Primary CVSS v3.1 7.5 AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H, CWE-294; CISA-ADP 8.3 AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H, CWE-489; 52 vulnerable controller CPE entries; published 2022-07-04. — NVD
  • JVNVU#97050784 (updated 2022-11-08): CVE-2022-33971 Active Debug Code (CWE-489), CVSS 8.3; an adjacent attacker who can analyze the communication between the controller and the specific software used by OMRON internally may cause DoS or execute a malicious program. — JPCERT/CC JVN
  • ICSA-22-314-07 (2022-11-10): CWE-489, CVSS v3 8.3; capture-replay can find unintended entry points; high attack complexity; NX7 <=1.28, NX1 <=1.48, NJ <=1.48; fixes NX7 1.29, NX1 1.50, NJ501-1300/1400/1500 1.49, other NJ 1.50; OMRON OMSR-2022-002; reported by Reid Wightman (Dragos). — CISA ICSA-22-314-07 (CSAF)
  • Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18. — CISA KEV
  • EPSS 0.01271, percentile 0.70329, dataset 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-22-314-07: Omron NJ/NX-series Machine Automation Controllers
  3. CISA CSAF: ICSA-22-314-07 (machine-readable advisory)
  4. JPCERT/CC JVNVU#97050784: Multiple vulnerabilities in OMRON products
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which versions fix CVE-2022-33971?

NX7 1.29 or later, NX1 1.50 or later, NJ501-1300/-1400/-1500 1.49 or later and all other NJ models 1.50 or later (per CISA ICSA-22-314-07).

Is CVE-2022-33971 capture-replay or active debug code?

NVD's description and Primary CWE say capture-replay (CWE-294); JPCERT/CC and CISA classify it as active debug code (CWE-489) reached by analyzing traffic with OMRON's internal software. The affected versions and fixes are the same (per NVD, JVN and CISA).

Does CVE-2022-33971 affect Sysmac Studio?

No. CISA ICSA-22-314-07 and NVD's CPE data list only the NJ, NX1 and NX7 controllers; Sysmac Studio and NA terminals appear in the related CVE-2022-33208 and CVE-2022-34151 (per CISA and NVD).

Is CVE-2022-33971 in the CISA KEV catalog?

No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01271, the 70th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).