CVE-2019-9013 is a credential-protection flaw in the CODESYS V3 runtime: without the TLS-based encrypted online communication, the CmpUserMgr login sends user credentials in a weakly protected form, so an attacker who can see the PLC's network traffic can capture and reuse them. It affects runtimes before 3.5.16.0, the fixed version. NVD scores it 8.8.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
0.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-9013 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| CODESYS Control for BeagleBone (CmpUserMgr component) | cpe:2.3:a:codesys:control_for_beaglebone_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control for emPC-A/iMX6 (CmpUserMgr component) | cpe:2.3:a:codesys:control_for_empc-a\/imx6_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control for IOT2000 (CmpUserMgr component) | cpe:2.3:a:codesys:control_for_iot2000_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control for Linux (CmpUserMgr component) | cpe:2.3:a:codesys:control_for_linux_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control for PFC100 (CmpUserMgr component) | cpe:2.3:a:codesys:control_for_pfc100_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control for PFC200 (CmpUserMgr component) | cpe:2.3:a:codesys:control_for_pfc200_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control for Raspberry Pi (CmpUserMgr component) | cpe:2.3:a:codesys:raspberry_pi:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control RTE V3, including RTE V3 (for Beckhoff CX) (CmpUserMgr component) | cpe:2.3:a:codesys:control_rte_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control Win V3 (CmpUserMgr component) | cpe:2.3:a:codesys:control_win_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Development System (V3 Simulation Runtime) (CmpUserMgr component) | cpe:2.3:a:codesys:development_system:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS HMI V3 (CmpUserMgr component) | cpe:2.3:a:codesys:hmi_sl:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control V3 Runtime System Toolkit (CmpUserMgr component) | cpe:2.3:a:codesys:runtime_toolkit:*:*:*:*:*:*:*:* | 3.0 up to (excluding) 3.5.16.0 (NVD); fixed in 3.5.16.0 (CODESYS Advisory 2019-08) |
| CODESYS Control for PLCnext (CmpUserMgr component) | — | all versions before 3.5.16.0 (CODESYS Advisory 2019-08); fixed in 3.5.16.0; no NVD CPE |
What does this mean for affected devices?
NVD's description: "The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport." It applies to all variants of the CODESYS V3 products that contain the CmpUserMgr component, regardless of CPU type or operating system. NVD's Primary score is CVSS v3.1 8.8 (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 5.8, with CWE-327 (use of a broken or risky cryptographic algorithm). The attack vector is Adjacent: the attacker needs a position on the network path to the controller. NVD's CPE configuration covers twelve CODESYS products from 3.0 up to, but excluding, 3.5.16.0. The record was published on 2019-08-15 (NVD).
Which CODESYS products and devices are affected?
CODESYS Advisory 2019-08 (version 7.0, 29 March 2021) lists every CODESYS V3 product before 3.5.16.0 that contains CmpUserMgr: Control for BeagleBone, emPC-A/iMX6, IOT2000, Linux, PLCnext, PFC100, PFC200 and Raspberry Pi, Control RTE V3 (also for Beckhoff CX), Control Win V3, the V3 Simulation Runtime in the Development System, the Control V3 Runtime System Toolkit and HMI V3. NVD's CPE list omits Control for PLCnext, which the CODESYS advisory names. The same advisory covers four related CVEs, including CVE-2019-9011 (user name enumeration) and CVE-2020-12069 (weak password hashing), and rates the set high with CVSS v3.0 8.8.
The Runtime System Toolkit is what device makers build into their own PLC, drive and HMI firmware, so the affected list reaches well past CODESYS-branded products. CISA republished the issue as ICSA-19-213-04 (released 2019-08-01, Update A 2020-05-14), scoring it 8.8 with CWE-522 (insufficiently protected credentials) and summarising the risk as "an attacker with access to PLC traffic" obtaining user credentials (CISA CSAF).
Why does an old credential flaw still matter?
