Security Advisory

CVE-2017-7903: MicroLogix 1100/1400 Weak Web Password

Last updated:
  • CVE-2017-7903

CVE-2017-7903 is a weak password requirement in the web server of Rockwell Automation Allen-Bradley MicroLogix 1100 and 1400 programmable logic controllers, version 16.00 and earlier: the password is numeric with a small maximum length, so it can be guessed. NVD scores it 9.8. MicroLogix 1400 Series B is fixed in FRN 21.00; for the other models Rockwell advises disabling the web server.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

3.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2017-7903 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Allen-Bradley MicroLogix 1100 (1763-L16AWA, -L16BBB, -L16BWA, -L16DWD), Series A and Bcpe:2.3:a:rockwellautomation:1763-l16awa_series_b:*:*:*:*:*:*:*:*16.00 and earlier; no fixed firmware, disable the web server (CISA ICSA-17-115-04)
Allen-Bradley MicroLogix 1400 Series A (1766-L32AWA, -L32AWAA, -L32BWA, -L32BWAA, -L32BXB, -L32BXBA)cpe:2.3:a:rockwellautomation:1766-l32awa_series_a:*:*:*:*:*:*:*:*16.00 and earlier; no fixed firmware, disable the web server (CISA ICSA-17-115-04)
Allen-Bradley MicroLogix 1400 Series B (same catalog numbers)cpe:2.3:a:rockwellautomation:1766-l32awa_series_b:*:*:*:*:*:*:*:*16.00 and earlier; fixed in FRN 21.00 (CISA ICSA-17-115-04)

What does this mean for affected devices?

What is CVE-2017-7903?

NVD describes "a Weak Password Requirements issue" in Allen-Bradley MicroLogix 1100 controllers 1763-L16AWA, -L16BBB, -L16BWA and -L16DWD and MicroLogix 1400 controllers 1766-L32AWA, -L32BWA, -L32BWAA, -L32BXB, -L32BXBA and -L32AWAA, Series A and B, version 16.00 and prior: "The affected products use a numeric password with a small maximum character size for the password." NVD's Primary score is CVSS v3.0 9.8 (critical), vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CVSS v2 5.0 and CWE-326, Inadequate Encryption Strength, as NVD's weakness; CISA's CNA entry uses CWE-521, Weak Password Requirements, and the CISA ADP entry on NVD gives the same 9.8 under CVSS v3.1 (NVD, CVE record). NVD's configuration lists each catalog number, Series A and B, up to and including 16.000.

Which MicroLogix controllers are affected?

CISA posted ICSA-17-115-04 to its secure portal on 2017-04-25 and released it publicly on 2017-05-23. The CISA CSAF record lists the ten MicroLogix 1100 and 1400 catalog numbers above, Series A and B, version 16.00 and earlier, and names the Food and Agriculture and Water and Wastewater sectors. CISA scores CVE-2017-7903 at 9.8 with the same vector as NVD.

The advisory has four sibling CVEs. The most serious is CVE-2017-7898 (CWE-307, 9.8): the web server does not limit failed login attempts, which is what makes a short numeric password practical to guess. The others are CVE-2017-7901 and CVE-2017-7902 (5.4 each, predictable values and nonce reuse) and CVE-2017-7899 (3.1, information exposure). CISA credits Rockwell Automation, David Formby and Raheem Beyah of Georgia Tech, Fortiphyd Logic and Ilya Karpov of Positive Technologies, and knew of no public exploits that specifically targeted these flaws.

How do I fix CVE-2017-7903?

CISA quotes Rockwell: it "has released a new firmware version for the Allen-Bradley MicroLogix 1400 Series B controllers, FRN 21.00, to address the identified vulnerabilities." There is no firmware fix for the MicroLogix 1100 or the 1400 Series A. For those, Rockwell's compensating controls are:

  • disable the web server, which is enabled by default, using Rockwell knowledge base article 732398
  • set the controller to RUN with the LCD soft keyswitch, which prevents the web server being re-enabled while in that mode
  • keep the controller off the internet and behind firewalls, with VPN for any remote access

Rockwell recommends disabling the web server even on updated controllers if it is not needed. The design fix, long passphrases with lockout or rate limiting on every login path, is covered in our weak cryptography fix guide and our Rockwell Logix controller guide.

Other MicroLogix advisories on this site: CVE-2017-7924 (MicroLogix 1100 PCCC denial of service), CVE-2017-16740 (MicroLogix 1400 Modbus TCP overflow) and CVE-2020-6990 (hard-coded key).

Is CVE-2017-7903 exploited?

CVE-2017-7903 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.03757, the 91st percentile, in the 2026-11-26 dataset, as of 2026-11-27 (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • Weak password requirements in MicroLogix 1100 (1763-L16AWA/BBB/BWA/DWD) and 1400 (1766-L32AWA/BWA/BWAA/BXB/BXBA/AWAA), Series A and B, 16.00 and prior; numeric password with small maximum size; NVD Primary CVSS v3.0 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; v2 5.0; NVD CWE-326, CNA CWE-521; CISA ADP CVSS v3.1 9.8; CPEs per catalog number and series up to 16.000. — NVD
  • ICSA-17-115-04 posted 2017-04-25 (portal), released 2017-05-23; CVE-2017-7898 (CWE-307, 9.8), 7899 (3.1), 7901 (5.4), 7902 (5.4), 7903 (CWE-521, 9.8); FRN 21.00 for MicroLogix 1400 Series B; no firmware for 1100 or 1400 Series A, disable web server (KB 732398), RUN mode via LCD soft keyswitch; sectors Food and Agriculture, Water and Wastewater; researchers credited; no known public exploits. — CISA ICSA-17-115-04 (CSAF)
  • Not in the KEV catalog, version 2026.11.25, checked 2026-11-27. — CISA KEV
  • EPSS 0.03757, 91st percentile, 2026-11-26 dataset. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-17-115-04: Rockwell Automation Allen-Bradley MicroLogix 1100 and 1400
  3. CISA CSAF record for ICSA-17-115-04
  4. CVE.org record
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is there a firmware fix for CVE-2017-7903?

Only for the MicroLogix 1400 Series B, in FRN 21.00. The MicroLogix 1100 and 1400 Series A get no firmware fix; Rockwell's mitigation is to disable the web server and lock it off with the RUN keyswitch mode (per CISA ICSA-17-115-04).

Why is a short numeric password scored 9.8?

Because the web server is reachable over the network without prior authentication and a numeric password with a small maximum length can be guessed; the sibling CVE-2017-7898 adds that failed login attempts are not limited. Once in, an attacker has full control of the controller's web functions (per NVD and CISA).

How do I disable the MicroLogix web server?

Rockwell knowledge base article 732398 describes how to disable the web server on the MicroLogix 1100 and 1400. Setting the controller to RUN with the LCD soft keyswitch then prevents it from being re-enabled (per CISA ICSA-17-115-04).

Is CVE-2017-7903 in the CISA KEV catalog?

No. It is not listed in catalog version 2026.11.25, checked 2026-11-27, and FIRST EPSS gives it 0.03757, the 91st percentile, in the 2026-11-26 dataset (per CISA KEV and FIRST EPSS).