CVE-2018-5459 is an improper authentication flaw in the CODESYS 2.3 and 2.4 runtime that WAGO ships on PFC200 controllers. The runtime listens on TCP port 2455 by default, and unauthenticated packets to it can read, write or delete files and change the running PLC application. NVD scores it 9.8; CISA says WAGO fixed it with FW11.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
2.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-5459 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| WAGO PFC200 Series 750-8202, 750-8203, 750-8204, 750-8206, 750-8207 and 750-8208 (incl. /025-xxx and /040-001 variants), CODESYS 2.3.x/2.4.x runtime | cpe:2.3:o:wago:pfc200_firmware:*:*:*:*:*:*:*:* | Firmware before 02.07.07(10) (NVD and CISA ICSA-18-044-01); WAGO security patch released with FW11 (CISA ICSA-18-044-01) |
What does this mean for affected devices?
NVD describes the flaw as follows: "An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455." NVD's Primary score is CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-287; ICS-CERT, the CNA, published the record on 2018-02-13 (NVD, CVE record).
Which PFC200 models and firmware are affected?
CISA's advisory ICSA-18-044-01 (CSAF) lists PFC200 models 750-8202, 750-8203, 750-8204, 750-8206, 750-8207 and 750-8208, including their /025-000, /025-001, /025-002 and /040-001 variants, with "Firmware prior to 02.07.07(10)" and the CODESYS runtime versions 2.3.X and 2.4.X. NVD's CPE uses the same boundary: PFC200 firmware before 02.07.07(10). CISA states that "WAGO released a security patch with FW11". Reid Wightman of Dragos found the flaw in the CODESYS runtime, and T. Weber of SEC Consult reported it to WAGO.
Why is port 2455 a concern on older WAGO controllers?
Port 2455 is the programming and online port of the CODESYS 2.3 runtime (WAGO-I/O-PRO). On affected firmware it answers file and application commands without a login, so anyone who can reach the port can change the logic the controller runs. CISA's risk note for this advisory reads "Remotely exploitable/low skill level to exploit. Public exploits are available." Later WAGO advisories for CODESYS 2.3 flaws, covered in the WAGO PFC controller guide, repeat the advice to disable the CODESYS 2.3 port where it is not needed.
How do you fix or mitigate it?
Update PFC200 controllers to FW11 or later. CISA's first recommended practice is to "Restrict access to Port 2455"; keep it reachable only from named engineering workstations, keep the controller off the internet, and put the control network behind a firewall. The authentication bypass fix guide and the CODESYS runtime guide explain this class of runtime exposure. For the CODESYS V3 runtime that later WAGO firmware uses, see CVE-2019-9013 and CVE-2022-47390; the I/O-Check service on the same controllers has its own flaws such as CVE-2019-5074.
CVE-2018-5459 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.02676, the 86.2nd percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Modified; published 2018-02-13; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 7.5; CWE-287 (NVD and ICS-CERT); CPE pfc200_firmware before 02.07.07(10) on PFC200 hardware 750-8202 to 750-8208 variants; reference ICSA-18-044-01. — NVD
- CISA ICSA-18-044-01 CSAF (2018-02-13), read 2026-11-21: PFC200 750-8202, 8203, 8204, 8206, 8207, 8208 and variants, firmware prior to 02.07.07(10), CoDeSys 2.3.X and 2.4.X; CVSS v3.0 9.8, CWE-287; port 2455 open by default; WAGO released a security patch with FW11; restrict access to port 2455; risk note: public exploits are available; Reid Wightman (Dragos) discovered, T. Weber (SEC Consult) reported. — CISA CSAF ICSA-18-044-01
- CVE record (checked 2026-11-21): state PUBLISHED, CNA ICS-CERT (icscert), published 2018-02-13; CWE-287; affected WAGO PFC200 Series. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-21. — CISA KEV
- EPSS 0.02676, percentile 0.86153, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which WAGO firmware fixes CVE-2018-5459?
CISA ICSA-18-044-01 says WAGO released a security patch with FW11. NVD and CISA list PFC200 firmware before 02.07.07(10) as affected.
Which models are affected?
PFC200 Series 750-8202, 750-8203, 750-8204, 750-8206, 750-8207 and 750-8208, including the /025-000, /025-001, /025-002 and /040-001 variants, running the CODESYS 2.3.x or 2.4.x runtime (CISA ICSA-18-044-01).
What can an attacker do over port 2455?
Without authentication, read, write or delete arbitrary files and manipulate the PLC application during runtime by sending crafted TCP packets, per the NVD and CISA description. CISA notes that public exploits are available.
Is CVE-2018-5459 in the CISA KEV catalog?
No, not as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.02676 (86.2nd percentile) in the 2026-11-20 dataset.
Questions about this page?