Security Advisory

CVE-2018-18995: ABB Pluto GATE-E1/E2 Missing Auth

Last updated:
  • CVE-2018-18995

CVE-2018-18995 is a missing authentication flaw in ABB's GATE-E1 and GATE-E2 Ethernet gateways for Pluto safety PLCs: the telnet and web admin interfaces cannot be password protected, so anyone who reaches them can reset the device, change registers or reconfigure it. NVD and CISA score it 9.8, ABB 9.4. Both products are end of life with no fix.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

2.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-18995 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
ABB GATE-E1 (Pluto safety PLC Ethernet gateway)cpe:2.3:o:abb:gate-e1_firmware:*:*:*:*:*:*:*:*All versions (NVD, CISA ICSA-18-352-01, ABB ABBVU-EPPC-3099-SE-002); end of life since 2013, no fix
ABB GATE-E2 (Pluto safety PLC Ethernet gateway)cpe:2.3:o:abb:gate-e2_firmware:*:*:*:*:*:*:*:*All versions (NVD, CISA ICSA-18-352-01, ABB ABBVU-EPPC-3099-SE-002); end of life since October 2018, no fix

What does this mean for affected devices?

The CVE record from CISA says that "Pluto Safety PLC Gateway Ethernet devices ABB GATE-E1 and GATE-E2 all versions do not allow authentication to be configured on administrative telnet or web interfaces, which could enable various effects vectors, including conducting device resets, reading or modifying registers, and changing configuration settings such as IP addresses." NVD's Primary score is 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5), the same 9.8 vector CISA calculated in its advisory. NVD and CISA both map it to CWE-306, missing authentication for a critical function (NVD, CVE record).

ABB scores it lower in its own cyber security advisory ABBVU-EPPC-3099-SE-002 (document 2CMT2018-005751, revision B, 2018-12-21): base 9.4, AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H, with a temporal score of 9.4. The only difference is low rather than high confidentiality impact. ABB explains the cause plainly: "At the time when the product was developed, it was not designed to provide security services such as authentication."

Which ABB devices are affected?

The GATE-E1 and GATE-E2 are Ethernet gateways for ABB's Pluto safety PLCs, and every product version of both is affected. CISA's ICSA-18-352-01, released on 2018-12-18 and never revised, lists the GATE-E1 as end of life since 2013 and the GATE-E2 as end of life since October 2018. It names Critical Manufacturing as the sector, worldwide deployment and Sweden as the company headquarters. Nelson Berg of Applied Risk reported the flaw. ABB says access to the administrative interface lets an attacker continuously reset the gateway, read or modify registers and change its configuration, such as its IP address, so the gateway can become unreachable. Because the gateway carries data from a safety PLC, a changed register or a reset can disturb the plant systems that read from it.

The same CISA advisory covers one sibling, CVE-2018-18997 (CWE-79, CISA 7.1): an unauthenticated attacker can store an HTML or JavaScript payload in device properties through the web interface, which then runs in a visitor's browser. ABB published it separately as ABBVU-EPPC-3099-SE-003.

How do you fix CVE-2018-18995?

There is no firmware fix. ABB states that the products "will not be updated with new firmware as products are in end-of-life (EOL)" and that customers who bought them received an email with instructions to secure an installation. The mitigations in ABB's advisory and in CISA's CSAF copy are network and physical:

  • separate the control network from other networks with a firewall and managed switches that expose a minimal number of ports;
  • give the gateway no direct connection to the internet;
  • physically protect the control system from unauthorized personnel;
  • scan portable computers and removable media for malware before connecting them.

In practice, place each GATE-E1 or GATE-E2 in a zone that only the systems which need its data can reach, block telnet and web access to it from everywhere else, and plan a hardware replacement. The authentication bypass fix guide covers how vendors add authentication to management interfaces, and the IEC 61511 safety instrumented systems guide covers protecting safety controllers and their gateways. Other ABB controller flaws are collected in the ABB guide, for example the AC500 web server denial of service CVE-2020-24686; another safety controller credential flaw is the MELSEC Safety CPU issue CVE-2021-20597.

Is CVE-2018-18995 exploited?

CVE-2018-18995 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.02646, the 86.34th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting these vulnerabilities, and ABB said that, when the advisory was first issued, it had no information that the flaw had been exploited and that it had not been publicly disclosed.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2019-01-03; [email protected] Primary CVSS 3.0 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5; CWE-306 ([email protected] Primary and ics-cert Secondary); CPEs abb gate-e1_firmware and gate-e2_firmware, all versions. — NVD
  • CISA ICSA-18-352-01 (initial release 2018-12-18, single revision): ABB GATE-E1 (EOL 2013) and GATE-E2 (EOL Oct 2018); CVE-2018-18995 CWE-306 CVSS 3.0 9.8; sibling CVE-2018-18997 CWE-79 7.1; ABB will not release updated firmware; defence-in-depth mitigations; ABB advisories ABBVU-EPPC-3099-SE-002 and -003; reported by Nelson Berg (Applied Risk); sector Critical Manufacturing, HQ Sweden; no known public exploits. — CISA CSAF
  • ABB cyber security advisory ABBVU-EPPC-3099-SE-002 (doc 2CMT2018-005751, rev B, 2018-12-21): GATE-E2 and GATE-E1 all product versions; CVSS v3 base 9.4, temporal 9.4, AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H/E:H/RL:U/RC:C; no new firmware as products are EOL, customers emailed securing instructions; product not designed to provide authentication; not publicly disclosed and no exploitation known when issued; thanks Nelson Berg (Applied Risk). — ABB
  • CVE.org record (CNA icscert): published 2019-01-03; product 'ABB GATE-E1 and GATE-E2', all versions; CWE-306; no CVSS in the record. — CVE.org
  • CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2018-18995 not listed; checked 2026-11-27. — CISA KEV
  • EPSS 0.02646, percentile 0.86344, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. ABB ABBVU-EPPC-3099-SE-002: Vulnerability in GATE E2 - No Access Control (2CMT2018-005751)
  3. CISA ICSA-18-352-01: ABB GATE-E2 (CSAF)
  4. CISA ICSA-18-352-01 advisory page
  5. CVE.org record CVE-2018-18995
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which ABB products are affected by CVE-2018-18995?

All versions of the ABB GATE-E1 and GATE-E2 Ethernet gateways for Pluto safety PLCs. CISA lists the GATE-E1 as end of life since 2013 and the GATE-E2 since October 2018 (per CISA ICSA-18-352-01 and ABB ABBVU-EPPC-3099-SE-002).

Is there a firmware update for CVE-2018-18995?

No. ABB will not release new firmware because both gateways are end of life. It recommends defence in depth: firewalled, separated control networks with few exposed ports, no direct internet connection, physical protection and scanning of portable media (per ABB ABBVU-EPPC-3099-SE-002 and CISA ICSA-18-352-01).

Why does ABB score CVE-2018-18995 9.4 and NVD 9.8?

ABB rates the confidentiality impact as low, giving 9.4; NVD and CISA rate it high, giving 9.8. All three agree on a network attack with no privileges or user interaction and high integrity and availability impact (per NVD, CISA ICSA-18-352-01 and ABB ABBVU-EPPC-3099-SE-002).

Is CVE-2018-18995 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02646, the 86.34th percentile, in the 2026-11-26 dataset (per CISA KEV and FIRST EPSS).