Security Advisory

CVE-2022-33208: Omron NJ/NX Capture-Replay Bypass

Last updated:
  • CVE-2022-33208

CVE-2022-33208 is an authentication bypass by capture-replay (CWE-294) in Omron NJ and NX machine automation controllers and the tools that talk to them: an attacker who captures and analyzes traffic between a controller and Sysmac Studio or an NA5 terminal can reuse it to log in and operate the controller. NVD scores it 8.1, CISA and JPCERT/CC 7.5. Fixes ship as NJ/NX1 1.50, NX7 1.29 and Sysmac Studio 1.50.

Vulnerability summary

CVSS base score

8.1

High severity

EPSS score (FIRST)

1.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-33208 · Source: NVD

Affected components

ComponentCPEVersion range
Omron NX7-series Machine Automation Controller (all models, e.g. NX701)cpe:2.3:o:omron:nx701-1600_firmware:*:*:*:*:*:*:*:*1.28 and earlier; fixed in 1.29 or later (NVD, CISA, JVN)
Omron NX1-series Machine Automation Controller (all models, e.g. NX102, NX1P2, NX1W)cpe:2.3:o:omron:nx102-1200_firmware:*:*:*:*:*:*:*:*1.48 and earlier; fixed in 1.50 or later (NVD, CISA, JVN)
Omron NJ-series Machine Automation Controller (all models, e.g. NJ501, NJ301, NJ101)cpe:2.3:o:omron:nj501-1300_firmware:*:*:*:*:*:*:*:*1.48 and earlier; fixed in 1.49 or later for NJ501-1300/-1400/-1500 and 1.50 or later for all other NJ models (CISA)
Omron Sysmac Studio automation softwarecpe:2.3:a:omron:sysmac_studio:*:*:*:*:*:*:*:*1.49 and earlier; fixed in 1.50 or later via Omron Automation Software AutoUpdate (CISA)
Omron NA-series Programmable Terminal NA5-15W, NA5-12W, NA5-9W, NA5-7Wcpe:2.3:o:omron:na5-15w_firmware:*:*:*:*:*:*:*:*Runtime 1.15 and earlier; fixed in runtime 1.16 or later (CISA)

What does this mean for affected devices?

NVD's description: "Authentication bypass by capture-replay vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who can analyze the communication between the affected controller and automation software 'Sysmac Studio' and/or a Programmable Terminal (PT) to access the controller." NVD's Primary score is CVSS v3.1 8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-294 (Authentication Bypass by Capture-replay). JPCERT/CC, the CNA, scores it 7.5 (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H) in JVNVU#97050784, which adds the user-interaction requirement that NVD's vector leaves out. NVD's CPE configuration lists 57 vulnerable entries across NX701, NX102, NX1P2, NX1W, NJ501, NJ301 and NJ101 firmware, Sysmac Studio and the four NA5 terminals (NVD).

Which versions fix it?

CISA's ICSA-22-314-08, released on 2022-11-10, covers this CVE together with the hard-coded credentials flaw CVE-2022-34151 and lists the fixes: NX7 series 1.29 or later, NX1 series 1.50 or later, NJ501-1300, NJ501-1400 and NJ501-1500 1.49 or later, all other NJ models 1.50 or later, Sysmac Studio 1.50 or later and NA-series runtime 1.16 or later. Controller firmware comes through OMRON sales offices or distributors; Sysmac Studio updates through the installed Omron Automation Software AutoUpdate tool. CISA credits Reid Wightman of Dragos and points to OMRON advisory OMSR-2022-001 and to the joint advisory AA22-103A on tools built to attack ICS devices (CISA CSAF). JVN lists the same AA22-103A reference and says OMRON reported the issues to JPCERT/CC.

Why does it matter on the plant floor?

CISA's risk evaluation is that an attacker may bypass authentication in the communications connection process to log in and operate the controller without authorization, the same access Sysmac Studio or a terminal normally has. A related NJ/NX flaw, CVE-2022-33971, was published the same day. The older FINS replay issue CVE-2019-13533 is a different path that no firmware fixes. Our OMRON FINS protocol security guide covers the NJ/NX update thresholds next to the FINS controls.

Until every controller, Sysmac Studio installation and NA terminal is updated, CISA recommends firewalls that close unused ports and isolate the controllers from the IT network, VPN and multifactor authentication for remote access, and regular backups. CVE-2022-33208 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01919, the 80th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD description as quoted; NVD Primary CVSS v3.1 8.1 AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H; CWE-294; 57 vulnerable CPE entries across NX701, NX102, NX1P2, NX1W, NJ501, NJ301, NJ101 firmware, Sysmac Studio <=1.49, NA5 <=1.15; published 2022-07-04; CNA JPCERT/CC. — NVD
  • ICSA-22-314-08 (2022-11-10): CVE-2022-33208 CWE-294, CVSS v3 7.5 AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H; fixes NX7 1.29, NX1 1.50, NJ501-1300/1400/1500 1.49, other NJ 1.50, Sysmac Studio 1.50, NA runtime 1.16; Sysmac Studio via AutoUpdate; OMRON OMSR-2022-001; reference AA22-103A; reported by Reid Wightman (Dragos); risk evaluation: bypass authentication in the communications connection process to login and operate the controller products without authorization. — CISA ICSA-22-314-08 (CSAF)
  • JVNVU#97050784 (published 2022-07-01, updated 2022-11-08): CVE-2022-33208 CWE-294 CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H 7.5; references AA22-103A; OMRON reported to JPCERT/CC. — JPCERT/CC JVN
  • Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18. — CISA KEV
  • EPSS 0.01919, percentile 0.80255, dataset 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-22-314-08: Omron NJ/NX-series Machine Automation Controllers
  3. CISA CSAF: ICSA-22-314-08 (machine-readable advisory)
  4. JPCERT/CC JVNVU#97050784: Multiple vulnerabilities in OMRON products
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which versions fix CVE-2022-33208?

NX7 1.29 or later, NX1 1.50 or later, NJ501-1300/-1400/-1500 1.49 or later, other NJ models 1.50 or later, Sysmac Studio 1.50 or later and NA runtime 1.16 or later (per CISA ICSA-22-314-08).

Does updating the controller alone close CVE-2022-33208?

No. CISA lists Sysmac Studio 1.49 and earlier and NA5 terminals with runtime 1.15 and earlier as affected too, each with its own fixed version (per CISA ICSA-22-314-08 and NVD).

Why is NVD's score 8.1 and CISA's 7.5?

CISA and JPCERT/CC require user interaction (UI:R) in the vector; NVD's vector does not, which raises its score to 8.1 (per NVD, CISA and JVN).

Is CVE-2022-33208 in the CISA KEV catalog?

No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01919, the 80th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).