Because it unlocks the authenticated bugs found later. Microsoft's 2023 CODESYS research used CVE-2019-9013 "to perform a replay attack against the PLC using the unsecured username and password's hash that were sent during the sign-in process", then exploited buffer overflows it had found in the CODESYS protocol servers, a set that includes the CmpTraceMgr stack overflow CVE-2022-47390, to take full control of a Schneider Electric Modicon TM251 and a WAGO PFC200. Those 2023 bugs, and the denial-of-service flaw CVE-2022-47378, need a login; a captured login meets that condition. Our CODESYS runtime vulnerabilities guide explains how to find the runtime version inside vendor firmware.
How do you fix it?
CODESYS fixed it in 3.5.16.0, which redesigned the online user management and the password transport. Clients must also be at 3.5.16.0 or later to use the new mechanism: the Development System, Edge Gateway, OPC Server and PLCHandler SDK. From 3.5.17.0 (the base of the SL products' 4.1.0.0) the online user management is enforced by default. For devices with CODESYS inside, the fix arrives in the device vendor's firmware.
If an update is out of reach, CODESYS's advice is to activate and use the encrypted online communication, which protects the password with TLS "independent of the weak password transmission", to keep user management on, and to limit network access to the controller with firewalls and VPNs. The unauthenticated web server overflow CVE-2020-10245 in the same runtime generation needs no credentials at all, so patching only this flaw is not enough.
CVE-2019-9013 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.00303, the 23rd percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: non-TLS based encryption, user credentials insufficiently protected during transport; CmpUserMgr; NVD Primary CVSS v3.1 8.8 AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS v2 5.8; CWE-327; 12 CODESYS CPEs from 3.0 up to excluding 3.5.16.0; published 2019-08-15; status Modified. — NVD
- CODESYS Advisory 2019-08 v7.0 (29 March 2021): all CODESYS V3 products before 3.5.16.0 with CmpUserMgr incl. Control for PLCnext; CVSS v3.0 8.8; fixed in 3.5.16.0; clients need 3.5.16.0; user management enforced by default from 3.5.17.0 (base of SL 4.1.0.0); mitigation: encrypted online communication, user management, firewalls, VPN. — CODESYS Advisory 2019-08
- ICSA-19-213-04 (Update A), released 2019-08-01, current 2020-05-14: CWE-522, CVSS v3 8.8; attacker with access to PLC traffic could obtain user credentials; fix 3.5.16.0. — CISA CSAF ICSA-19-213-04
- Microsoft used CVE-2019-9013 to replay the captured username and password hash and log in to a Schneider Electric Modicon TM251 and a WAGO PFC200 before exploiting the 2022 CODESYS buffer overflows. — Microsoft Security Blog
- Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18. — CISA KEV
- EPSS 0.00303, percentile 0.23359, dataset 2026-11-17. — FIRST EPSS

Related advisories
Sources
- NVD
- CODESYS Advisory 2019-08: Security update for CODESYS Control V3 password handling
- CISA ICS Advisory ICSA-19-213-04: 3S-Smart Software Solutions GmbH CODESYS V3 (Update A)
- CISA CSAF: ICSA-19-213-04 (machine-readable advisory)
- Microsoft Security Blog: Multiple high severity vulnerabilities in CODESYS V3 SDK (August 2023)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which CODESYS versions fix CVE-2019-9013?
Version 3.5.16.0 and later of the CODESYS V3 runtime systems, with the CODESYS clients (Development System, Edge Gateway, OPC Server, PLCHandler SDK) also at 3.5.16.0 or later to use the new password transport. On devices that embed CODESYS, the fix comes in the device vendor's firmware (per CODESYS Advisory 2019-08).
What does an attacker need to exploit CVE-2019-9013?
Access to the online communication between a CODESYS client and the controller, which is why NVD scores the attack vector as Adjacent. With that traffic the attacker can capture the login and reuse it; Microsoft replayed a captured username and password hash this way in its 2023 research (per NVD, CODESYS Advisory 2019-08 and Microsoft).
Does encrypted communication protect against CVE-2019-9013 without updating?
Yes, per CODESYS: the TLS-based encrypted online communication protects the password transmission independently of the weak mechanism, and CODESYS recommends activating it whenever possible, together with online user management and firewalls, if the update is not applied.
Is CVE-2019-9013 in the CISA KEV catalog?
No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.00303, the 23rd percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?